SPEC: 83038

Quadruplex 600 Volt USE-2 HI-SCORE Underground Service Entrance or Street Lighting SPEC83038

Aluminum Conductor. HI-SCORE Cross-linked Polyethylene (XLP) Insulation

Download Category Specifications
PDF Excel Table

Application & Features

Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum, insulated with cross-linked polyethylene. Especially suited for applications requiring superior resistance to mechanical damage. Neutrals are identified by three yellow extruded stripes. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Three-phase conductors and one neutral conductor are cabled together to produce the quadruplex cable configuration. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL listed as USE-2 per UL 854 Service-Entrance Cables. These wet-rated cables can be direct buried underground or installed in a duct to power high-intensity street lighting circuits.

Specifications

Select more options below for part numbers, packaging, and color options:
Code Word Cond. Size Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Num x Neutral Size Neutral Stranding (mils) (mm) Neutral Insulation Thickness Ground Size Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km)
More Options
SWARTHMORE SWARTHMORE
3/0 AWG 3/0 AWG
17 17
0.456 1.16
80 2.03
0.616 1.56
1/0 1/0
7 0.18
80 80
AWG AWG
1.456 3.70
798 1188
More Options
WAKE FOREST WAKE FOREST
4/0 AWG 4/0 AWG
18 18
0.512 1.30
80 2.03
0.672 1.71
2/0 2/0
11 0.28
80 80
AWG AWG
1.588 4.03
973 1448
More Options
SLIPPERY ROCK SLIPPERY ROCK
350 KCMIL 350 KCMIL
30 30
0.661 1.68
95 2.41
0.851 2.16
4/0 4/0
17 0.43
80 80
KCMIL KCMIL
2.006 5.10
1547 2302
More Options
WOFFORD WOFFORD
500 KCMIL 500 KCMIL
37 37
0.789 2.00
95 2.41
0.979 2.49
350 350
33 0.84
95 95
KCMIL KCMIL
2.293 5.82
2180 3244

Notes:
1. The actual number of strands may differ for single input wire per ASTM B901
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Code Word Cond. Size Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity In Duct 90C
More Options
SWARTHMORE SWARTHMORE
3/0 AWG 3/0 AWG
7.3 18.54
4027 1826.61
0.105 0.16
0.131 0.19
0.042 0.06
155/175 155/175
More Options
WAKE FOREST WAKE FOREST
4/0 AWG 4/0 AWG
7.9 20.07
5078 2303.34
0.084 0.13
0.105 0.16
0.041 0.06
180/205 180/205
More Options
SLIPPERY ROCK SLIPPERY ROCK
350 KCMIL 350 KCMIL
12 30.48
8400 3810.17
0.051 0.08
0.064 0.10
0.040 0.06
250/280 250/280
More Options
WOFFORD WOFFORD
500 KCMIL 500 KCMIL
13.8 35.05
12000 5443.10
0.036 0.05
0.045 0.07
0.039 0.06
310/350 310/350

Notes:
1. Inductive reactance assumes cables are cradled in conduit, and the neutral is carrying no current.
2. Triple parallel inductive reactance calculation assumes the phase conductors are adjacent to one another.
3. Conductors assumed to be reverse lay stranded, compressed construction.
4. Phase spacing assumes cables are touching.
5. Resistances shown are for the Phase conductors only.
6. Ampacity based on 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor.

Standards & References

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • UL 854 Service Entrance Cable
  • ICEA S-81-570 Standard for 600 Volt Rated Cables of Ruggedized Design for Direct Burial Installations as Single Conductors or Assemblies of Single Conductors

Construction

  1. Conductor:Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum
  2. Insulation:Rugged Cross Linked Polyethylene (XLPE) meeting the requirements of ANSI/ICEA S-81-570. LLDPE and HDPE or MDPE
  3. Neutral:Cross Linked Polyethylene (XLPE) with three Yellow Extruded Stripes (YES)