ACSR (Aluminum Conductor, Steel Reinforced) is a concentrically stranded conductor consisting of one or more layers of hard-drawn aluminum (1350-H19) wires surrounding a galvanized (GA) or mischmetal (MA) steel core. The aluminum strands provide efficient electrical conductivity, while the steel core supplies high tensile strength and improved sag performance. ACSR is widely used for overhead transmission and distribution applications where a combination of ampacity, strength, and economical design is required.
Continuous operating temperature - 75°C
Emergency operating temperature - 100°C
|
Stock Number Stranding Diameter DC Resistance @ 20°C |
Code Word Cross-Sectional Area Weight |
Conductor Size Layers of Al Rated Breaking Strength |
||||||||||||||
|
Individual Strands
Individual Strands
|
Steel Core
Steel Core
|
Complete Conductor
Complete Conductor
|
||||||||||||||
|
Al
Al
|
Total
Total
|
Al
Al
|
St
St
|
Al
Al
|
Total
Total
|
Std
Std
|
HS
HS
|
UHS
UHS
|
||||||||
|
AWG/kcmil
AWG/kcmil
|
Al/St
Al/St
|
in²
in²
|
in²
in²
|
in
in
|
in
in
|
in
in
|
in
in
|
lb/1000ft
lb/1000ft
|
lb/1000ft
lb/1000ft
|
lb
lb
|
lb
lb
|
lb
lb
|
Ω/mile
Ω/mile
|
|||
|
TBA
TBA
|
Turkey
Turkey
|
6
6
|
6/1
6/1
|
0.0206
0.0206
|
0.0240
0.0240
|
1
1
|
0.0661
0.0661
|
0.0661
0.0661
|
0.0661
0.0661
|
0.198
0.198
|
24.46
24.46
|
35.92
35.92
|
1,190
1,190
|
1,260
1,260
|
1,320
1,320
|
3.3884
3.3884
|
|
TBA
TBA
|
Thrush
Thrush
|
5
5
|
6/1
6/1
|
0.0260
0.0260
|
0.0303
0.0303
|
1
1
|
0.0743
0.0743
|
0.0743
0.0743
|
0.0743
0.0743
|
0.223
0.223
|
30.88
30.88
|
45.38
45.38
|
1,490
1,490
|
1,570
1,570
|
1,660
1,660
|
2.6845
2.6845
|
|
TBA
TBA
|
Swan
Swan
|
4
4
|
6/1
6/1
|
0.0328
0.0328
|
0.0383
0.0383
|
1
1
|
0.0834
0.0834
|
0.0834
0.0834
|
0.0834
0.0834
|
0.250
0.250
|
38.95
38.95
|
57.50
57.50
|
1,860
1,860
|
1,970
1,970
|
2,070
2,070
|
2.1273
2.1273
|
|
TBA
TBA
|
Swanate
Swanate
|
4
4
|
7/1
7/1
|
0.0328
0.0328
|
0.0411
0.0411
|
1
1
|
0.0772
0.0772
|
0.1029
0.1029
|
0.1029
0.1029
|
0.257
0.257
|
38.95
38.95
|
66.94
66.94
|
2,360
2,360
|
2,520
2,520
|
2,680
2,680
|
2.1040
2.1040
|
|
TBA
TBA
|
Swallow
Swallow
|
3
3
|
6/1
6/1
|
0.0413
0.0413
|
0.0482
0.0482
|
1
1
|
0.0936
0.0936
|
0.0936
0.0936
|
0.0936
0.0936
|
0.281
0.281
|
49.05
49.05
|
72.32
72.32
|
2,290
2,290
|
2,420
2,420
|
2,560
2,560
|
1.6896
1.6896
|
|
TBA
TBA
|
Sparrow
Sparrow
|
2
2
|
6/1
6/1
|
0.0522
0.0522
|
0.0609
0.0609
|
1
1
|
0.1052
0.1052
|
0.1052
0.1052
|
0.1052
0.1052
|
0.316
0.316
|
61.99
61.99
|
91.33
91.33
|
2,850
2,850
|
3,010
3,010
|
3,180
3,180
|
1.3369
1.3369
|
|
TBA
TBA
|
Sparate
Sparate
|
2
2
|
7/1
7/1
|
0.0522
0.0522
|
0.0655
0.0655
|
1
1
|
0.0974
0.0974
|
0.1299
0.1299
|
0.1299
0.1299
|
0.325
0.325
|
61.99
61.99
|
106.8
106.8
|
3,640
3,640
|
3,900
3,900
|
4,150
4,150
|
1.3218
1.3218
|
|
TBA
TBA
|
Robin
Robin
|
1
1
|
6/1
6/1
|
0.0657
0.0657
|
0.0767
0.0767
|
1
1
|
0.1181
0.1181
|
0.1181
0.1181
|
0.1181
0.1181
|
0.354
0.354
|
78.02
78.02
|
115.1
115.1
|
3,550
3,550
|
3,760
3,760
|
3,980
3,980
|
1.0621
1.0621
|
|
TBA
TBA
|
Raven
Raven
|
1/0
1/0
|
6/1
6/1
|
0.0830
0.0830
|
0.0968
0.0968
|
1
1
|
0.1327
0.1327
|
0.1327
0.1327
|
0.1327
0.1327
|
0.398
0.398
|
98.57
98.57
|
145.1
145.1
|
4,380
4,380
|
4,650
4,650
|
4,910
4,910
|
0.8408
0.8408
|
|
TBA
TBA
|
Quail
Quail
|
2/0
2/0
|
6/1
6/1
|
0.1045
0.1045
|
0.1219
0.1219
|
1
1
|
0.1489
0.1489
|
0.1489
0.1489
|
0.1489
0.1489
|
0.447
0.447
|
124.1
124.1
|
182.8
182.8
|
5,300
5,300
|
5,720
5,720
|
6,050
6,050
|
0.6678
0.6678
|
|
TBA
TBA
|
Bobwhite
Bobwhite
|
2/0
2/0
|
7/1
7/1
|
0.1045
0.1045
|
0.1311
0.1311
|
1
1
|
0.1379
0.1379
|
0.1839
0.1839
|
0.1839
0.1839
|
0.460
0.460
|
124.1
124.1
|
213.8
213.8
|
6,840
6,840
|
7,480
7,480
|
7,990
7,990
|
0.6603
0.6603
|
|
TBA
TBA
|
Pigeon
Pigeon
|
3/0
3/0
|
6/1
6/1
|
0.1317
0.1317
|
0.1537
0.1537
|
1
1
|
0.1672
0.1672
|
0.1672
0.1672
|
0.1672
0.1672
|
0.502
0.502
|
156.4
156.4
|
230.6
230.6
|
6,620
6,620
|
7,150
7,150
|
7,570
7,570
|
0.5299
0.5299
|
|
TBA
TBA
|
Penguin
Penguin
|
4/0
4/0
|
6/1
6/1
|
0.1662
0.1662
|
0.1939
0.1939
|
1
1
|
0.1878
0.1878
|
0.1878
0.1878
|
0.1878
0.1878
|
0.563
0.563
|
197.4
197.4
|
290.8
290.8
|
8,350
8,350
|
9,010
9,010
|
9,550
9,550
|
0.4199
0.4199
|
|
TBA
TBA
|
Vulture
Vulture
|
4/0
4/0
|
5/1
5/1
|
0.1662
0.1662
|
0.1810
0.1810
|
1
1
|
0.2057
0.2057
|
0.1371
0.1371
|
0.1371
0.1371
|
0.549
0.549
|
197.4
197.4
|
247.3
247.3
|
6,380
6,380
|
6,660
6,660
|
6,950
6,950
|
0.4242
0.4242
|
|
TBA
TBA
|
Barbet
Barbet
|
4/0
4/0
|
18/1
18/1
|
0.1661
0.1661
|
0.1753
0.1753
|
2
2
|
0.1084
0.1084
|
0.1084
0.1084
|
0.1084
0.1084
|
0.542
0.542
|
198.2
198.2
|
229.2
229.2
|
5,660
5,660
|
5,830
5,830
|
6,010
6,010
|
0.4284
0.4284
|
|
TBA
TBA
|
Bantam
Bantam
|
13.125
13.125
|
3/4
3/4
|
0.0103
0.0103
|
0.0240
0.0240
|
0.5
0.5
|
0.0661
0.0661
|
0.0661
0.0661
|
---
---
|
0.198
0.198
|
12.23
12.23
|
58.93
58.93
|
2,790
2,790
|
3,050
3,050
|
3,310
3,310
|
5.8959
5.8959
|
|
TBA
TBA
|
Magpie
Magpie
|
20.87
20.87
|
3/4
3/4
|
0.0164
0.0164
|
0.0383
0.0383
|
0.5
0.5
|
0.0834
0.0834
|
0.0834
0.0834
|
---
---
|
0.250
0.250
|
19.48
19.48
|
94.14
94.14
|
4,420
4,420
|
4,840
4,840
|
5,260
5,260
|
3.7008
3.7008
|
|
TBA
TBA
|
Shrike
Shrike
|
33.185
33.185
|
3/4
3/4
|
0.0261
0.0261
|
0.0609
0.0609
|
0.5
0.5
|
0.1052
0.1052
|
0.1052
0.1052
|
---
---
|
0.316
0.316
|
31.00
31.00
|
149.6
149.6
|
6,830
6,830
|
7,490
7,490
|
8,160
8,160
|
2.3259
2.3259
|
|
TBA
TBA
|
Snipe
Snipe
|
52.77
52.77
|
3/4
3/4
|
0.0414
0.0414
|
0.0966
0.0966
|
0.5
0.5
|
0.1326
0.1326
|
0.1326
0.1326
|
---
---
|
0.398
0.398
|
49.16
49.16
|
237.4
237.4
|
10,500
10,500
|
11,600
11,600
|
12,700
12,700
|
1.4663
1.4663
|
|
TBA
TBA
|
Albatross
Albatross
|
54.95
54.95
|
7/1
7/1
|
0.0432
0.0432
|
0.0542
0.0542
