Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -40°C for cold bend and cold impact and marked with "LTGG" when CSA listed or dual UL/CSA listed. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground Size | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
1/0 AWG
1/0 AWG
|
10
10
|
0.336
0.85
|
0.814
2.07
|
220
5.59
|
0.874
2.22
|
1x6
1x6
|
2.259
5.74
|
75
1.91
|
2.409
6.12
|
2335
3475
|
1900
861.82
|
16.8
42.67
|
| More Options |
2/0 AWG
2/0 AWG
|
12
12
|
0.376
0.96
|
0.854
2.17
|
220
5.59
|
0.914
2.32
|
1x4
1x4
|
2.345
5.96
|
80
2.03
|
2.511
6.38
|
2620
3899
|
2395
1086.35
|
17.5
44.45
|
| More Options |
4/0 AWG
4/0 AWG
|
18
18
|
0.474
1.20
|
0.953
2.42
|
220
5.59
|
1.013
2.57
|
1x4
1x4
|
2.559
6.50
|
80
2.03
|
2.725
6.92
|
3089
4597
|
3808
1727.28
|
19.0
48.26
|
| More Options |
250 KCMIL
250 KCMIL
|
22
22
|
0.520
1.32
|
1.006
2.56
|
220
5.59
|
1.066
2.71
|
1x3/0
1x3/0
|
2.674
6.79
|
80
2.03
|
2.840
7.21
|
3734
5557
|
4500
2041.16
|
19.8
50.29
|
| More Options |
500 KCMIL
500 KCMIL
|
34
34
|
0.735
1.87
|
1.244
3.16
|
220
5.59
|
1.304
3.31
|
1x1
1x1
|
3.188
8.10
|
90
2.29
|
3.376
8.58
|
5019
7469
|
9000
4082.33
|
23.6
59.94
|
| More Options |
750 KCMIL
750 KCMIL
|
58
58
|
0.908
2.31
|
1.416
3.60
|
220
5.59
|
1.476
3.75
|
1x1
1x1
|
3.560
9.04
|
90
2.29
|
3.747
9.52
|
6127
9118
|
13500
6123.49
|
26.2
66.55
|
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
| More Options |
1/0 AWG
1/0 AWG
|
0.168
0.25
|
0.211
0.31
|
0.046
0.07
|
0.044
0.07
|
0.379 + j0.261
0.379 + j0.261
|
0.047 + j0.042
0.047 + j0.042
|
2738
2738
|
150
150
|
165
165
|
170
170
|
185
185
|
| More Options |
2/0 AWG
2/0 AWG
|
0.133
0.20
|
0.167
0.25
|
0.042
0.06
|
0.043
0.06
|
0.379 + j0.302
0.379 + j0.302
|
0.031 + j0.038
0.031 + j0.038
|
2862
2862
|
170
170
|
185
185
|
190
190
|
215
215
|
| More Options |
4/0 AWG
4/0 AWG
|
0.084
0.13
|
0.105
0.16
|
0.036
0.05
|
0.040
0.06
|
0.381 + j0.278
0.381 + j0.278
|
0.042 + j0.042
0.042 + j0.042
|
3166
3166
|
220
220
|
240
240
|
255
255
|
285
285
|
| More Options |
250 KCMIL
250 KCMIL
|
0.071
0.11
|
0.090
0.13
|
0.034
0.05
|
0.039
0.06
|
0.381 + j0.278
0.381 + j0.278
|
0.042 + j0.042
0.042 + j0.042
|
3333
3333
|
245
245
|
265
265
|
280
280
|
315
315
|
| More Options |
500 KCMIL
500 KCMIL
|
0.035
0.05
|
0.046
0.07
|
0.026
0.04
|
0.035
0.05
|
0.382 + j0.281
0.382 + j0.281
|
0.040 + j0.037
0.040 + j0.037
|
3999
3999
|
355
355
|
385
385
|
425
425
|
475
475
|
| More Options |
750 KCMIL
750 KCMIL
|
0.024
0.04
|
0.033
0.05
|
0.022
0.03
|
0.033
0.05
|
0.382 + j0.309
0.382 + j0.309
|
0.031 + j0.035
0.031 + j0.035
|
4566
4566
|
440
440
|
475
475
|
540
540
|
600
600
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(14) Detail 1.
* For Free Air: Table 310.60(C)(6).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
* Capacitive Reactance is between Phase-to-Shield.