Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
890674 |
2
2
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
355
9.03
|
67
100
|
|
890675 |
3
3
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
376
9.56
|
92
136
|
|
890676 |
4
4
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
409
10.41
|
111
166
|
|
890677 |
5
5
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
447
11.36
|
129
192
|
|
890678 |
7
7
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
486
12.35
|
172
256
|
|
890679 |
9
9
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
587
14.93
|
231
344
|
|
550407 |
12
12
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
670
17.02
|
299
445
|
|
550411 |
2
2
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
388
9.87
|
90
134
|
|
890681 |
3
3
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
412
10.46
|
121
180
|
|
890682 |
4
4
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
449
11.41
|
154
230
|
|
890683 |
5
5
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
491
12.48
|
179
266
|
|
890684 |
12
12
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
738
18.76
|
408
607
|
|
890685 |
3
3
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
463
11.77
|
167
249
|
|
890686 |
4
4
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
547
13.90
|
229
341
|
|
550420 |
5
5
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
587
14.93
|
270
402
|
|
550421 |
7
7
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
639
16.23
|
358
532
|
|