|
1
1
|
0.0886
0.0886
|
0.1181
0.1181
|
0.1181
0.1181
|
0.295
0.295
|
51.30
51.30
|
88.39
88.39
|
3,080
3,080
|
3,300
3,300
|
3,510
3,510
|
1.5972
1.5972
|
|
TBA
TBA
|
Shoebill
Shoebill
|
57.50
57.50
|
3/4
3/4
|
0.0451
0.0451
|
0.1053
0.1053
|
0.5
0.5
|
0.1384
0.1384
|
0.1384
0.1384
|
---
---
|
0.415
0.415
|
53.56
53.56
|
258.8
258.8
|
11,500
11,500
|
12,600
12,600
|
13,800
13,800
|
1.3458
1.3458
|
|
TBA
TBA
|
Loon
Loon
|
66.54
66.54
|
3/4
3/4
|
0.0522
0.0522
|
0.1219
0.1219
|
0.5
0.5
|
0.1489
0.1489
|
0.1489
0.1489
|
---
---
|
0.447
0.447
|
61.99
61.99
|
299.6
299.6
|
12,600
12,600
|
14,300
14,300
|
15,600
15,600
|
1.1627
1.1627
|
|
TBA
TBA
|
Grouse
Grouse
|
80.00
80.00
|
8/1
8/1
|
0.0628
0.0628
|
0.0846
0.0846
|
1
1
|
0.1000
0.1000
|
0.1667
0.1667
|
0.1667
0.1667
|
0.367
0.367
|
74.95
74.95
|
148.5
148.5
|
5,190
5,190
|
5,710
5,710
|
6,130
6,130
|
1.0909
1.0909
|
|
TBA
TBA
|
Petrel
Petrel
|
101.8
101.8
|
12/7
12/7
|
0.0799
0.0799
|
0.1265
0.1265
|
1
1
|
0.0921
0.0921
|
0.0921
0.0921
|
0.2763
0.2763
|
0.461
0.461
|
95.82
95.82
|
253.6
253.6
|
10,400
10,400
|
11,200
11,200
|
12,100
12,100
|
0.8364
0.8364
|
|
TBA
TBA
|
Minorca
Minorca
|
110.8
110.8
|
12/7
12/7
|
0.0870
0.0870
|
0.1378
0.1378
|
1
1
|
0.0961
0.0961
|
0.0961
0.0961
|
0.2883
0.2883
|
0.481
0.481
|
104.3
104.3
|
276.3
276.3
|
11,300
11,300
|
12,200
12,200
|
13,200
13,200
|
0.7681
0.7681
|
|
TBA
TBA
|
Leghorn
Leghorn
|
134.6
134.6
|
12/7
12/7
|
0.1057
0.1057
|
0.1674
0.1674
|
1
1
|
0.1059
0.1059
|
0.1059
0.1059
|
0.3177
0.3177
|
0.530
0.530
|
126.8
126.8
|
335.7
335.7
|
13,600
13,600
|
14,800
14,800
|
16,000
16,000
|
0.6322
0.6322
|
|
TBA
TBA
|
Guinea
Guinea
|
159.0
159.0
|
12/7
12/7
|
0.1249
0.1249
|
0.1977
0.1977
|
1
1
|
0.1151
0.1151
|
0.1151
0.1151
|
0.3453
0.3453
|
0.576
0.576
|
149.8
149.8
|
396.3
396.3
|
16,000
16,000
|
17,400
17,400
|
18,800
18,800
|
0.5351
0.5351
|
|
TBA
TBA
|
Dotterel
Dotterel
|
176.9
176.9
|
12/7
12/7
|
0.1389
0.1389
|
0.2199
0.2199
|
1
1
|
0.1214
0.1214
|
0.1214
0.1214
|
0.3642
0.3642
|
0.607
0.607
|
166.6
166.6
|
440.8
440.8
|
17,300
17,300
|
18,900
18,900
|
20,400
20,400
|
0.4811
0.4811
|
|
TBA
TBA
|
Dorking
Dorking
|
190.8
190.8
|
12/7
12/7
|
0.1499
0.1499
|
0.2373
0.2373
|
1
1
|
0.1261
0.1261
|
0.1261
0.1261
|
0.3783
0.3783
|
0.631
0.631
|
179.8
179.8
|
475.7
475.7
|
18,700
18,700
|
20,400
20,400
|
22,100
22,100
|
0.4458
0.4458
|
|
TBA
TBA
|
Auk
Auk
|
203.0
203.0
|
8/7
8/7
|
0.1594
0.1594
|
0.2025
0.2025
|
1
1
|
0.1593
0.1593
|
0.0885
0.0885
|
0.2655
0.2655
|
0.584
0.584
|
190.2
190.2
|
336.1
336.1
|
11,500
11,500
|
12,400
12,400
|
13,200
13,200
|
0.4341
0.4341
|
|
TBA
TBA
|
Brahma
Brahma
|
203.2
203.2
|
16/19
16/19
|
0.1596
0.1596
|
0.3020
0.3020
|
1
1
|
0.1127
0.1127
|
0.0977
0.0977
|
0.4885
0.4885
|
0.714
0.714
|
191.4
191.4
|
674.5
674.5
|
28,400
28,400
|
31,100
31,100
|
33,700
33,700
|
0.4034
0.4034
|
|
TBA
TBA
|
Cochin
Cochin
|
211.3
211.3
|
12/7
12/7
|
0.1660
0.1660
|
0.2628
0.2628
|
1
1
|
0.1327
0.1327
|
0.1327
0.1327
|
0.3981
0.3981
|
0.664
0.664
|
199.1
199.1
|
526.8
526.8
|
20,700
20,700
|
22,600
22,600
|
24,400
24,400
|
0.4026
0.4026
|
|
TBA
TBA
|
Jaeger
Jaeger
|
228.2
228.2
|
18/1
18/1
|
0.1792
0.1792
|
0.1892
0.1892
|
2
2
|
0.1126
0.1126
|
0.1126
0.1126
|
0.1126
0.1126
|
0.563
0.563
|
213.9
213.9
|
247.6
247.6
|
6,020
6,020
|
6,210
6,210
|
6,400
6,400
|
0.3970
0.3970
|
|
TBA
TBA
|
Owl
Owl
|
266.8
266.8
|
6/7
6/7
|
0.2096
0.2096
|
0.2368
0.2368
|
1
1
|
0.2109
0.2109
|
0.0703
0.0703
|
0.2109
0.2109
|
0.633
0.633
|
248.9
248.9
|
341.0
341.0
|
9,680
9,680
|
10,200
10,200
|
10,700
10,700
|
0.3346
0.3346
|
|
TBA
TBA
|
Waxwing
Waxwing
|
266.8
266.8
|
18/1
18/1
|
0.2094
0.2094
|
0.2210
0.2210
|
2
2
|
0.1217
0.1217
|
0.1217
0.1217
|
0.1217
0.1217
|
0.609
0.609
|
249.9
249.9
|
289.0
289.0
|
6,880
6,880
|
7,100
7,100
|
7,320
7,320
|
0.3398
0.3398
|
|
TBA
TBA
|
Spoonbill
Spoonbill
|
266.8
266.8
|
22/7
22/7
|
0.2095
0.2095
|
0.2301
0.2301
|
2
2
|
0.1101
0.1101
|
0.0612
0.0612
|
0.1836
0.1836
|
0.624
0.624
|
251.2
251.2
|
320.9
320.9
|
8,720
8,720
|
9,120
9,120
|
9,510
9,510
|
0.3394
0.3394
|
|
TBA
TBA
|
Scaup
Scaup
|
266.8
266.8
|
24/7
24/7
|
0.2094
0.2094
|
0.2366
0.2366
|
2
2
|
0.1054
0.1054
|
0.0703
0.0703
|
0.2109
0.2109
|
0.633
0.633
|
251.1
251.1
|
343.2
343.2
|
10,000
10,000
|
10,500
10,500
|
11,100
11,100
|
0.3381
0.3381
|
|
TBA
TBA
|
Partridge
Partridge
|
266.8
266.8
|
26/7
26/7
|
0.2095
0.2095
|
0.2436
0.2436
|
2
2
|
0.1013
0.1013
|
0.0788
0.0788
|
0.2364
0.2364
|
0.642
0.642
|
251.2
251.2
|
366.6
366.6
|
11,300
11,300
|
11,900
11,900
|
12,600
12,600
|
0.3365
0.3365
|
|
TBA
TBA
|
Junco
Junco
|
266.8
266.8
|
30/7
30/7
|
0.2095
0.2095
|
0.2584
0.2584
|
2
2
|
0.0943
0.0943
|
0.0943
0.0943
|
0.2829
0.2829
|
0.660
0.660
|
251.9
251.9
|
417.5
417.5
|
13,900
13,900
|
14,900
14,900
|
15,800
15,800
|
0.3342
0.3342
|
|
TBA
TBA
|
Eider
Eider
|
266.8
266.8
|
45/7
45/7
|
0.2095
0.2095
|
0.2240
0.2240
|
3
3
|
0.0770
0.0770
|
0.0513
0.0513
|
0.1539
0.1539
|
0.616
0.616
|
251.2
251.2
|
300.3
300.3
|
7,980
7,980
|
8,260
8,260
|
8,530
8,530
|
0.3407
0.3407
|
|
TBA
TBA
|
Rhea
Rhea
|
286.2
286.2
|
18/19
18/19
|
0.2248
0.2248
|
0.4621
0.4621
|
1
1
|
0.1261
0.1261
|
0.1261
0.1261
|
0.6305
0.6305
|
0.883
0.883
|
269.6
269.6
|
1075.0
1075.0
|
45,100
45,100
|
49,500
49,500
|
53,900
53,900
|
0.2809
0.2809
|
|
TBA
TBA
|
Phoebe
Phoebe
|
300.0
300.0
|
18/1
18/1
|
0.2356
0.2356
|
0.2487
0.2487
|
2
2
|
0.1291
0.1291
|
0.1291
0.1291
|
0.1291
0.1291
|
0.646
0.646
|
281.2
281.2
|
325.4
325.4
|
7,740
7,740
|
7,990
7,990
|
8,240
8,240
|
0.3020
0.3020
|
|
TBA
TBA
|
Gadwall
Gadwall
|
300.0
300.0
|
24/7
24/7
|
0.2356
0.2356
|
0.2661
0.2661
|
2
2
|
0.1118
0.1118
|
0.0745
0.0745
|
0.2235
0.2235
|
0.671
0.671
|
282.5
