SPEC: 10004

TFN/TFFN Copper SPEC10004

600 Volt. Copper Conductor. PVC Insulation/Nylon Sheath. Heat, Moisture, Oil, and Gasoline Resistant II. Also Rated MTW and AWM.

Download Category Specifications
PDF Excel Table

Application & Features

APPLICATION
Southwire Type TFN/TFFN or MTW or AWM may be used as fixture wire, machine tool wiring, or appliance wiring material as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. Allowable temperatures are as follows:

- TFN/TFFN- Dry locations not to exceed 90°C
- AWM- When rated as appliance wiring material in dry locations, conductor temperatures not to exceed 105°C
- MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)

FEATURES
- Gasoline and Oil Resistant II
- MTW- Stranded Constructions Only
- RoHS Compliant

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
18 AWG 18 AWG
1 1
Solid Solid
0.040 0.10
15 0.38
5 0.13
0.080 0.20
4 6
6 9
More Options
18 AWG 18 AWG
1 1
16 16
0.045 0.11
15 0.38
5 0.13
0.085 0.22
4 6
7 10
More Options
16 AWG 16 AWG
1 1
Solid Solid
0.050 0.13
15 0.38
5 0.13
0.090 0.23
7 10
10 15
More Options
16 AWG 16 AWG
1 1
26 26
0.059 0.15
15 0.38
5 0.13
0.101 0.26
7 10
10 15

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
18 AWG 18 AWG
1 1
0.3 0.76
6.669 9.92
8.035 11.96
0.036 0.05
- -
6 6
More Options
18 AWG 18 AWG
1 1
0.3 0.76
7.148 10.64
8.613 12.82
0.036 0.05
- -
6 6
More Options
16 AWG 16 AWG
1 1
0.4 1.02
4.181 6.22
5.037 7.50
0.033 0.05
- -
8 8
More Options
16 AWG 16 AWG
1 1
0.4 1.02
4.487 6.68
5.406 8.05
0.033 0.05
- -
8 8

* Ampacities based on 2023 NEC Table 402.5.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Size (Strand) Black Red Blue White Brown Orange Yellow Gray Pink Purple Tan Green
18 (Solid) 18 (Solid)
269779
269795
269803
269787
269845
269837
269829
269878
269860
269811
16 (Solid) 16 (Solid)
269886
269902
269910
269894
269951
269944
269936
269985
457241
269977
269928
18 (16) 18 (16)
270215
270231
270249
270223
270280
270272
270264
270314
270298
270306
270256
16 (26) 16 (26)
270322
270348
270355
270330
270397
270389
270371
270421
270405
270413
297531
270363

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 66 Fixture Wire
  • UL 758 Standard for Appliance Wiring Material
  • UL 1063 Machine Tool Wiring (MTW)

Construction

  1. Conductor: Solid soft drawn bare copper per ASTM B3 for TFN. Class K bunch-stranded soft drawn bare copper per ASTM B174 for TFFN.
  2. Insulation: Heat and moisture resistant PVC
  3. Sheath:Nylon