Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -25°C for cold bend. ST1 (low smoke) Rated for sizes 1/0 and larger. Rated for 1000 lbs./FT maximum sidewall pressure.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
| More Options |
2 AWG
2 AWG
|
7
7
|
0.283
0.72
|
0.551
1.40
|
115
2.92
|
0.611
1.55
|
55
1.40
|
0.755
1.92
|
463
689
|
530
240.40
|
9.1
23.11
|
2
5.08
|
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
0.674
1.71
|
115
2.92
|
0.734
1.86
|
80
2.03
|
0.914
2.32
|
762
1134
|
1064
482.62
|
11
27.94
|
2.5
6.35
|
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
0.78
1.98
|
115
2.92
|
0.84
2.13
|
80
2.03
|
1.02
2.59
|
1059
1576
|
1692
767.48
|
12.2
30.99
|
2.5
6.35
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
0.818
2.08
|
115
2.92
|
0.878
2.23
|
80
2.03
|
1.058
2.69
|
1194
1777
|
2000
907.18
|
12.6
32.00
|
3.0
7.62
|
| More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
0.917
2.33
|
115
2.92
|
0.977
2.48
|
80
2.03
|
1.157
2.94
|
1558
2319
|
2800
1270.06
|
13.9
35.31
|
3
7.62
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.042
2.65
|
115
2.92
|
1.102
2.80
|
80
2.03
|
1.282
3.26
|
2087
3106
|
4000
1814.37
|
15.4
39.12
|
3.5
8.89
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
1.254
3.19
|
115
2.92
|
1.314
3.34
|
80
2.03
|
1.494
3.79
|
2974
4426
|
6000
2721.55
|
17.9
45.47
|
4
10.16
|
* Conduit size based on 3 phase 40% fill-factor without ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
| More Options |
2 AWG
2 AWG
|
0.162
0.24
|
0.221
0.33
|
0.028
0.04
|
0.044
0.07
|
0.566+j0.549
0.566+j0.549
|
0.222+j0.051
0.222+j0.051
|
1924
1924
|
135
135
|
145
145
|
140
140
|
154
154
|
| More Options |
2/0 AWG
2/0 AWG
|
0.082
0.12
|
0.112
0.17
|
0.022
0.03
|
0.040
0.06
|
0.468+j0.487
0.468+j0.487
|
0.113+j0.046
0.113+j0.046
|
2305
2305
|
200
200
|
220
220
|
215
215
|
240
240
|
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.070
0.10
|
0.018
0.03
|
0.038
0.06
|
0.431+j0.440
0.431+j0.440
|
0.071+j0.043
0.071+j0.043
|
2634
2634
|
265
265
|
280
280
|
285
285
|
320
320
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.056
0.08
|
0.020
0.03
|
0.037
0.06
|
0.384 + j0.304
0.384 + j0.304
|
0.034 + j0.033
0.034 + j0.033
|
2800
2800
|
320
320
|
345
345
|
445
445
|
495
495
|
| More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.043
0.06
|
0.014
0.02
|
0.035
0.05
|
0.403+j0.387
0.403+j0.387
|
0.044+j0.040
0.044+j0.040
|
3058
3058
|
355
355
|
380
380
|
395
395
|
440
440
|
| More Options |
500 KCMIL
500 KCMIL
|
0.021
0.03
|
0.030
0.04
|
0.012
0.02
|
0.033
0.05
|
0.386+j0.346
0.386+j0.346
|
0.031+j0.038
0.031+j0.038
|
3445
3445
|
430
430
|
460
460
|
485
485
|
545
545
|
| More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.021
0.03
|
0.011
0.02
|
0.032
0.05
|
0.364+j0.289
0.364+j0.289
|
0.022+j0.037
0.022+j0.037
|
4102
4102
|
530
530
|
570
570
|
615
615
|
685
685
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.