282.5
|
385.8
385.8
|
11,200
11,200
|
11,700
11,700
|
12,300
12,300
|
0.3005
0.3005
|
|
TBA
TBA
|
Ostrich
Ostrich
|
300.0
300.0
|
26/7
26/7
|
0.2355
0.2355
|
0.2738
0.2738
|
2
2
|
0.1074
0.1074
|
0.0835
0.0835
|
0.2505
0.2505
|
0.680
0.680
|
282.4
282.4
|
412.1
412.1
|
12,700
12,700
|
13,400
13,400
|
14,200
14,200
|
0.2994
0.2994
|
|
TBA
TBA
|
Piper
Piper
|
300.0
300.0
|
30/7
30/7
|
0.2356
0.2356
|
0.2906
0.2906
|
2
2
|
0.1000
0.1000
|
0.1000
0.1000
|
0.3000
0.3000
|
0.700
0.700
|
283.2
283.2
|
469.4
469.4
|
15,700
15,700
|
16,700
16,700
|
17,800
17,800
|
0.2972
0.2972
|
|
TBA
TBA
|
Merlin
Merlin
|
336.4
336.4
|
18/1
18/1
|
0.2642
0.2642
|
0.2789
0.2789
|
2
2
|
0.1367
0.1367
|
0.1367
0.1367
|
0.1367
0.1367
|
0.684
0.684
|
315.3
315.3
|
364.9
364.9
|
8,680
8,680
|
8,960
8,960
|
9,240
9,240
|
0.2693
0.2693
|
|
TBA
TBA
|
Trogon
Trogon
|
336.4
336.4
|
20/7
20/7
|
0.2642
0.2642
|
0.2824
0.2824
|
2
2
|
0.1297
0.1297
|
0.0576
0.0576
|
0.1728
0.1728
|
0.692
0.692
|
316.8
316.8
|
378.4
378.4
|
9,470
9,470
|
9,820
9,820
|
10,200
10,200
|
0.2702
0.2702
|
|
TBA
TBA
|
Woodcock
Woodcock
|
336.4
336.4
|
22/7
22/7
|
0.2644
0.2644
|
0.2903
0.2903
|
2
2
|
0.1237
0.1237
|
0.0687
0.0687
|
0.2061
0.2061
|
0.701
0.701
|
317.1
317.1
|
404.8
404.8
|
10,900
10,900
|
11,400
11,400
|
11,900
11,900
|
0.2689
0.2689
|
|
TBA
TBA
|
Widgeon
Widgeon
|
336.4
336.4
|
24/7
24/7
|
0.2642
0.2642
|
0.2984
0.2984
|
2
2
|
0.1184
0.1184
|
0.0789
0.0789
|
0.2367
0.2367
|
0.710
0.710
|
316.8
316.8
|
432.6
432.6
|
12,500
12,500
|
13,200
13,200
|
13,800
13,800
|
0.2680
0.2680
|
|
TBA
TBA
|
Linnet
Linnet
|
336.4
336.4
|
26/7
26/7
|
0.2640
0.2640
|
0.3070
0.3070
|
2
2
|
0.1137
0.1137
|
0.0884
0.0884
|
0.2652
0.2652
|
0.720
0.720
|
316.6
316.6
|
462.2
462.2
|
14,100
14,100
|
14,900
14,900
|
15,700
15,700
|
0.2670
0.2670
|
|
TBA
TBA
|
Oriole
Oriole
|
336.4
336.4
|
30/7
30/7
|
0.2642
0.2642
|
0.3259
0.3259
|
2
2
|
0.1059
0.1059
|
0.1059
0.1059
|
0.3177
0.3177
|
0.741
0.741
|
317.6
317.6
|
526.5
526.5
|
17,300
17,300
|
18,500
18,500
|
19,700
19,700
|
0.2650
0.2650
|
|
TBA
TBA
|
Hummingbird
Hummingbird
|
336.4
336.4
|
45/7
45/7
|
0.2644
0.2644
|
0.2827
0.2827
|
3
3
|
0.0865
0.0865
|
0.0577
0.0577
|
0.1731
0.1731
|
0.692
0.692
|
317.1
317.1
|
379.1
379.1
|
9,960
9,960
|
10,300
10,300
|
10,700
10,700
|
0.2699
0.2699
|
|
TBA
TBA
|
Chickadee
Chickadee
|
397.5
397.5
|
18/1
18/1
|
0.3122
0.3122
|
0.3295
0.3295
|
2
2
|
0.1486
0.1486
|
0.1486
0.1486
|
0.1486
0.1486
|
0.743
0.743
|
372.6
372.6
|
430.9
430.9
|
9,940
9,940
|
10,400
10,400
|
10,700
10,700
|
0.2279
0.2279
|
|
TBA
TBA
|
Ptarmigan
Ptarmigan
|
397.5
397.5
|
20/7
20/7
|
0.3123
0.3123
|
0.3339
0.3339
|
2
2
|
0.1410
0.1410
|
0.0627
0.0627
|
0.1881
0.1881
|
0.752
0.752
|
374.5
374.5
|
447.6
447.6
|
11,100
11,100
|
11,500
11,500
|
11,900
11,900
|
0.2285
0.2285
|
|
TBA
TBA
|
Stork
Stork
|
397.5
397.5
|
22/7
22/7
|
0.3121
0.3121
|
0.3428
0.3428
|
2
2
|
0.1344
0.1344
|
0.0747
0.0747
|
0.2241
0.2241
|
0.762
0.762
|
374.3
374.3
|
478.2
478.2
|
12,900
12,900
|
13,400
13,400
|
14,000
14,000
|
0.2278
0.2278
|
|
TBA
TBA
|
Brant
Brant
|
397.5
397.5
|
24/7
24/7
|
0.3122
0.3122
|
0.3527
0.3527
|
2
2
|
0.1287
0.1287
|
0.0858
0.0858
|
0.2574
0.2574
|
0.772
0.772
|
374.4
374.4
|
511.5
511.5
|
14,600
14,600
|
15,400
15,400
|
16,200
16,200
|
0.2268
0.2268
|
|
TBA
TBA
|
Ibis
Ibis
|
397.5
397.5
|
26/7
26/7
|
0.3120
0.3120
|
0.3628
0.3628
|
2
2
|
0.1236
0.1236
|
0.0961
0.0961
|
0.2883
0.2883
|
0.783
0.783
|
374.2
374.2
|
546.2
546.2
|
16,300
16,300
|
17,200
17,200
|
18,200
18,200
|
0.2260
0.2260
|
|
TBA
TBA
|
Lark
Lark
|
397.5
397.5
|
30/7
30/7
|
0.3121
0.3121
|
0.3849
0.3849
|
2
2
|
0.1151
0.1151
|
0.1151
0.1151
|
0.3453
0.3453
|
0.806
0.806
|
375.2
375.2
|
621.7
621.7
|
20,300
20,300
|
21,700
21,700
|
23,100
23,100
|
0.2244
0.2244
|
|
TBA
TBA
|
Erne
Erne
|
397.5
397.5
|
42/7
42/7
|
0.3123
0.3123
|
0.3284
0.3284
|
3
3
|
0.0973
0.0973
|
0.0541
0.0541
|
0.1623
0.1623
|
0.746
0.746
|
374.5
374.5
|
429.0
429.0
|
10,600
10,600
|
10,900
10,900
|
11,200
11,200
|
0.2291
0.2291
|
|
TBA
TBA
|
Longspur
Longspur
|
397.5
397.5
|
45/7
45/7
|
0.3123
0.3123
|
0.3339
0.3339
|
3
3
|
0.0940
0.0940
|
0.0627
0.0627
|
0.1881
0.1881
|
0.752
0.752
|
374.5
374.5
|
447.6
447.6
|
11,600
11,600
|
12,000
12,000
|
12,400
12,400
|
0.2285
0.2285
|
|
TBA
TBA
|
Pintail
Pintail
|
419.0
419.0
|
30/7
30/7
|
0.3292
0.3292
|
0.4060
0.4060
|
2
2
|
0.1182
0.1182
|
0.1182
0.1182
|
0.3546
0.3546
|
0.827
0.827
|
395.8
395.8
|
655.8
655.8
|
21,400
21,400
|
22,900
22,900
|
24,400
24,400
|
0.2127
0.2127
|
|
TBA
TBA
|
Pelican
Pelican
|
477.0
477.0
|
18/1
18/1
|
0.3747
0.3747
|
0.3955
0.3955
|
2
2
|
0.1628
0.1628
|
0.1628
0.1628
|
0.1628
0.1628
|
0.814
0.814
|
447.2
447.2
|
517.3
517.3
|
11,800
11,800
|
12,300
12,300
|
12,700
12,700
|
0.1899
0.1899
|
|
TBA
TBA
|
Tailorbird
Tailorbird
|
477.0
477.0
|
20/7
20/7
|
0.3745
0.3745
|
0.4004
0.4004
|
2
2
|
0.1544
0.1544
|
0.0686
0.0686
|
0.2058
0.2058
|
0.823
0.823
|
449.1
449.1
|
536.8
536.8
|
13,100
13,100
|
13,600
13,600
|
14,100
14,100
|
0.1906
0.1906
|
|
TBA
TBA
|
Toucan
Toucan
|
477.0
477.0
|
22/7
22/7
|
0.3744
0.3744
|
0.4112
0.4112
|
2
2
|
0.1472
0.1472
|
0.0818
0.0818
|
0.2454
0.2454
|
0.834
0.834
|
449.0
449.0
|
573.6
573.6
|
15,200
15,200
|
15,900
15,900
|
16,700
16,700
|
0.1899
0.1899
|
|
TBA
TBA
|
Flicker
Flicker
|
477.0
477.0
|
24/7
24/7
|
0.3747
0.3747
|
0.4233
0.4233
|
2
2
|
0.1410
0.1410
|
0.0940
0.0940
|
0.2820
0.2820
|
0.846
0.846
|
449.4
449.4
|
613.9
613.9
|
17,200
17,200
|
18,100
18,100
|
19,000
19,000
|
0.1890
0.1890
|
|
TBA
TBA
|
Hawk
Hawk
|
477.0
477.0
|
26/7
26/7
|
0.3744
0.3744
|
0.4354
0.4354
|
2
2
|
0.1354
0.1354
|
0.1053
0.1053
|
0.3159
0.3159
|
0.858
0.858
|
449.0
449.0
|
655.5
655.5
