SPEC: 45006

CU 600V EPR Insulation Thermoset LSZH-TS Jacket RHH/RHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free SPEC45006

Power Cable 600Volt Single Conductor Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 USE-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket. CT Rated 1/0 and Larger - Silicone Free

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. CT Rated 1/0 and Larger - Silicone Free

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
1 1
7 7
0.142 0.36
15 0.38
15 0.38
0.271 0.69
51 76
75 112
More Options
6 AWG 6 AWG
1 1
7 7
0.178 0.45
30 0.76
30 0.76
0.342 0.87
81 121
120 179
More Options
2 AWG 2 AWG
1 1
7 7
0.283 0.72
45 1.14
30 0.76
0.447 1.14
205 305
260 387
More Options
1/0 AWG 1/0 AWG
1 1
19 19
0.362 0.92
45 1.14
45 1.14
0.575 1.46
326 485
419 624
More Options
2/0 AWG 2/0 AWG
1 1
19 19
0.405 1.03
55 1.40
45 1.14
0.617 1.57
411 612
512 762
More Options
3/0 AWG 3/0 AWG
1 1
19 19
0.456 1.16
45 1.14
45 1.14
0.669 1.70
518 771
629 936
More Options
4/0 AWG 4/0 AWG
1 1
19 19
0.512 1.30
45 1.14
45 1.14
0.711 1.81
653 972
771 1147
More Options
250 KCMIL 250 KCMIL
1 1
37 37
0.558 1.42
65 1.65
65 1.65
0.817 2.08
772 1149
945 1406
More Options
350 KCMIL 350 KCMIL
1 1
37 37
0.661 1.68
65 1.65
65 1.65
0.916 2.33
1081 1609
1281 1906
More Options
500 KCMIL 500 KCMIL
1 1
37 37
0.789 2.00
65 1.65
65 1.65
1.041 2.64
1544 2298
1775 2641
More Options
750 KCMIL 750 KCMIL
1 1
61 61
0.968 2.46
65 1.65
65 1.65
1.275 3.24
2316 3447
2633 3918

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
* Tinned Copper

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
8 AWG 8 AWG
1 1
1.1 2.79
132 59.87
0.653 0.97
0.810 1.21
0.052 0.08
50 50
55 55
More Options
6 AWG 6 AWG
1 1
1.4 3.56
209 94.80
0.411 0.61
0.510 0.76
0.051 0.08
65 65
75 75
More Options
2 AWG 2 AWG
1 1
1.8 4.57
530 240.40
0.162 0.24
0.201 0.30
0.045 0.07
115 115
130 130
More Options
1/0 AWG 1/0 AWG
1 1
2.3 5.84
844 382.83
0.102 0.15
0.127 0.19
0.044 0.07
150 150
170 170
More Options
2/0 AWG 2/0 AWG
1 1
2.5 6.35
1064 482.62
0.082 0.12
0.102 0.15
0.043 0.06
175 175
195 195
More Options
3/0 AWG 3/0 AWG
1 1
2.7 6.86
1342 608.72
0.064 0.10
0.079 0.12
0.042 0.06
200 200
225 225
More Options
4/0 AWG 4/0 AWG
1 1
2.8 7.11
1692 767.48
0.051 0.08
0.063 0.09
0.041 0.06
230 230
260 260
More Options
250 KCMIL 250 KCMIL
1 1
3.3 8.38
2000 907.18
0.043 0.06
0.053 0.08
0.041 0.06
255 255
290 290
More Options
350 KCMIL 350 KCMIL
1 1
3.7 9.40
2800 1270.06
0.031 0.05
0.039 0.06
0.040 0.06
310 310
350 350
More Options
500 KCMIL 500 KCMIL
1 1
5.2 13.21
4000 1814.37
0.021 0.03
0.027 0.04
0.039 0.06
380 380
430 430
More Options
750 KCMIL 750 KCMIL
1 1
6.4 16.26
6000 2721.55
0.014 0.02
0.019 0.03
0.038 0.06
475 475
535 535

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE Sizes 1/0 AWG and Larger

Construction

  1. Conductor:Class B compressed stranded bare or tinned copper per ASTM B3, ASTM B8 and ASTM B33
  2. Binder Tape:Mylar Tape
  3. Insulation:Ethylene Propylene Rubber (EPR) Type RHH/RHW-2 USE-2
  4. Overall Jacket:Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Silicone-Free Jacket

Resources