SPEC 45263 AL 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600Volt Three Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

Download Category Specifications
Excel Table

Application

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
675613
3 3
2 AWG 2 AWG
7 7
40 1.02
6 6
945 24.02
569 847
675618
3 3
1 AWG 1 AWG
8 8
50 1.27
6 6
1052 26.72
661 984
675620
3 3
1/0 AWG 1/0 AWG
10 10
50 1.27
4 4
1132 28.75
764 1137
675622
3 3
2/0 AWG 2/0 AWG
12 12
50 1.27
3 3
1218 30.95
880 1310
675624
3 3
3/0 AWG 3/0 AWG
15 15
50 1.27
4 4
1319 33.53
1002 1491
673253
3 3
4/0 AWG 4/0 AWG
19 19
50 1.27
2 2
1432 36.38
1141 1698
675626
3 3
250 KCMIL 250 KCMIL
22 22
60 1.52
2 2
1577 40.06
1367 2034
673497
3 3
600 KCMIL 600 KCMIL
41 41
70 1.78
600 600
2498 63.45
3359 4999
677400
3 3
750 KCMIL 750 KCMIL
58 58
70 1.78
3/0 3/0
2522 64.07
3581 5329

Standards & References

  • ASTM B801: Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836: Compact Rounded Stranded Aluminum Conductors
  • UL 83: Thermoplastic Insulated Wires and Cables
  • UL 1277: Electrical Power and Control Tray Cables
  • UL 1685: Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679: Control Cable Conductor Identification Method 4

Construction

  • Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  • Insulation: Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  • Grounding Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  • Filler: Paper filler (cable size 8 & 6 uses Polypropylene filler)
  • Binder: Polyester flat thread binder tape for cable sizes larger than 2 AWG
  • Overall Jacket: Polyvinyl Chloride (PVC) Jacket