|
19,500
19,500
|
20,700
20,700
|
21,900
21,900
|
0.1883
0.1883
|
|
TBA
TBA
|
Hen
Hen
|
477.0
477.0
|
30/7
30/7
|
0.3747
0.3747
|
0.4621
0.4621
|
2
2
|
0.1261
0.1261
|
0.1261
0.1261
|
0.3783
0.3783
|
0.883
0.883
|
450.5
450.5
|
746.4
746.4
|
23,800
23,800
|
25,500
25,500
|
27,200
27,200
|
0.1869
0.1869
|
|
TBA
TBA
|
Kestrel
Kestrel
|
477.0
477.0
|
42/7
42/7
|
0.3748
0.3748
|
0.3941
0.3941
|
3
3
|
0.1066
0.1066
|
0.0592
0.0592
|
0.1776
0.1776
|
0.817
0.817
|
449.5
449.5
|
514.8
514.8
|
12,400
12,400
|
12,800
12,800
|
13,100
13,100
|
0.1909
0.1909
|
|
TBA
TBA
|
Jackdaw
Jackdaw
|
477.0
477.0
|
45/7
45/7
|
0.3750
0.3750
|
0.4009
0.4009
|
3
3
|
0.1030
0.1030
|
0.0687
0.0687
|
0.2061
0.2061
|
0.824
0.824
|
449.7
449.7
|
537.4
537.4
|
13,600
13,600
|
14,100
14,100
|
14,600
14,600
|
0.1903
0.1903
|
|
TBA
TBA
|
Heron
Heron
|
500.0
500.0
|
30/7
30/7
|
0.3927
0.3927
|
0.4843
0.4843
|
2
2
|
0.1291
0.1291
|
0.1291
0.1291
|
0.3873
0.3873
|
0.904
0.904
|
472.1
472.1
|
782.2
782.2
|
25,000
25,000
|
26,700
26,700
|
28,500
28,500
|
0.1783
0.1783
|
|
TBA
TBA
|
Nightingale
Nightingale
|
517.0
517.0
|
20/7
20/7
|
0.4062
0.4062
|
0.4343
0.4343
|
2
2
|
0.1608
0.1608
|
0.0715
0.0715
|
0.2145
0.2145
|
0.858
0.858
|
487.1
487.1
|
582.2
582.2
|
14,200
14,200
|
14,700
14,700
|
15,300
15,300
|
0.1757
0.1757
|
|
TBA
TBA
|
Osprey
Osprey
|
556.5
556.5
|
18/1
18/1
|
0.4369
0.4369
|
0.4612
0.4612
|
2
2
|
0.1758
0.1758
|
0.1758
0.1758
|
0.1758
0.1758
|
0.879
0.879
|
521.4
521.4
|
603.3
603.3
|
13,700
13,700
|
14,300
14,300
|
14,800
14,800
|
0.1629
0.1629
|
|
TBA
TBA
|
Tody
Tody
|
556.5
556.5
|
20/7
20/7
|
0.4370
0.4370
|
0.4672
0.4672
|
2
2
|
0.1668
0.1668
|
0.0741
0.0741
|
0.2223
0.2223
|
0.890
0.890
|
524.1
524.1
|
626.3
626.3
|
15,300
15,300
|
15,800
15,800
|
16,400
16,400
|
0.1633
0.1633
|
|
TBA
TBA
|
Sapsucker
Sapsucker
|
556.5
556.5
|
22/7
22/7
|
0.4368
0.4368
|
0.4797
0.4797
|
2
2
|
0.1590
0.1590
|
0.0883
0.0883
|
0.2649
0.2649
|
0.901
0.901
|
523.8
523.8
|
669.0
669.0
|
17,600
17,600
|
18,400
18,400
|
19,200
19,200
|
0.1628
0.1628
|
|
TBA
TBA
|
Parakeet
Parakeet
|
556.5
556.5
|
24/7
24/7
|
0.4372
0.4372
|
0.4938
0.4938
|
2
2
|
0.1523
0.1523
|
0.1015
0.1015
|
0.3045
0.3045
|
0.914
0.914
|
524.3
524.3
|
715.9
715.9
|
19,800
19,800
|
20,900
20,900
|
22,000
22,000
|
0.1620
0.1620
|
|
TBA
TBA
|
Dove
Dove
|
556.5
556.5
|
26/7
26/7
|
0.4371
0.4371
|
0.5083
0.5083
|
2
2
|
0.1463
0.1463
|
0.1138
0.1138
|
0.3414
0.3414
|
0.927
0.927
|
524.2
524.2
|
765.2
765.2
|
22,600
22,600
|
24,000
24,000
|
25,300
25,300
|
0.1613
0.1613
|
|
TBA
TBA
|
Eagle
Eagle
|
556.5
556.5
|
30/7
30/7
|
0.4371
0.4371
|
0.5391
0.5391
|
2
2
|
0.1362
0.1362
|
0.1362
0.1362
|
0.4086
0.4086
|
0.953
0.953
|
525.5
525.5
|
870.8
870.8
|
27,800
27,800
|
29,700
29,700
|
31,700
31,700
|
0.1602
0.1602
|
|
TBA
TBA
|
Blackbird
Blackbird
|
556.5
556.5
|
42/7
42/7
|
0.4370
0.4370
|
0.4594
0.4594
|
3
3
|
0.1151
0.1151
|
0.0639
0.0639
|
0.1917
0.1917
|
0.882
0.882
|
524.1
524.1
|
599.9
599.9
|
14,200
14,200
|
14,700
14,700
|
15,100
15,100
|
0.1637
0.1637
|
|
TBA
TBA
|
Sunbird
Sunbird
|
556.5
556.5
|
45/7
45/7
|
0.4370
0.4370
|
0.4672
0.4672
|
3
3
|
0.1112
0.1112
|
0.0741
0.0741
|
0.2223
0.2223
|
0.890
0.890
|
524.1
524.1
|
626.3
626.3
|
15,600
15,600
|
16,200
16,200
|
16,800
16,800
|
0.1633
0.1633
|
|
TBA
TBA
|
Peacock
Peacock
|
605.0
605.0
|
24/7
24/7
|
0.4753
0.4753
|
0.5370
0.5370
|
2
2
|
0.1588
0.1588
|
0.1059
0.1059
|
0.3177
0.3177
|
0.953
0.953
|
570.0
570.0
|
778.9
778.9
|
21,600
21,600
|
22,700
22,700
|
23,900
23,900
|
0.1490
0.1490
|
|
TBA
TBA
|
Squab
Squab
|
605.0
605.0
|
26/7
26/7
|
0.4749
0.4749
|
0.5522
0.5522
|
2
2
|
0.1525
0.1525
|
0.1186
0.1186
|
0.3558
0.3558
|
0.966
0.966
|
569.5
569.5
|
831.2
831.2
|
24,300
24,300
|
25,800
25,800
|
27,300
27,300
|
0.1485
0.1485
|
|
TBA
TBA
|
Wood Duck
Wood Duck
|
605.0
605.0
|
30/7
30/7
|
0.4751
0.4751
|
0.5860
0.5860
|
2
2
|
0.1420
0.1420
|
0.1420
0.1420
|
0.4260
0.4260
|
0.994
0.994
|
571.2
571.2
|
946.7
946.7
|
28,900
28,900
|
31,600
31,600
|
33,700
33,700
|
0.1474
0.1474
|
|
TBA
TBA
|
Teal
Teal
|
605.0
605.0
|
30/19
30/19
|
0.4751
0.4751
|
0.5834
0.5834
|
2
2
|
0.1420
0.1420
|
0.0852
0.0852
|
0.4260
0.4260
|
0.994
0.994
|
571.2
571.2
|
938.6
938.6
|
30,000
30,000
|
32,000
32,000
|
34,000
34,000
|
0.1475
0.1475
|
|
TBA
TBA
|
Sandpiper
Sandpiper
|
605.0
605.0
|
45/7
45/7
|
0.4756
0.4756
|
0.5085
0.5085
|
3
3
|
0.1160
0.1160
|
0.0773
0.0773
|
0.2319
0.2319
|
0.928
0.928
|
570.4
570.4
|
681.8
681.8
|
17,000
17,000
|
17,700
17,700
|
18,300
18,300
|
0.1501
0.1501
|
|
TBA
TBA
|
Duck
Duck
|
605.0
605.0
|
54/7
54/7
|
0.4747
0.4747
|
0.5362
0.5362
|
3
3
|
0.1058
0.1058
|
0.1058
0.1058
|
0.3174
0.3174
|
0.952
0.952
|
569.3
569.3
|
777.5
777.5
|
22,200
22,200
|
23,300
23,300
|
24,500
24,500
|
0.1492
0.1492
|
|
TBA
TBA
|
Kingbird
Kingbird
|
636.0
636.0
|
18/1
18/1
|
0.4997
0.4997
|
0.5275
0.5275
|
2
2
|
0.1880
0.1880
|
0.1880
0.1880
|
0.1880
0.1880
|
0.940
0.940
|
596.3
596.3
|
690.0
690.0
|
15,700
15,700
|
16,300
16,300
|
16,900
16,900
|
0.1424
0.1424
|
|
TBA
TBA
|
Swift
Swift
|
636.0
636.0
|
36/1
36/1
|
0.4994
0.4994
|
0.5133
0.5133
|
3
3
|
0.1329
0.1329
|
0.1329
0.1329
|
0.1329
0.1329
|
0.930
0.930
|
596.0
596.0
|
642.9
642.9
|
13,800
13,800
|
14,000
14,000
|
14,300
14,300
|
0.1430
0.1430
|
|
TBA
TBA
|
Turacos
Turacos
|
636.0
636.0
|
20/7
20/7
|
0.4994
0.4994
|
0.5339
0.5339
|
2
2
|
0.1783
0.1783
|
0.0792
0.0792
|
0.2376
0.2376
|
0.951
0.951
|
598.9
598.9
|
715.7
715.7
|
17,400
17,400
|
18,100
18,100
|
18,800
18,800
|
0.1429
0.1429
|
|
TBA
TBA
|
Goldfinch
Goldfinch
|
636.0
636.0
|
22/7
22/7
|
0.4994
0.4994
|
0.5484
0.5484
|
2
2
|
0.1700
0.1700
|
0.0944
0.0944
|
0.2832
0.2832
|
0.963
0.963
|
598.9
598.9
|
764.8
764.8
