Southwire’s shielded Machine Flex® tray control cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. Southwire’s shielded flexible machine tray cable is ideal for use in for use in CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and bever- age, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Min. Bend Radius (in) (cm) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
18 AWG
18 AWG
|
2
2
|
16
16
|
0.044
0.11
|
15
0.38
|
45
1.14
|
0.293
0.74
|
24
36
|
52
77
|
7.148
10.64
|
8.613
12.82
|
3.5
8.89
|
-
-
|
14
14
|
| More Options |
18 AWG
18 AWG
|
3
3
|
16
16
|
0.044
0.11
|
15
0.38
|
45
1.14
|
0.320
0.81
|
30
45
|
63
94
|
7.148
10.64
|
8.613
12.82
|
3.8
9.65
|
-
-
|
14
14
|
| More Options |
18 AWG
18 AWG
|
4
4
|
16
16
|
0.044
0.11
|
15
0.38
|
45
1.14
|
0.326
0.83
|
36
54
|
70
104
|
7.148
10.64
|
8.613
12.82
|
3.9
9.91
|
-
-
|
11
11
|
| More Options |
18 AWG
18 AWG
|
5
5
|
16
16
|
0.044
0.11
|
15
0.38
|
45
1.14
|
0.353
0.90
|
43
64
|
82
122
|
7.148
10.64
|
8.613
12.82
|
4.2
10.67
|
-
-
|
11
11
|
| More Options |
18 AWG
18 AWG
|
7
7
|
16
16
|
0.044
0.11
|
15
0.38
|
45
1.14
|
0.378
0.96
|
55
82
|
100
149
|
7.148
10.64
|
8.613
12.82
|
4.5
11.43
|
-
-
|
9
9
|
| More Options |
18 AWG
18 AWG
|
9
9
|
16
16
|
0.044
0.11
|
15
0.38
|
45
1.14
|
0.442
1.12
|
68
101
|
129
192
|
7.148
10.64
|
8.613
12.82
|
5.3
13.46
|
-
-
|
9
9
|
| More Options |
18 AWG
18 AWG
|
12
12
|
16
16
|
0.044
0.11
|
15
0.38
|
45
1.14
|
0.478
1.21
|
86
128
|
155
231
|
7.148
10.64
|
8.613
12.82
|
5.7
14.48
|
-
-
|
7
7
|
| More Options |
18 AWG
18 AWG
|
18
18
|
16
16
|
0.044
0.11
|
15
0.38
|
60
1.52
|
0.576
1.46
|
119
177
|
222
330
|
7.148
10.64
|
8.613
12.82
|
6.9
17.53
|
-
-
|
7
7
|
| More Options |
18 AWG
18 AWG
|
25
25
|
16
16
|
0.044
0.11
|
15
0.38
|
60
1.52
|
0.658
1.67
|
161
240
|
289
430
|
7.148
10.64
|
8.613
12.82
|
7.8
19.81
|
-
-
|
6
6
|
| More Options |
16 AWG
16 AWG
|
2
2
|
26
26
|
0.059
0.15
|
15
0.38
|
45
1.14
|
0.321
0.82
|
34
51
|
66
98
|
4.487
6.68
|
5.406
8.05
|
3.8
9.65
|
-
-
|
18
18
|
| More Options |
16 AWG
16 AWG
|
3
3
|
26
26
|
0.059
0.15
|
15
0.38
|
45
1.14
|
0.331
0.84
|
43
64
|
78
116
|
4.487
6.68
|
5.406
8.05
|
3.9
9.91
|
-
-
|
18
18
|
| More Options |
16 AWG
16 AWG
|
4
4
|
26
26
|
0.059
0.15
|
15
0.38
|
45
1.14
|
0.360
0.91
|
53
79
|
93
138
|
4.487
6.68
|
5.406
8.05
|
4.3
10.92
|
-
-
|
14
14
|
| More Options |
16 AWG
