SPEC: 45103

CU 600/1000V XLPE Insulation PVC Jacket XHHW-2 With Green Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free SPEC45103

Type TC-ER Control Cable 600 or 1000 Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Insulated Green CU Ground, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 or 1000 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone Free

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Color Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
14 AWG 14 AWG
3 3
7 7
BK,RD,BE,GN BK,RD,BE,GN
30 0.76
45 1.14
0.409 1.04
51 76
110 164
2.631 3.92
3.170 4.72
1.6 4.06
20 20
25 25
More Options
12 AWG 12 AWG
2 2
7 7
BK,RD,GN BK,RD,GN
30 0.76
45 1.14
0.425 1.08
61 91
122 182
1.662 2.47
2.002 2.98
1.7 4.32
25 25
30 30
More Options
12 AWG 12 AWG
3 3
7 7
BK,RD,BE,GN BK,RD,BE,GN
30 0.76
45 1.14
0.449 1.14
81 121
152 226
1.662 2.47
2.002 2.98
1.8 4.57
25 25
30 30
More Options
12 AWG 12 AWG
4 4
7 7
BK,RD,BE,OE,GN BK,RD,BE,OE,GN
30 0.76
45 1.14
0.491 1.25
101 150
176 262
1.662 2.47
2.002 2.98
2.0 5.08
20 20
24 24
More Options
10 AWG 10 AWG
2 2
7 7
BK,RD,GN BK,RD,GN
30 0.76
45 1.14
0.476 1.21
97 144
168 250
1.040 1.55
1.253 1.86
1.9 4.83
35 35
40 40
More Options
10 AWG 10 AWG
3 3
7 7
BK,RD,BE,GN BK,RD,BE,GN
30 0.76
45 1.14
0.547 1.39
129 192
224 333
1.040 1.55
1.253 1.86
2.2 5.59
35 35
40 40
More Options
10 AWG 10 AWG
4 4
7 7
BK,RD,BE,OE,GN BK,RD,BE,OE,GN
30 0.76
60 1.52
0.603 1.53
161 240
273 406
1.040 1.55
1.253 1.86
2.4 6.10
28 28
32 32
More Options
10 AWG 10 AWG
5 5
7 7
BK,RD,BE,OE,YW,GN BK,RD,BE,OE,YW,GN
30 0.76
60 1.52
0.657 1.67
193 287
322 479
1.040 1.55
1.253 1.86
2.6 6.60
28 28
32 32

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Note: Conductor number = number of phase conductors. Does not include green ground.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • VW-1 (Vertical-Wire) Flame Test

Construction

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes
  3. Grounding Conductor:Class B compressed stranded copper with green insulation
  4. Filler:Polypropylene filler
  5. Overall Jacket:Polyvinyl Chloride (PVC) Jacket