|
19,800
19,800
|
20,800
20,800
|
21,700
21,700
|
0.1424
0.1424
|
|
TBA
TBA
|
Rook
Rook
|
636.0
636.0
|
24/7
24/7
|
0.4996
0.4996
|
0.5643
0.5643
|
2
2
|
0.1628
0.1628
|
0.1085
0.1085
|
0.3255
0.3255
|
0.977
0.977
|
599.1
599.1
|
818.1
818.1
|
22,600
22,600
|
23,900
23,900
|
25,100
25,100
|
0.1417
0.1417
|
|
TBA
TBA
|
Grosbeak
Grosbeak
|
636.0
636.0
|
26/7
26/7
|
0.4995
0.4995
|
0.5808
0.5808
|
2
2
|
0.1564
0.1564
|
0.1216
0.1216
|
0.3648
0.3648
|
0.990
0.990
|
599.0
599.0
|
874.2
874.2
|
25,200
25,200
|
26,800
26,800
|
28,300
28,300
|
0.1411
0.1411
|
|
TBA
TBA
|
Scoter
Scoter
|
636.0
636.0
|
30/7
30/7
|
0.4995
0.4995
|
0.6160
0.6160
|
2
2
|
0.1456
0.1456
|
0.1456
0.1456
|
0.4368
0.4368
|
1.019
1.019
|
600.5
600.5
|
994.9
994.9
|
30,400
30,400
|
33,200
33,200
|
35,400
35,400
|
0.1402
0.1402
|
|
TBA
TBA
|
Egret
Egret
|
636.0
636.0
|
30/19
30/19
|
0.4995
0.4995
|
0.6135
0.6135
|
2
2
|
0.1456
0.1456
|
0.0874
0.0874
|
0.4370
0.4370
|
1.019
1.019
|
600.5
600.5
|
987.2
987.2
|
31,500
31,500
|
33,600
33,600
|
35,800
35,800
|
0.1403
0.1403
|
|
TBA
TBA
|
Pipit
Pipit
|
636.0
636.0
|
42/7
42/7
|
0.4999
0.4999
|
0.5256
0.5256
|
3
3
|
0.1231
0.1231
|
0.0684
0.0684
|
0.2052
0.2052
|
0.944
0.944
|
599.5
599.5
|
686.5
686.5
|
16,100
16,100
|
16,600
16,600
|
17,100
17,100
|
0.1431
0.1431
|
|
TBA
TBA
|
Killdeer
Killdeer
|
636.0
636.0
|
45/7
45/7
|
0.4997
0.4997
|
0.5343
0.5343
|
3
3
|
0.1189
0.1189
|
0.0793
0.0793
|
0.2379
0.2379
|
0.951
0.951
|
599.3
599.3
|
716.4
716.4
|
17,900
17,900
|
18,600
18,600
|
19,200
19,200
|
0.1428
0.1428
|
|
TBA
TBA
|
Goose
Goose
|
636.0
636.0
|
54/7
54/7
|
0.4993
0.4993
|
0.5640
0.5640
|
3
3
|
0.1085
0.1085
|
0.1085
0.1085
|
0.3255
0.3255
|
0.977
0.977
|
598.8
598.8
|
817.8
817.8
|
23,300
23,300
|
24,600
24,600
|
25,800
25,800
|
0.1418
0.1418
|
|
TBA
TBA
|
Edison Bird
Edison Bird
|
653.9
653.9
|
18/3
18/3
|
0.5136
0.5136
|
0.5319
0.5319
|
2
2
|
0.1906
0.1906
|
0.0882
0.0882
|
0.1905
0.1905
|
0.762
0.762
|
612.9
612.9
|
675.5
675.5
|
14,800
14,800
|
15,200
15,200
|
15,500
15,500
|
0.1389
0.1389
|
|
TBA
TBA
|
Flamingo
Flamingo
|
666.6
666.6
|
24/7
24/7
|
0.5238
0.5238
|
0.5917
0.5917
|
2
2
|
0.1667
0.1667
|
0.1111
0.1111
|
0.3333
0.3333
|
1.000
1.000
|
628.2
628.2
|
858.1
858.1
|
23,700
23,700
|
25,000
25,000
|
26,300
26,300
|
0.1352
0.1352
|
|
TBA
TBA
|
Gannet
Gannet
|
666.6
666.6
|
26/7
26/7
|
0.5234
0.5234
|
0.6086
0.6086
|
2
2
|
0.1601
0.1601
|
0.1245
0.1245
|
0.3735
0.3735
|
1.014
1.014
|
627.7
627.7
|
916.1
916.1
|
26,400
26,400
|
28,000
28,000
|
29,700
29,700
|
0.1347
0.1347
|
|
TBA
TBA
|
Crossbill
Crossbill
|
666.6
666.6
|
45/7
45/7
|
0.5235
0.5235
|
0.5597
0.5597
|
3
3
|
0.1217
0.1217
|
0.0811
0.0811
|
0.2433
0.2433
|
0.974
0.974
|
627.8
627.8
|
750.4
750.4
|
18,500
18,500
|
19,200
19,200
|
19,900
19,900
|
0.1363
0.1363
|
|
TBA
TBA
|
Gull
Gull
|
666.6
666.6
|
54/7
54/7
|
0.5235
0.5235
|
0.5914
0.5914
|
3
3
|
0.1111
0.1111
|
0.1111
0.1111
|
0.3333
0.3333
|
1.000
1.000
|
627.8
627.8
|
857.7
857.7
|
24,200
24,200
|
25,500
25,500
|
26,800
26,800
|
0.1353
0.1353
|
|
TBA
TBA
|
Stilt
Stilt
|
715.5
715.5
|
24/7
24/7
|
0.5622
0.5622
|
0.6350
0.6350
|
2
2
|
0.1727
0.1727
|
0.1151
0.1151
|
0.3453
0.3453
|
1.036
1.036
|
674.2
674.2
|
920.7
920.7
|
25,500
25,500
|
26,900
26,900
|
28,300
28,300
|
0.1259
0.1259
|
|
TBA
TBA
|
Starling
Starling
|
715.5
715.5
|
26/7
26/7
|
0.5620
0.5620
|
0.6535
0.6535
|
2
2
|
0.1659
0.1659
|
0.1290
0.1290
|
0.3870
0.3870
|
1.051
1.051
|
674.0
674.0
|
983.8
983.8
|
28,400
28,400
|
30,100
30,100
|
31,900
31,900
|
0.1254
0.1254
|
|
TBA
TBA
|
Buteo
Buteo
|
715.5
715.5
|
30/7
30/7
|
0.5617
0.5617
|
0.6928
0.6928
|
2
2
|
0.1544
0.1544
|
0.1544
0.1544
|
0.4632
0.4632
|
1.081
1.081
|
675.3
675.3
|
1119.0
1119.0
|
33,900
33,900
|
37,100
37,100
|
39,600
39,600
|
0.1247
0.1247
|
|
TBA
TBA
|
Redwing
Redwing
|
715.5
715.5
|
30/19
30/19
|
0.5617
0.5617
|
0.6897
0.6897
|
2
2
|
0.1544
0.1544
|
0.0926
0.0926
|
0.4630
0.4630
|
1.081
1.081
|
675.3
675.3
|
1110
1110
|
34,600
34,600
|
36,900
36,900
|
39,300
39,300
|
0.1248
0.1248
|
|
TBA
TBA
|
Grebe
Grebe
|
715.5
715.5
|
45/7
45/7
|
0.5620
0.5620
|
0.6009
0.6009
|
3
3
|
0.1261
0.1261
|
0.0841
0.0841
|
0.2523
0.2523
|
1.009
1.009
|
674.0
674.0
|
806
806
|
19,900
19,900
|
20,600
20,600
|
21,400
21,400
|
0.1270
0.1270
|
|
TBA
TBA
|
Crow
Crow
|
715.5
715.5
|
54/7
54/7
|
0.5619
0.5619
|
0.6347
0.6347
|
3
3
|
0.1151
0.1151
|
0.1151
0.1151
|
0.3453
0.3453
|
1.036
1.036
|
673.9
673.9
|
920.4
920.4
|
26,000
26,000
|
27,400
27,400
|
28,800
28,800
|
0.1260
0.1260
|
|
TBA
TBA
|
Coot
Coot
|
795.0
795.0
|
36/1
36/1
|
0.6244
0.6244
|
0.6417
0.6417
|
3
3
|
0.1486
0.1486
|
0.1486
0.1486
|
0.1486
0.1486
|
1.040
1.040
|
745.2
745.2
|
803.5
803.5
|
16,800
16,800
|
17,200
17,200
|
17,500
17,500
|
0.1144
0.1144
|
|
TBA
TBA
|
Turbit
Turbit
|
795.0
795.0
|
20/7
20/7
|
0.6246
0.6246
|
0.6678
0.6678
|
2
2
|
0.1994
0.1994
|
0.0886
0.0886
|
0.2658
0.2658
|
1.063
1.063
|
749.1
749.1
|
895.4
895.4
|
21,800
21,800
|
22,600
22,600
|
23,500
23,500
|
0.1143
0.1143
|
|
TBA
TBA
|
Puffin
Puffin
|
795.0
795.0
|
22/7
22/7
|
0.6244
0.6244
|
0.6857
0.6857
|
2
2
|
0.1901
0.1901
|
0.1056
0.1056
|
0.3168
0.3168
|
1.077
1.077
|
748.8
748.8
|
956.3
956.3
|
24,800
24,800
|
26,000
26,000
|
27,200
27,200
|
0.1139
0.1139
|
|
TBA
TBA
|
Cuckoo
Cuckoo
|
795.0
795.0
|
24/7
24/7
|
0.6244
0.6244
|
0.7053
0.7053
|
2
2
|
0.1820
0.1820
|
0.1213
0.1213
|
0.3639
0.3639
|
1.092
1.092
|
748.8
748.8
|
1023
1023
|
27,900
27,900
|
29,500
29,500
|
31,000
31,000
|
0.1134
0.1134
|
|
TBA
TBA
|
Drake
Drake
|
795.0
795.0
|
26/7
26/7
|
0.6247
0.6247
|
0.7264
0.7264
|
2
2
|
0.1749
0.1749
|
0.1360
0.1360
|
0.4080
0.4080
|
1.108
1.108
|
749.2
749.2
|
1094
1094
|
31,500
31,500
|
33,500
