SPEC: 47302

3/C CU 2KV Type SHD-GC RHINOSHIELDTM CPE Mining Cable 90°C. CSA - MSHA Approved SPEC47302

Flexible Copper conductors, EPR 100% Insulation Level, Cu/Nylon Braid Shield, Extra Heavy Duty Two Layer Chlorinated Polyethylene (CPE) Jacket with Optional Reflective Stripes

Download Category Specifications
PDF Excel Table

Application & Features

RHINOSHIELDTM Type SHD-GC is a heavy-duty trailing cable where flexibility and maximum protection is required. For use with mobile, reeling, or stationary mining equipment, continuous mining machines, longwall mining systems, and blast hole drillers. It is also an ex- cellent choice for shovels, draglines, dredges, cranes and marine shore-to-ship power supplies, and anytime extra-durable, flexible cable is required. Suitable for continuous submersion in water. Ground check conductor provides fail-safe ground monitoring. Embossed print legend for easy cable identification. Cold Bend and Impact Tested to -50°C.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Ground Check Size Inner Jacket Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km)
More Options
14 AWG 14 AWG
3 3
41 41
0.073 0.19
60 1.52
0.199 0.51
14 14
130 3.30
0.852 2.16
368 548
More Options
10 AWG 10 AWG
3 3
104 104
0.117 0.30
60 1.52
0.24 0.61
12 12
155 3.94
1 2.54
554 824
More Options
8 AWG 8 AWG
3 3
168 168
0.153 0.39
70 1.78
0.301 0.76
10 10
145 3.68
1.093 2.78
740 1101
More Options
6 AWG 6 AWG
3 3
133 133
0.198 0.50
70 1.78
0.356 0.90
10 10
165 4.19
1.247 3.17
874 1301
More Options
4 AWG 4 AWG
3 3
259 259
0.235 0.60
70 1.78
0.4 1.02
8 8
180 4.57
1.366 3.47
1227 1826
More Options
2 AWG 2 AWG
3 3
308 308
0.302 0.77
70 1.78
0.466 1.18
8 8
180 4.57
1.535 3.90
1743 2594
More Options
1 AWG 1 AWG
3 3
385 385
0.355 0.90
80 2.03
0.512 1.30
8 8
235 5.97
1.732 4.40
2249 3347
More Options
1/0 AWG 1/0 AWG
3 3
273 273
0.354 0.90
80 2.03
0.557 1.41
8 8
290 7.37
1.85 4.70
2590 3854
More Options
2/0 AWG 2/0 AWG
3 3
324 324
0.4 1.02
110 2.79
0.714 1.81
8 8
245 6.22
245 6.22
2.165 5.50
3113 4633
More Options
3/0 AWG 3/0 AWG
3 3
418 418
0.533 1.35
80 2.03
0.672 1.71
8 8
120 3.05
150 3.81
2.126 5.40
3651 5433
More Options
4/0 AWG 4/0 AWG
3 3
532 532
0.55 1.40
80 2.03
0.751 1.91
8 8
260 6.60
2.298 5.84
3873 5764
More Options
250 KCMIL 250 KCMIL
3 3
608 608
0.682 1.73
100 2.54
0.816 2.07
6 6
100 2.54
205 5.21
2.480 6.30
4888 7274
More Options
350 KCMIL 350 KCMIL
3 3
855 855
0.809 2.05
100 2.54
0.926 2.35
6 6
100 2.54
135 3.43
2.795 7.10
6204 9233
More Options
500 KCMIL 500 KCMIL
3 3
1221 1221
0.987 2.51
100 2.54
1.106 2.81
6 6
155 3.94
190 4.83
3.189 8.10
9022 13426

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Rated Strength (lbs) (kg) Min. Bend Radius (in) (cm) Allowable Ampacity In Air 90C
More Options
14 AWG 14 AWG
2.621 3.90
3.311 4.93
0.045 0.07
28 12.70
6.8 17.27
More Options
10 AWG 10 AWG
1.040 1.55
1.314 1.96
0.038 0.06
70 31.75
8 20.32
More Options
8 AWG 8 AWG
0.666 0.99
0.841 1.25
0.037 0.06
112 50.80
8.7 22.10
59 59
More Options
6 AWG 6 AWG
0.450 0.67
0.568 0.85
0.035 0.05
179 81.19
9.9 25.15
79 79
More Options
4 AWG 4 AWG
0.263 0.39
0.332 0.49
0.034 0.05
285 129.27
10.9 27.69
104 104
More Options
2 AWG 2 AWG
0.167 0.25
0.211 0.31
0.032 0.05
453 205.48
12.2 30.99
138 138
More Options
1 AWG 1 AWG
0.143 0.21
0.180 0.27
0.031 0.05
572 259.45
13.8 35.05
161 161
More Options
1/0 AWG 1/0 AWG
0.105 0.16
0.132 0.20
0.032 0.05
722 327.49
14.8 37.59
186 186
More Options
2/0 AWG 2/0 AWG
0.084 0.13
0.106 0.16
0.035 0.05
910 412.77
17.3 43.94
215 215
More Options
3/0 AWG 3/0 AWG
0.072 0.11
0.091 0.14
0.027 0.04
1147 520.27
17.0 43.18
249 249
More Options
4/0 AWG 4/0 AWG
0.053 0.08
0.068 0.10
0.029 0.04
1447 656.35
18.3 46.48
287 287
More Options
250 KCMIL 250 KCMIL
0.048 0.07
0.062 0.09
0.026 0.04
1710 775.64
19.8 50.29
320 320
More Options
350 KCMIL 350 KCMIL
0.035 0.05
0.046 0.07
0.025 0.04
2394 1085.90
22.3 56.64
394 394
More Options
500 KCMIL 500 KCMIL
0.024 0.04
0.034 0.05
0.024 0.04
3420 1551.28
25.5 64.77
487 487

* Ampacities based upon ICEA S-75-381 Table H-1.

Standards & References

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • CSA C22.2 No. 96 Portable Power Cables
  • ICEA S-75-381 Portable and Power Feeder Cables for Use in Mines
  • MSHA Approved

Construction

  1. Conductor:Tin coated, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B33/B172
  2. Separator Tape:Semi-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Rubber (EPR) 100% Insulation Level
  4. Braid Shield:Tin coated, soft drawn, annealed, copper braid shield (60% minimum coverage), combined with color coded nylon (Black, Red, Blue) with a 40% maximum coverage
  5. Ground Conductors:Two uninsulated, tin coated, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B33/B172
  6. Ground Check Conductor:Tin coated, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B33/B172 with yellow, high strength, polypropylene insulation
  7. Filler:Rubber fillers as needed
  8. Tape:SBR tape applied over the cabled core for improved mechanical integrity and ease of stripping. Reinforcing twine applied between SBR tape and outer jacket
  9. Outer Jacket:Black, mold cured, extra heavy-duty, flame resistant, thermosetting Chlorinated Polyethylene (CPE). Other colors available
  10. Reflective Stripe (Optional):Highly visible reflective stripe embedded into the outer jacket to increase safety and help prevent cable runover.

Resources

There are no downloadable resources for this product.