Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.275
3.24
|
220
5.59
|
1.335
3.39
|
80
2.03
|
1.973
5.01
|
26x14
26x14
|
60
1.52
|
2.093
5.32
|
3118
4640
|
4000
1814.37
|
25.1
63.75
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
1.464
3.72
|
220
5.59
|
1.524
3.87
|
110
2.79
|
2.222
5.64
|
21x12
21x12
|
75
1.91
|
2.342
5.95
|
4258
6337
|
6000
2721.55
|
28.1
71.37
|
| More Options |
1000 KCMIL
1000 KCMIL
|
61
61
|
1.117
2.84
|
1.613
4.10
|
220
5.59
|
1.673
4.25
|
110
2.79
|
2.369
6.02
|
21x12
21x12
|
75
1.91
|
2.519
6.40
|
5277
7853
|
8000
3628.74
|
30.2
76.71
|
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity Directly Buried 90C | Allowable Ampacity In Air 90C | |
| More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.030
0.04
|
0.030
0.04
|
0.044
0.07
|
0.358 + j0.252
0.358 + j0.252
|
0.031 + j0.044
0.031 + j0.044
|
20275
20275
|
497
497
|
616
616
|
| More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.023
0.03
|
0.026
0.04
|
0.042
0.06
|
0.333 + j0.214
0.333 + j0.214
|
0.024 + j0.042
0.024 + j0.042
|
26018
26018
|
551
551
|
706
706
|
| More Options |
1000 KCMIL
1000 KCMIL
|
0.011
0.02
|
0.019
0.03
|
0.023
0.03
|
0.040
0.06
|
0.315 + j0.189
0.315 + j0.189
|
0.020 + j0.040
0.020 + j0.040
|
26018
26018
|
596
596
|
813
813
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A