33,500
|
35,400
35,400
|
0.1129
0.1129
|
|
TBA
TBA
|
Skimmer
Skimmer
|
795.0
795.0
|
30/7
30/7
|
0.6245
0.6245
|
0.7702
0.7702
|
2
2
|
0.1628
0.1628
|
0.1628
0.1628
|
0.4884
0.4884
|
1.140
1.140
|
750.8
750.8
|
1244
1244
|
37,700
37,700
|
41,200
41,200
|
44,000
44,000
|
0.1121
0.1121
|
|
TBA
TBA
|
Mallard
Mallard
|
795.0
795.0
|
30/19
30/19
|
0.6245
0.6245
|
0.7669
0.7669
|
2
2
|
0.1628
0.1628
|
0.0977
0.0977
|
0.4885
0.4885
|
1.140
1.140
|
750.8
750.8
|
1234
1234
|
38,400
38,400
|
41,100
41,100
|
43,700
43,700
|
0.1122
0.1122
|
|
TBA
TBA
|
Macaw
Macaw
|
795.0
795.0
|
42/7
42/7
|
0.6246
0.6246
|
0.6567
0.6567
|
3
3
|
0.1376
0.1376
|
0.0764
0.0764
|
0.2292
0.2292
|
1.055
1.055
|
749.1
749.1
|
857.8
857.8
|
20,100
20,100
|
20,700
20,700
|
21,300
21,300
|
0.1145
0.1145
|
|
TBA
TBA
|
Tern
Tern
|
795.0
795.0
|
45/7
45/7
|
0.6242
0.6242
|
0.6674
0.6674
|
3
3
|
0.1329
0.1329
|
0.0886
0.0886
|
0.2658
0.2658
|
1.063
1.063
|
748.6
748.6
|
894.9
894.9
|
22,100
22,100
|
22,900
22,900
|
23,700
23,700
|
0.1143
0.1143
|
|
TBA
TBA
|
Condor
Condor
|
795.0
795.0
|
54/7
54/7
|
0.6240
0.6240
|
0.7049
0.7049
|
3
3
|
0.1213
0.1213
|
0.1213
0.1213
|
0.3639
0.3639
|
1.092
1.092
|
748.3
748.3
|
1022
1022
|
28,200
28,200
|
29,700
29,700
|
31,300
31,300
|
0.1135
0.1135
|
|
TBA
TBA
|
Willet
Willet
|
874.5
874.5
|
45/7
45/7
|
0.6868
0.6868
|
0.7342
0.7342
|
3
3
|
0.1394
0.1394
|
0.0929
0.0929
|
0.2787
0.2787
|
1.115
1.115
|
823.6
823.6
|
984
984
|
24,100
24,100
|
25,000
25,000
|
25,900
25,900
|
0.1039
0.1039
|
|
TBA
TBA
|
Crane
Crane
|
874.5
874.5
|
54/7
54/7
|
0.6873
0.6873
|
0.7764
0.7764
|
3
3
|
0.1273
0.1273
|
0.1273
0.1273
|
0.3819
0.3819
|
1.146
1.146
|
824.2
824.2
|
1126
1126
|
31,000
31,000
|
32,700
32,700
|
34,500
34,500
|
0.1030
0.1030
|
|
TBA
TBA
|
Turnstone
Turnstone
|
900.0
900.0
|
20/7
20/7
|
0.7066
0.7066
|
0.7555
0.7555
|
2
2
|
0.2121
0.2121
|
0.0943
0.0943
|
0.2829
0.2829
|
1.131
1.131
|
847.4
847.4
|
1013
1013
|
24,100
24,100
|
25,100
25,100
|
26,000
26,000
|
0.1010
0.1010
|
|
TBA
TBA
|
Redstart
Redstart
|
900.0
900.0
|
24/7
24/7
|
0.7065
0.7065
|
0.7981
0.7981
|
2
2
|
0.1936
0.1936
|
0.1291
0.1291
|
0.3873
0.3873
|
1.162
1.162
|
847.3
847.3
|
1157
1157
|
31,600
31,600
|
33,400
33,400
|
35,100
35,100
|
0.1002
0.1002
|
|
TBA
TBA
|
Baldpate
Baldpate
|
900.0
900.0
|
30/7
30/7
|
0.7068
0.7068
|
0.8717
0.8717
|
2
2
|
0.1732
0.1732
|
0.1732
0.1732
|
0.5196
0.5196
|
1.212
1.212
|
849.7
849.7
|
1408
1408
|
42,700
42,700
|
46,600
46,600
|
49,800
49,800
|
0.0991
0.0991
|
|
TBA
TBA
|
Ruddy
Ruddy
|
900.0
900.0
|
45/7
45/7
|
0.7066
0.7066
|
0.7555
0.7555
|
3
3
|
0.1414
0.1414
|
0.0943
0.0943
|
0.2829
0.2829
|
1.131
1.131
|
847.4
847.4
|
1013
1013
|
24,400
24,400
|
25,400
25,400
|
26,300
26,300
|
0.1010
0.1010
|
|
TBA
TBA
|
Canary
Canary
|
900.0
900.0
|
54/7
54/7
|
0.7069
0.7069
|
0.7985
0.7985
|
3
3
|
0.1291
0.1291
|
0.1291
0.1291
|
0.3873
0.3873
|
1.162
1.162
|
847.7
847.7
|
1158
1158
|
31,900
31,900
|
33,700
33,700
|
35,400
35,400
|
0.1002
0.1002
|
|
TBA
TBA
|
Catbird
Catbird
|
954.0
954.0
|
36/1
36/1
|
0.7494
0.7494
|
0.7702
0.7702
|
3
3
|
0.1628
0.1628
|
0.1628
0.1628
|
0.1628
0.1628
|
1.140
1.140
|
894.3
894.3
|
964
964
|
19,800
19,800
|
20,300
20,300
|
20,700
20,700
|
0.0953
0.0953
|
|
TBA
TBA
|
Corncrake
Corncrake
|
954.0
954.0
|
20/7
20/7
|
0.7492
0.7492
|
0.8010
0.8010
|
2
2
|
0.2184
0.2184
|
0.0971
0.0971
|
0.2913
0.2913
|
1.165
1.165
|
898.5
898.5
|
1074
1074
|
25,600
25,600
|
26,600
26,600
|
27,600
27,600
|
0.0953
0.0953
|
|
TBA
TBA
|
Redbird
Redbird
|
954.0
954.0
|
24/7
24/7
|
0.7495
0.7495
|
0.8466
0.8466
|
2
2
|
0.1994
0.1994
|
0.1329
0.1329
|
0.3987
0.3987
|
1.196
1.196
|
898.8
898.8
|
1228
1228
|
33,500
33,500
|
35,400
35,400
|
37,200
37,200
|
0.0945
0.0945
|
|
TBA
TBA
|
Merganser
Merganser
|
954.0
954.0
|
30/7
30/7
|
0.7491
0.7491
|
0.9239
0.9239
|
2
2
|
0.1783
0.1783
|
0.1783
0.1783
|
0.5349
0.5349
|
1.248
1.248
|
900.5
900.5
|
1492
1492
|
45,200
45,200
|
49,400
49,400
|
52,800
52,800
|
0.0935
0.0935
|
|
TBA
TBA
|
Canvasback
Canvasback
|
954.0
954.0
|
30/19
30/19
|
0.7491
0.7491
|
0.9199
0.9199
|
2
2
|
0.1783
0.1783
|
0.1070
0.1070
|
0.5350
0.5350
|
1.248
1.248
|
900.5
900.5
|
1480
1480
|
46,100
46,100
|
49,300
49,300
|
52,500
52,500
|
0.0935
0.0935
|
|
TBA
TBA
|
Phoenix
Phoenix
|
954.0
954.0
|
42/7
42/7
|
0.7491
0.7491
|
0.7876
0.7876
|
3
3
|
0.1507
0.1507
|
0.0837
0.0837
|
0.2511
0.2511
|
1.155
1.155
|
898.4
898.4
|
1029
1029
|
23,400
23,400
|
24,100
24,100
|
24,900
24,900
|
0.0955
0.0955
|
|
TBA
TBA
|
Rail
Rail
|
954.0
954.0
|
45/7
45/7
|
0.7492
0.7492
|
0.8010
0.8010
|
3
3
|
0.1456
0.1456
|
0.0971
0.0971
|
0.2913
0.2913
|
1.165
1.165
|
898.5
898.5
|
1074
1074
|
25,900
25,900
|
26,900
26,900
|
27,900
27,900
|
0.0953
0.0953
|
|
TBA
TBA
|
Towhee
Towhee
|
954.0
954.0
|
48/7
48/7
|
0.7495
0.7495
|
0.8157
0.8157
|
3
3
|
0.1410
0.1410
|
0.1097
0.1097
|
0.3291
0.3291
|
1.175
1.175
|
898.8
898.8
|
1123
1123
|
28,500
28,500
|
29,700
29,700
|
31,000
31,000
|
0.0950
0.0950
|
|
TBA
TBA
|
Cardinal
Cardinal
|
954.0
954.0
|
54/7
54/7
|
0.7491
0.7491
|
0.8462
0.8462
|
3
3
|
0.1329
0.1329
|
0.1329
0.1329
|
0.3987
0.3987
|
1.196
1.196
|
898.4
898.4
|
1227
1227
|
33,800
33,800
|
35,700
35,700
|
37,600
37,600
|
0.0945
0.0945
|
|
TBA
TBA
|
Vireo
Vireo
|
1027.4
1027.4
|
48/7
48/7
|
0.8069
0.8069
|
0.8781
0.8781
|
3
3
|
0.1463
0.1463
|
0.1138
0.1138
|
0.3414
0.3414
|
1.219
1.219
|
967.7
967.7
|
1209
1209
|
30,600
30,600
|
32,000
32,000
|
33,400
33,400
|
0.0882
0.0882
|
|
TBA
TBA
|
Tanager
Tanager
|
1033.5
1033.5
|
36/1
36/1
|
0.8114
0.8114
|
0.8339
0.8339
|
3
3
|
0.1694
0.1694
|
0.1694
0.1694
|
0.1694
0.1694
|
1.186
1.186
|
968.3
968.3
|
1044
1044
|
21,400
21,400
|
21,900
21,900
|
22,400
22,400
|
0.0880
