Southwire's 35kV cables are suited for use in wet and dry areas, conduits, ducts, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
| Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground Size | Concentric Neutral | Neutral DC Resistance 25C (ohms/1000') (ohms/km) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | |
| More Options |
19
19
|
0.362
0.92
|
1.072
2.72
|
345
8.76
|
1.182
3.00
|
AWG
AWG
|
6x14
6x14
|
0.540
0.80
|
50
1.27
|
1.41
3.58
|
786
1170
|
9.9
25.15
|
633
287.12
|
| More Options |
19
19
|
0.395
1.00
|
1.115
2.83
|
345
8.76
|
1.225
3.11
|
AWG
AWG
|
7x14
7x14
|
0.463
0.69
|
50
1.27
|
1.453
3.69
|
855
1272
|
10.2
25.91
|
798
361.97
|
| More Options |
19
19
|
0.498
1.26
|
1.218
3.09
|
345
8.76
|
1.328
3.37
|
AWG
AWG
|
11x14
11x14
|
0.295
0.44
|
50
1.27
|
1.556
3.95
|
1052
1566
|
10.9
27.69
|
1269
575.61
|
| More Options |
37
37
|
0.789
2.00
|
1.519
3.86
|
345
8.76
|
1.629
4.14
|
KCMIL
KCMIL
|
16x12
16x12
|
0.128
0.19
|
75
1.91
|
1.945
4.94
|
1837
2734
|
13.6
34.54
|
3000
1360.78
|
| More Options |
61
61
|
1.117
2.84
|
1.857
4.72
|
345
8.76
|
1.997
5.07
|
KCMIL
KCMIL
|
20x10
20x10
|
0.064
0.10
|
75
1.91
|
2.355
5.98
|
3023
4499
|
16.5
41.91
|
6000
2721.55
|
* Pulling tension based on pulling eye directly connected to conductor
^ HiDri Plus® - Water Blocking Powder
^^ HiDri Plus® - Water Blocking Powder. All Black Jacket
^^^ HiDri Plus® - Water Blocking Powder, UL listed MV-90 Rated
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Charging Current (A/1000') (A/km) | Dielectric Loss (W/1000') (W/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity Directly Buried 90C | |
| More Options |
1/0 AWG
1/0 AWG
|
0.167
0.25
|
0.229
0.34
|
0.067
0.10
|
0.053
0.08
|
0.3
0.45
|
6.1
9.08
|
0.562+j0.278
0.562+j0.278
|
0.230+j0.059
0.230+j0.059
|
2095
2095
|
160
160
|
195
195
|
| More Options |
2/0 AWG
2/0 AWG
|
0.133
0.20
|
0.182
0.27
|
0.064
0.10
|
0.052
0.08
|
0.31
0.46
|
6.3
9.38
|
0.497+j0.232
0.497+j0.232
|
0.183+j0.057
0.183+j0.057
|
2444
2444
|
185
185
|
220
220
|
| More Options |
4/0 AWG
4/0 AWG
|
0.084
0.13
|
0.115
0.17
|
0.056
0.08
|
0.048
0.07
|
0.36
0.54
|
7.3
10.86
|
0.359+j0.130
0.359+j0.130
|
0.117+j0.053
0.117+j0.053
|
3840
3840
|
235
235
|
285
285
|
| More Options |
500 KCMIL
500 KCMIL
|
0.036
0.05
|
0.050
0.07
|
0.041
0.06
|
0.042
0.06
|
0.5
0.74
|
10.0
14.88
|
0.172+j0.047
0.172+j0.047
|
0.054+j0.047
0.054+j0.047
|
8865
8865
|
380
380
|
445
445
|
| More Options |
1000 KCMIL
1000 KCMIL
|
0.017
0.03
|
0.025
0.04
|
0.031
0.05
|
0.039
0.06
|
0.65
0.97
|
13.1
19.49
|
0.088+j0.026
0.088+j0.026
|
0.033+j0.041
0.033+j0.041
|
17615
17615
|
530
530
|
585
585
|
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.