16 AWG
|
5
5
|
26
26
|
0.059
0.15
|
15
0.38
|
45
1.14
|
0.391
0.99
|
63
94
|
110
164
|
4.487
6.68
|
5.406
8.05
|
4.6
11.68
|
-
-
|
14
14
|
| More Options |
16 AWG
16 AWG
|
7
7
|
26
26
|
0.059
0.15
|
15
0.38
|
45
1.14
|
0.427
1.08
|
80
119
|
135
201
|
4.487
6.68
|
5.406
8.05
|
5.1
12.95
|
-
-
|
12
12
|
| More Options |
16 AWG
16 AWG
|
9
9
|
26
26
|
0.059
0.15
|
15
0.38
|
45
1.14
|
0.491
1.25
|
100
149
|
171
254
|
4.487
6.68
|
5.406
8.05
|
5.8
14.73
|
-
-
|
12
12
|
| More Options |
16 AWG
16 AWG
|
12
12
|
26
26
|
0.059
0.15
|
15
0.38
|
60
1.52
|
0.562
1.43
|
128
190
|
220
327
|
4.487
6.68
|
5.406
8.05
|
6.7
17.02
|
-
-
|
9
9
|
| More Options |
16 AWG
16 AWG
|
18
18
|
26
26
|
0.059
0.15
|
15
0.38
|
60
1.52
|
0.646
1.64
|
185
275
|
303
451
|
4.487
6.68
|
5.406
8.05
|
7.7
19.56
|
-
-
|
9
9
|
| More Options |
16 AWG
16 AWG
|
25
25
|
26
26
|
0.059
0.15
|
15
0.38
|
60
1.52
|
0.746
1.89
|
248
369
|
398
592
|
4.487
6.68
|
5.406
8.05
|
8.9
22.61
|
-
-
|
8
8
|
| More Options |
14 AWG
14 AWG
|
2
2
|
41
41
|
0.073
0.19
|
15
0.38
|
45
1.14
|
0.349
0.89
|
48
71
|
84
125
|
2.814
4.19
|
3.391
5.05
|
4.1
10.41
|
20
20
|
25
25
|
| More Options |
14 AWG
14 AWG
|
3
3
|
41
41
|
0.073
0.19
|
15
0.38
|
45
1.14
|
0.363
0.92
|
62
92
|
102
152
|
2.814
4.19
|
3.391
5.05
|
4.3
10.92
|
20
20
|
25
25
|
| More Options |
14 AWG
14 AWG
|
4
4
|
41
41
|
0.073
0.19
|
15
0.38
|
45
1.14
|
0.402
1.02
|
76
113
|
125
186
|
2.814
4.19
|
3.391
5.05
|
4.8
12.19
|
16
16
|
20
20
|
| More Options |
14 AWG
14 AWG
|
5
5
|
41
41
|
0.073
0.19
|
15
0.38
|
45
1.14
|
0.431
1.09
|
91
135
|
144
214
|
2.814
4.19
|
3.391
5.05
|
5.1
12.95
|
16
16
|
20
20
|
| More Options |
14 AWG
14 AWG
|
7
7
|
41
41
|
0.073
0.19
|
15
0.38
|
45
1.14
|
0.466
1.18
|
119
177
|
178
265
|
2.814
4.19
|
3.391
5.05
|
5.5
13.97
|
14
14
|
17
17
|
| More Options |
14 AWG
14 AWG
|
12
12
|
41
41
|
0.073
0.19
|
15
0.38
|
60
1.52
|
0.623
1.58
|
192
286
|
297
442
|
2.814
4.19
|
3.391
5.05
|
7.4
18.80
|
10
10
|
12
12
|
| More Options |
14 AWG
14 AWG
|
18
18
|
41
41
|
0.073
0.19
|
15
0.38
|
60
1.52
|
0.720
1.83
|
277
412
|
412
613
|
2.814
4.19
|
3.391
5.05
|
8.6
21.84
|
10
10
|
12
12
|
| More Options |
14 AWG
14 AWG
|
25
25
|
41
41
|
0.073
0.19
|
15
0.38
|
80
2.03
|
0.875
2.22
|
384
571
|
582
866
|
2.814
4.19
|
3.391
5.05
|
10.5
26.67
|
9
9
|
11
11
|
| More Options |
12 AWG
12 AWG
|
2
2
|
65
65
|
0.094
0.24