0.0880
|
|
TBA
TBA
|
Snowbird
Snowbird
|
1033.5
1033.5
|
42/7
42/7
|
0.8121
0.8121
|
0.8539
0.8539
|
3
3
|
0.1569
0.1569
|
0.0872
0.0872
|
0.2616
0.2616
|
1.203
1.203
|
973.9
973.9
|
1115
1115
|
25,400
25,400
|
26,200
26,200
|
27,000
27,000
|
0.0881
0.0881
|
|
TBA
TBA
|
Ortolan
Ortolan
|
1033.5
1033.5
|
45/7
45/7
|
0.8112
0.8112
|
0.8673
0.8673
|
3
3
|
0.1515
0.1515
|
0.1010
0.1010
|
0.3030
0.3030
|
1.212
1.212
|
972.8
972.8
|
1163
1163
|
27,700
27,700
|
28,800
28,800
|
29,800
29,800
|
0.0880
0.0880
|
|
TBA
TBA
|
Whooper
Whooper
|
1033.5
1033.5
|
48/7
48/7
|
0.8113
0.8113
|
0.8829
0.8829
|
3
3
|
0.1467
0.1467
|
0.1141
0.1141
|
0.3423
0.3423
|
1.223
1.223
|
973.0
973.0
|
1215
1215
|
30,800
30,800
|
32,200
32,200
|
33,500
33,500
|
0.0878
0.0878
|
|
TBA
TBA
|
Curlew
Curlew
|
1033.5
1033.5
|
54/7
54/7
|
0.8112
0.8112
|
0.9164
0.9164
|
3
3
|
0.1383
0.1383
|
0.1383
0.1383
|
0.4149
0.4149
|
1.245
1.245
|
972.8
972.8
|
1329
1329
|
36,600
36,600
|
38,600
38,600
|
40,700
40,700
|
0.0873
0.0873
|
|
TBA
TBA
|
Avocet
Avocet
|
1113.0
1113.0
|
42/7
42/7
|
0.8743
0.8743
|
0.9192
0.9192
|
3
3
|
0.1628
0.1628
|
0.0904
0.0904
|
0.2712
0.2712
|
1.248
1.248
|
1049
1049
|
1201
1201
|
27,100
27,100
|
27,900
27,900
|
28,800
28,800
|
0.0818
0.0818
|
|
TBA
TBA
|
Bluejay
Bluejay
|
1113.0
1113.0
|
45/7
45/7
|
0.8745
0.8745
|
0.9350
0.9350
|
3
3
|
0.1573
0.1573
|
0.1049
0.1049
|
0.3147
0.3147
|
1.259
1.259
|
1049
1049
|
1254
1254
|
29,800
29,800
|
31,000
31,000
|
32,200
32,200
|
0.0816
0.0816
|
|
TBA
TBA
|
Bullfinch
Bullfinch
|
1113.0
1113.0
|
48/7
48/7
|
0.8744
0.8744
|
0.9516
0.9516
|
3
3
|
0.1523
0.1523
|
0.1185
0.1185
|
0.3555
0.3555
|
1.269
1.269
|
1049
1049
|
1310
1310
|
32,800
32,800
|
34,300
34,300
|
35,800
35,800
|
0.0814
0.0814
|
|
TBA
TBA
|
Finch
Finch
|
1113.0
1113.0
|
54/19
54/19
|
0.8746
0.8746
|
0.9855
0.9855
|
3
3
|
0.1436
0.1436
|
0.0862
0.0862
|
0.4310
0.4310
|
1.293
1.293
|
1054
1054
|
1430
1430
|
39,100
39,100
|
41,200
41,200
|
43,200
43,200
|
0.0814
0.0814
|
|
TBA
TBA
|
Oxbird
Oxbird
|
1192.5
1192.5
|
42/7
42/7
|
0.9366
0.9366
|
0.9848
0.9848
|
3
3
|
0.1685
0.1685
|
0.0936
0.0936
|
0.2808
0.2808
|
1.292
1.292
|
1123
1123
|
1286
1286
|
29,000
29,000
|
29,900
29,900
|
30,900
30,900
|
0.0764
0.0764
|
|
TBA
TBA
|
Bunting
Bunting
|
1192.5
1192.5
|
45/7
45/7
|
0.9367
0.9367
|
1.0014
1.0014
|
3
3
|
0.1628
0.1628
|
0.1085
0.1085
|
0.3255
0.3255
|
1.302
1.302
|
1123
1123
|
1342
1342
|
32,000
32,000
|
33,200
33,200
|
34,400
34,400
|
0.0762
0.0762
|
|
TBA
TBA
|
Cormorant
Cormorant
|
1192.5
1192.5
|
48/7
48/7
|
0.9364
0.9364
|
1.0190
1.0190
|
3
3
|
0.1576
0.1576
|
0.1226
0.1226
|
0.3678
0.3678
|
1.313
1.313
|
1123
1123
|
1403
1403
|
34,700
34,700
|
36,300
36,300
|
37,900
37,900
|
0.0760
0.0760
|
|
TBA
TBA
|
Grackle
Grackle
|
1192.5
1192.5
|
54/19
54/19
|
0.9365
0.9365
|
1.0552
1.0552
|
3
3
|
0.1486
0.1486
|
0.0892
0.0892
|
0.4460
0.4460
|
1.338
1.338
|
1129
1129
|
1532
1532
|
41,900
41,900
|
44,100
44,100
|
46,300
46,300
|
0.0760
0.0760
|
|
TBA
TBA
|
Skylark
Skylark
|
1272.0
1272.0
|
36/1
36/1
|
0.9993
0.9993
|
1.0271
1.0271
|
3
3
|
0.1880
0.1880
|
0.1880
0.1880
|
0.1880
0.1880
|
1.316
1.316
|
1193
1193
|
1287
1287
|
26,400
26,400
|
27,000
27,000
|
27,600
27,600
|
0.0715
0.0715
|
|
TBA
TBA
|
Scissortail
Scissortail
|
1272.0
1272.0
|
42/7
42/7
|
0.9987
0.9987
|
1.0501
1.0501
|
3
3
|
0.1740
0.1740
|
0.0967
0.0967
|
0.2901
0.2901
|
1.334
1.334
|
1198
1198
|
1372
1372
|
30,900
30,900
|
31,900
31,900
|
32,900
32,900
|
0.0716
0.0716
|
|
TBA
TBA
|
Bittern
Bittern
|
1272.0
1272.0
|
45/7
45/7
|
0.9987
0.9987
|
1.0678
1.0678
|
3
3
|
0.1681
0.1681
|
0.1121
0.1121
|
0.3363
0.3363
|
1.345
1.345
|
1198
1198
|
1432
1432
|
34,100
34,100
|
35,400
35,400
|
36,700
36,700
|
0.0715
0.0715
|
|
TBA
TBA
|
Diver
Diver
|
1272.0
1272.0
|
48/7
48/7
|
0.9992
0.9992
|
1.0873
1.0873
|
3
3
|
0.1628
0.1628
|
0.1266
0.1266
|
0.3798
0.3798
|
1.357
1.357
|
1198
1198
|
1496
1496
|
37,000
37,000
|
38,700
38,700
|
40,400
40,400
|
0.0713
0.0713
|
|
TBA
TBA
|
Pheasant
Pheasant
|
1272.0
1272.0
|
54/19
54/19
|
0.9993
0.9993
|
1.1259
1.1259
|
3
3
|
0.1535
0.1535
|
0.0921
0.0921
|
0.4605
0.4605
|
1.382
1.382
|
1204
1204
|
1634
1634
|
43,600
43,600
|
46,000
46,000
|
48,300
48,300
|
0.0712
0.0712
|
|
TBA
TBA
|
Frigate
Frigate
|
1351.5
1351.5
|
22/7
22/7
|
1.0619
1.0619
|
1.1661
1.1661
|
2
2
|
0.2479
0.2479
|
0.1377
0.1377
|
0.4131
0.4131
|
1.405
1.405
|
1273
1273
|
1626
1626
|
41,200
41,200
|
43,200
43,200
|
45,200
45,200
|
0.0670
0.0670
|
|
TBA
TBA
|
Ringdove
Ringdove
|
1351.5
1351.5
|
42/7
42/7
|
1.0617
1.0617
|
1.1163
1.1163
|
3
3
|
0.1794
0.1794
|
0.0997
0.0997
|
0.2991
0.2991
|
1.376
1.376
|
1273
1273
|
1458
1458
|
32,900
32,900
|
33,900
33,900
|
35,000
35,000
|
0.0674
0.0674
|
|
TBA
TBA
|
Dipper
Dipper
|
1351.5
1351.5
|
45/7
45/7
|
1.0614
1.0614
|
1.1347
1.1347
|
3
3
|
0.1733
0.1733
|
0.1155
0.1155
|
0.3465
0.3465
|
1.386
1.386
|
1273
1273
|
1521
1521
|
36,200
36,200
|
37,600
37,600
|
39,000
39,000
|
0.0672
0.0672
|
|
TBA
TBA
|
Martin
Martin
|
1351.5
1351.5
|
54/19
54/19
|
1.0614
1.0614
|
1.1958
1.1958
|
3
3
|
0.1582
0.1582
|
0.0949
0.0949
|
0.4745
0.4745
|
1.424
1.424
|
1279
1279
|
1735
1735
|
46,300
46,300
|
48,800
48,800
|
51,300
51,300
|
0.0671
0.0671
|
|
TBA
TBA
|
Popinjay
Popinjay
|
1431.0
1431.0
|
42/7
42/7
|
1.1241
1.1241
|
1.1820
1.1820
|
3
3
|
0.1846
0.1846
|
0.1026
0.1026
|
0.3078
0.3078
|
1.415
1.415
|
1348
1348
|
1544
1544
|
34,800
34,800
|
35,900
35,900
|
37,100
37,100
|
0.0636
0.0636
|
|
TBA
TBA
|
Bobolink
Bobolink
|
1431.0
1431.0
|
45/7
45/7
|
1.1236
1.1236
|
1.2013
1.2013
|
3
3
|
0.1783
0.1783
|
0.1189
0.1189
|
0.3567
0.3567
|
1.427
1.427
|
1347
1347
|
1610
1610
|
38,300
38,300
|
39,800
39,800
|
41,300
41,300
|
0.0635
0.0635
|
