SPEC: 48002

CU 600V LSZH RHH/RHW-2/RW90 SOLONONplus™ SPEC48002

SOLONONplus™ 600Volt Single Conductor Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type RHH/RHW-2/RW90

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 Volt SOLONONplus™ Type RHH/RHW-2/RW90 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and as otherwise permitted by the NEC® for Type RHH/RHW-2 or the CE Code for Type RW90. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

a. The conductors are available in tinned and flexible copper stranding upon request.
b. NEC compliant
c. The halogen content is less than 0.2% and Acid gas less than 2.0%
d. 70,000 BTU/Hr. Vertical Flame Test
e. UL listed for CT use on 1/0 and Larger
f. UL listed FT4 and ST-1 (limited smoke)
g. -40°C Cold impact and cold bend
h. Gasoline and Oil Resistant GRI and GRII
i. UV/Sunlight resistant all colors
j. Color available upon request

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Cond. Strands Strand Class Conductor Number Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Color Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km) DC Resistance at 25C (ohms/1000') (ohms/km) Max Pull Tension (lbs) (kg)
More Options
14 AWG 14 AWG
7 7
B B
1 1
0.071 0.18
45 1.14
BK BK
0.165 0.42
24 36
2.631 3.92
More Options
12 AWG 12 AWG
7 7
B B
1 1
0.089 0.23
45 1.14
BK BK
0.183 0.46
33 49
1.662 2.47
More Options
10 AWG 10 AWG
7 7
B B
1 1
0.113 0.29
45 1.14
BK BK
0.207 0.53
48 71
1.040 1.55
More Options
8 AWG 8 AWG
7 7
B B
1 1
0.142 0.36
60 1.52
BK BK
0.268 0.68
78 116
0.653 0.97
132 59.87
More Options
6 AWG 6 AWG
7 7
B B
1 1
0.178 0.45
60 1.52
BK BK
0.304 0.77
113 168
0.411 0.61
210 95.25
More Options
4 AWG 4 AWG
7 7
B B
1 1
0.225 0.57
60 1.52
BK BK
0.351 0.89
167 249
0.258 0.38
334 151.50
More Options
3 AWG 3 AWG
7 7
B B
1 1
0.252 0.64
60 1.52
GN GN
0.378 0.96
204 304
0.205 0.31
421 190.96
More Options
2 AWG 2 AWG
7 7
B B
1 1
0.283 0.72
60 1.52
BK BK
0.409 1.04
251 374
0.162 0.24
531 240.86
More Options
1 AWG 1 AWG
19 19
B B
1 1
0.322 0.82
80 2.03
BK BK
0.49 1.24
330 491
0.128 0.19
670 303.91
More Options
1/0 AWG 1/0 AWG
19 19
B B
1 1
0.362 0.92
80 2.03
BK BK
0.53 1.35
405 603
0.102 0.15
845 383.29
More Options
2/0 AWG 2/0 AWG
19 19
B B
1 1
0.405 1.03
80 2.03
BK BK
0.574 1.46
498 741
0.082 0.12
1065 483.08
More Options
3/0 AWG 3/0 AWG
19 19
B B
1 1
0.456 1.16
80 2.03
BK BK
0.624 1.58
614 914
0.064 0.10
1342 608.72
More Options
4/0 AWG 4/0 AWG
19 19
B B
1 1
0.512 1.30
80 2.03
BK BK
0.68 1.73
760 1131
0.051 0.08
1693 767.93
More Options
250 KCMIL 250 KCMIL
37 37
B B
1 1
0.558 1.42
95 2.41
BK BK
0.758 1.93
910 1354
0.043 0.06
2000 907.18
More Options
350 KCMIL 350 KCMIL
37 37
B B
1 1
0.661 1.68
95 2.41
BK BK
0.841 2.14
1236 1839
0.031 0.05
2800 1270.06
More Options
500 KCMIL 500 KCMIL
37 37
B B
1 1
0.789 2.00
95 2.41
BK BK
0.995 2.53
1733 2579
0.021 0.03
4000 1814.37
More Options
600 KCMIL 600 KCMIL
61 61
B B
1 1
0.866 2.20
110 2.79
BN BN
1.072 2.72
2084 3101
0.018 0.03
4800 2177.24
More Options
750 KCMIL 750 KCMIL
61 61
B B
1 1
0.968 2.46
110 2.79
BK BK
1.2 3.05
2579 3838
0.014 0.02
6000 2721.55
More Options
1000 KCMIL 1000 KCMIL
61 61
B B
1 1
1.117 2.84
110 2.79
BK BK
1.349 3.43
3388 5042
0.011 0.02
8000 3628.74

Tinned Copper Conductor
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • ISO 9001 Quality management
  • ISO 14001 Environmental management systems standard
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways (non-emergency circuits only)

Construction

  1. Conductor:Class B compressed stranded bare or tinned copper per ASTM B3, ASTM B8 and ASTM B33.
  2. Insulation:SOLONONplus™ Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type RHH/RHW-2/RW90