Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Type (TC-ER) per NEC 336.10. Silicone free.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Ground Size | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
8 AWG
8 AWG
|
2
2
|
7
7
|
0.142
0.36
|
45
1.14
|
1x10
1x10
|
60
1.52
|
0.592
1.50
|
135
201
|
234
348
|
| More Options |
6 AWG
6 AWG
|
2
2
|
7
7
|
0.178
0.45
|
45
1.14
|
1x8
1x8
|
60
1.52
|
0.691
1.76
|
215
320
|
343
510
|
| More Options |
4 AWG
4 AWG
|
2
2
|
7
7
|
0.225
0.57
|
45
1.14
|
1x8
1x8
|
60
1.52
|
0.764
1.94
|
312
464
|
448
667
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
GG indicates green ground. Others are bare.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
8 AWG
8 AWG
|
2
2
|
2.4
6.10
|
264
119.75
|
0.653
0.97
|
0.810
1.21
|
0.052
0.08
|
50
50
|
55
55
|
| More Options |
6 AWG
6 AWG
|
2
2
|
2.8
7.11
|
419
190.06
|
0.411
0.61
|
0.510
0.76
|
0.051
0.08
|
65
65
|
75
75
|
| More Options |
4 AWG
4 AWG
|
2
2
|
3.1
7.87
|
667
302.55
|
0.258
0.38
|
0.320
0.48
|
0.048
0.07
|
85
85
|
95
95
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.