|
TBA
TBA
|
Wagtail
Wagtail
|
1431.0
1431.0
|
48/7
48/7
|
1.1244
1.1244
|
1.2236
1.2236
|
3
3
|
0.1727
0.1727
|
0.1343
0.1343
|
0.4029
0.4029
|
1.439
1.439
|
1348
1348
|
1684
1684
|
41,700
41,700
|
43,600
43,600
|
45,500
45,500
|
0.0633
0.0633
|
|
TBA
TBA
|
Plover
Plover
|
1431.0
1431.0
|
54/19
54/19
|
1.1241
1.1241
|
1.2665
1.2665
|
3
3
|
0.1628
0.1628
|
0.0977
0.0977
|
0.4885
0.4885
|
1.465
1.465
|
1355
1355
|
1838
1838
|
49,100
49,100
|
51,700
51,700
|
54,400
54,400
|
0.0633
0.0633
|
|
TBA
TBA
|
Nuthatch
Nuthatch
|
1510.5
1510.5
|
45/7
45/7
|
1.1862
1.1862
|
1.2682
1.2682
|
3
3
|
0.1832
0.1832
|
0.1221
0.1221
|
0.3663
0.3663
|
1.466
1.466
|
1423
1423
|
1701
1701
|
40,100
40,100
|
41,600
41,600
|
43,200
43,200
|
0.0602
0.0602
|
|
TBA
TBA
|
Parrot
Parrot
|
1510.5
1510.5
|
54/19
54/19
|
1.1856
1.1856
|
1.3357
1.3357
|
3
3
|
0.1672
0.1672
|
0.1003
0.1003
|
0.5015
0.5015
|
1.505
1.505
|
1429
1429
|
1938
1938
|
51,700
51,700
|
54,500
54,500
|
57,300
57,300
|
0.0600
0.0600
|
|
TBA
TBA
|
Ratite
Ratite
|
1590.0
1590.0
|
42/7
42/7
|
1.2492
1.2492
|
1.3134
1.3134
|
3
3
|
0.1946
0.1946
|
0.1081
0.1081
|
0.3243
0.3243
|
1.492
1.492
|
1498
1498
|
1715
1715
|
38,700
38,700
|
39,900
39,900
|
41,200
41,200
|
0.0573
0.0573
|
|
TBA
TBA
|
Lapwing
Lapwing
|
1590.0
1590.0
|
45/7
45/7
|
1.2492
1.2492
|
1.3355
1.3355
|
3
3
|
0.1880
0.1880
|
0.1253
0.1253
|
0.3759
0.3759
|
1.504
1.504
|
1498
1498
|
1790
1790
|
42,200
42,200
|
43,900
43,900
|
45,500
45,500
|
0.0571
0.0571
|
|
TBA
TBA
|
Hornbill
Hornbill
|
1590.0
1590.0
|
48/7
48/7
|
1.2487
1.2487
|
1.3589
1.3589
|
3
3
|
0.1820
0.1820
|
0.1416
0.1416
|
0.4248
0.4248
|
1.517
1.517
|
1498
1498
|
1871
1871
|
45,300
45,300
|
47,900
47,900
|
50,000
50,000
|
0.0570
0.0570
|
|
TBA
TBA
|
Falcon
Falcon
|
1590.0
1590.0
|
54/19
54/19
|
1.2489
1.2489
|
1.4072
1.4072
|
3
3
|
0.1716
0.1716
|
0.1030
0.1030
|
0.5150
0.5150
|
1.545
1.545
|
1505
1505
|
2042
2042
|
54,500
54,500
|
57,500
57,500
|
60,400
60,400
|
0.0570
0.0570
|
|
TBA
TBA
|
Smew
Smew
|
1780.0
1780.0
|
76/19
76/19
|
1.3973
1.3973
|
1.4734
1.4734
|
4
4
|
0.1530
0.1530
|
0.0714
0.0714
|
0.3570
0.3570
|
1.581
1.581
|
1684
1684
|
1942
1942
|
43,600
43,600
|
45,000
45,000
|
46,500
46,500
|
0.0514
0.0514
|
|
TBA
TBA
|
Chukar
Chukar
|
1780.0
1780.0
|
84/19
84/19
|
1.3986
1.3986
|
1.5126
1.5126
|
4
4
|
0.1456
0.1456
|
0.0874
0.0874
|
0.4370
0.4370
|
1.602
1.602
|
1685
1685
|
2072
2072
|
51,000
51,000
|
53,100
53,100
|
55,200
55,200
|
0.0512
0.0512
|
|
TBA
TBA
|
Woodpecker
Woodpecker
|
1843.0
1843.0
|
72/7
72/7
|
1.4476
1.4476
|
1.5102
1.5102
|
4
4
|
0.1600
0.1600
|
0.1067
0.1067
|
0.3201
0.3201
|
1.600
1.600
|
1745
1745
|
1957
1957
|
42,400
42,400
|
43,600
43,600
|
44,800
44,800
|
0.0497
0.0497
|
|
TBA
TBA
|
Seahawk
Seahawk
|
1869.0
1869.0
|
68/7
68/7
|
1.4681
1.4681
|
1.5147
1.5147
|
4
4
|
0.1658
0.1658
|
0.0921
0.0921
|
0.2763
0.2763
|
1.603
1.603
|
1769
1769
|
1927
1927
|
40,000
40,000
|
40,900
40,900
|
41,800
41,800
|
0.0491
0.0491
|
|
TBA
TBA
|
Mynah
Mynah
|
2000.0
2000.0
|
84/19
84/19
|
1.5707
1.5707
|
1.6987
1.6987
|
4
4
|
0.1543
0.1543
|
0.0926
0.0926
|
0.4630
0.4630
|
1.697
1.697
|
1893
1893
|
2327
2327
|
55,900
55,900
|
58,300
58,300
|
60,700
60,700
|
0.0456
0.0456
|
|
TBA
TBA
|
Mockingbird
Mockingbird
|
2034.5
2034.5
|
72/7
72/7
|
1.5979
1.5979
|
1.6670
1.6670
|
4
4
|
0.1681
0.1681
|
0.1121
0.1121
|
0.3363
0.3363
|
1.681
1.681
|
1926
1926
|
2160
2160
|
46,800
46,800
|
48,100
48,100
|
49,400
49,400
|
0.0450
0.0450
|
|
TBA
TBA
|
Roadrunner
Roadrunner
|
2057.0
2057.0
|
76/19
76/19
|
1.6152
1.6152
|
1.7032
1.7032
|
4
4
|
0.1645
0.1645
|
0.0768
0.0768
|
0.3840
0.3840
|
1.700
1.700
|
1946
1946
|
2245
2245
|
50,400
50,400
|
52,100
52,100
|
53,700
53,700
|
0.0445
0.0445
|
|
TBA
TBA
|
Dodo
Dodo
|
2129.0
2129.0
|
84/19
84/19
|
1.6721
1.6721
|
1.8082
1.8082
|
4
4
|
0.1592
0.1592
|
0.0955
0.0955
|
0.4775
0.4775
|
1.751
1.751
|
2015
2015
|
2477
2477
|
59,500
59,500
|
62,100
62,100
|
64,600
64,600
|
0.0428
0.0428
|
|
TBA
TBA
|
Cockatoo
Cockatoo
|
2156.0
2156.0
|
76/19
76/19
|
1.6927
1.6927
|
1.7849
1.7849
|
4
4
|
0.1684
0.1684
|
0.0786
0.0786
|
0.3930
0.3930
|
1.740
1.740
|
2040
2040
|
2353
2353
|
52,900
52,900
|
54,600
54,600
|
56,300
56,300
|
0.0425
0.0425
|
|
TBA
TBA
|
Bluebird
Bluebird
|
2156.0
2156.0
|
84/19
84/19
|
1.6931
1.6931
|
1.8309
1.8309
|
4
4
|
0.1602
0.1602
|
0.0961
0.0961
|
0.4805
0.4805
|
1.762
1.762
|
2040
2040
|
2507
2507
|
60,300
60,300
|
62,800
62,800
|
65,400
65,400
|
0.0423
0.0423
|
|
TBA
TBA
|
Kiwi
Kiwi
|
2167.0
2167.0
|
72/7
72/7
|
1.7022
1.7022
|
1.7758
1.7758
|
4
4
|
0.1735
0.1735
|
0.1157
0.1157
|
0.3471
0.3471
|
1.735
1.735
|
2051
2051
|
2300
2300
|
49,800
49,800
|
51,300
51,300
|
52,700
52,700
|
0.0423
0.0423
|
|
TBA
TBA
|
Cockatiel
Cockatiel
|
2300.0
2300.0
|
84/19
84/19
|
1.8070
1.8070
|
1.9541
1.9541
|
4
4
|
0.1655
0.1655
|
0.0993
0.0993
|
0.4965
0.4965
|
1.821
1.821
|
2178
2178
|
2677
2677
|
64,300
64,300
|
67,100
67,100
|
69,800
69,800
|
0.0396
0.0396
|
|
TBA
TBA
|
Thrasher
Thrasher
|
2312.0
2312.0
|
76/19
76/19
|
1.8155
1.8155
|
1.9144
1.9144
|
4
4
|
0.1744
0.1744
|
0.0814
0.0814
|
0.4070
0.4070
|
1.802
1.802
|
2188
2188
|
2524
2524
|
56,700
56,700
|
58,500
58,500
|
60,400
60,400
|
0.0396
0.0396
|
|
TBA
TBA
|
Kingfisher
Kingfisher
|
2385.0
2385.0
|
72/7
72/7
|
1.8731
1.8731
|
1.9540
1.9540
|
4
4
|
0.1820
0.1820
|
0.1213
0.1213
|
0.3639
0.3639
|
1.820
1.820
|
2257
2257
|
2531
2531
|
54,400
54,400
|
56,000
56,000
|
57,500
57,500
|
0.0384
0.0384
|
|
TBA
TBA
|
Joree
Joree
|
2515.0
2515.0
|
76/19
76/19
|
1.9750
1.9750
|
2.0826
2.0826
|
4
4
|
0.1819
0.1819
|
0.0849
0.0849
|
0.4245
0.4245
|
1.880
1.880
|
2380
2380
|
2745
2745
|
61,700
61,700
|
63,700
63,700
|
65,700
65,700
|
0.0364
0.0364
|