|
15
0.38
|
45
1.14
|
0.387
0.98
|
70
104
|
112
167
|
1.774
2.64
|
2.137
3.18
|
4.6
11.68
|
25
25
|
30
30
|
| More Options |
12 AWG
12 AWG
|
3
3
|
65
65
|
0.094
0.24
|
15
0.38
|
45
1.14
|
0.416
1.06
|
91
135
|
142
211
|
1.774
2.64
|
2.137
3.18
|
4.9
12.45
|
25
25
|
30
30
|
| More Options |
12 AWG
12 AWG
|
4
4
|
65
65
|
0.094
0.24
|
15
0.38
|
45
1.14
|
0.450
1.14
|
114
170
|
172
256
|
1.774
2.64
|
2.137
3.18
|
5.4
13.72
|
20
20
|
24
24
|
| More Options |
12 AWG
12 AWG
|
5
5
|
65
65
|
0.094
0.24
|
15
0.38
|
45
1.14
|
0.489
1.24
|
138
205
|
207
308
|
1.774
2.64
|
2.137
3.18
|
5.8
14.73
|
20
20
|
24
24
|
| More Options |
12 AWG
12 AWG
|
7
7
|
65
65
|
0.094
0.24
|
15
0.38
|
60
1.52
|
0.555
1.41
|
181
269
|
268
399
|
1.774
2.64
|
2.137
3.18
|
6.6
16.76
|
17
17
|
21
21
|
| More Options |
10 AWG
10 AWG
|
2
2
|
105
105
|
0.117
0.30
|
20
0.51
|
60
1.52
|
0.455
1.16
|
102
152
|
159
237
|
1.111
1.65
|
1.339
1.99
|
5.4
13.72
|
35
35
|
40
40
|
| More Options |
10 AWG
10 AWG
|
3
3
|
105
105
|
0.117
0.30
|
20
0.51
|
60
1.52
|
0.544
1.38
|
136
202
|
218
324
|
1.111
1.65
|
1.339
1.99
|
6.5
16.51
|
35
35
|
40
40
|
| More Options |
10 AWG
10 AWG
|
4
4
|
105
105
|
0.117
0.30
|
20
0.51
|
60
1.52
|
0.574
1.46
|
177
263
|
268
399
|
1.111
1.65
|
1.339
1.99
|
6.8
17.27
|
28
28
|
32
32
|
| More Options |
10 AWG
10 AWG
|
5
5
|
105
105
|
0.117
0.30
|
20
0.51
|
60
1.52
|
0.608
1.54
|
212
315
|
316
470
|
1.111
1.65
|
1.339
1.99
|
7.2
18.29
|
28
28
|
32
32
|
| More Options |
10 AWG
10 AWG
|
7
7
|
105
105
|
0.117
0.30
|
20
0.51
|
60
1.52
|
0.658
1.67
|
280
417
|
394
586
|
1.111
1.65
|
1.339
1.99
|
7.8
19.81
|
24
24
|
28
28
|
| More Options |
8 AWG
8 AWG
|
4
4
|
168
168
|
0.153
0.39
|
30
0.76
|
60
1.52
|
0.742
1.88
|
292
435
|
438
652
|
0.715
1.06
|
0.861
1.28
|
8.9
22.61
|
40
40
|
44
44
|
| More Options |
6 AWG
6 AWG
|
4
4
|
259
259
|
0.198
0.50
|
30
0.76
|
60
1.52
|
0.885
2.25
|
463
689
|
668
994
|
0.450
0.67
|
0.541
0.81
|
10.6
26.92
|
52
52
|
60
60
|
| More Options |
4 AWG
4 AWG
|
4
4
|
420
420
|
0.235
0.60
|
40
1.02
|
80
2.03
|
1.057
2.68
|
674
1003
|
997
1484
|
0.282
0.42
|
0.340
0.51
|
12.6
32.00
|
68
68
|
76
76
|
| More Options |
2 AWG
2 AWG
|
4
4
|
651
651
|
0.302
0.77
|
40
1.02
|
80
2.03
|
1.237
3.14
|
1060
1577
|
1433
2133
|
0.179
0.27
|
0.216
0.32
|
14.8
37.59
|
92
92
|
104
104
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.