SPEC: 46002

CU Compressed 2.4kV NLEPR Insulation PVC Jacket. MV 90. SPEC46002

Type MV-90 Single Conductor Copper, No Lead Ethylene Propylene Rubber (NL-EPR) Polyvinyl Chloride (PVC) Jacket

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 2.4KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Conduit Size (in) (cm)
More Options
2 AWG 2 AWG
7 7
0.282 0.72
0.570 1.45
125 3.18
25 0.64
0.746 1.89
413 615
530 240.40
5.9 14.99
2.5 6.35
More Options
1 AWG 1 AWG
19 19
0.322 0.82
0.610 1.55
125 3.18
85 2.16
0.786 2.00
484 720
669 303.45
6.2 15.75
2.5 6.35
More Options
1/0 AWG 1/0 AWG
19 19
0.361 0.92
0.650 1.65
125 3.18
85 2.16
0.826 2.10
568 845
844 382.83
6.6 16.76
2.5 6.35
More Options
2/0 AWG 2/0 AWG
19 19
0.405 1.03
0.695 1.77
125 3.18
85 2.16
0.871 2.21
671 999
1064 482.62
6.9 17.53
2.5 6.35
More Options
3/0 AWG 3/0 AWG
19 19
0.456 1.16
0.745 1.89
125 3.18
105 2.67
0.955 2.43
830 1235
1342 608.72
7.6 19.30
3.0 7.62
More Options
4/0 AWG 4/0 AWG
19 19
0.512 1.30
0.785 1.99
125 3.18
105 2.67
0.995 2.53
978 1455
1692 767.48
7.9 20.07
3.0 7.62
More Options
250 KCMIL 250 KCMIL
37 37
0.558 1.42
0.870 2.21
140 3.56
120 3.05
1.112 2.82
1179 1755
2000 907.18
8.8 22.35
3.5 8.89
More Options
350 KCMIL 350 KCMIL
37 37
0.661 1.68
0.965 2.45
140 3.56
120 3.05
1.207 3.07
1531 2278
2800 1270.06
9.6 24.38
3.5 8.89
More Options
500 KCMIL 500 KCMIL
37 37
0.789 2.00
1.090 2.77
140 3.56
120 3.05
1.322 3.36
2052 3054
4000 1814.37
10.5 26.67
4.0 10.16
More Options
750 KCMIL 750 KCMIL
61 61
0.968 2.46
1.335 3.39
155 3.94
135 3.43
1.611 4.09
3038 4521
6000 2721.55
12.8 32.51
4.5 11.43
More Options
1000 KCMIL 1000 KCMIL
61 61
1.117 2.84
1.485 3.77
155 3.94
135 3.43
1.761 4.47
3893 5793
8000 3628.74
14.0 35.56
5.0 12.70

* Conduit size based on 3 phase 40% fill-factor without ground

Cond. Size DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity In Duct 90C Allowable Ampacity In Duct 105C Allowable Ampacity In Air 90C Allowable Ampacity In Air 105C
More Options
2 AWG 2 AWG
0.162 0.24
0.204 0.30
0.043 0.06
145 145
- -
190 190
- -
More Options
1 AWG 1 AWG
0.128 0.19
0.162 0.24
0.042 0.06
170 170
- -
225 225
- -
More Options
1/0 AWG 1/0 AWG
0.102 0.15
0.128 0.19
0.040 0.06
195 195
- -
260 260
- -
More Options
2/0 AWG 2/0 AWG
0.081 0.12
0.102 0.15
0.039 0.06
220 220
- -
300 300
- -
More Options
3/0 AWG 3/0 AWG
0.064 0.10
0.081 0.12
0.038 0.06
250 250
- -
345 345
- -
More Options
4/0 AWG 4/0 AWG
0.051 0.08
0.065 0.10
0.037 0.05
290 290
- -
400 400
- -
More Options
250 KCMIL 250 KCMIL
0.043 0.06
0.056 0.08
0.037 0.06
320 320
- -
445 445
- -
More Options
350 KCMIL 350 KCMIL
0.031 0.05
0.041 0.06
0.036 0.05
385 385
- -
550 550
- -
More Options
500 KCMIL 500 KCMIL
0.022 0.03
0.030 0.04
0.034 0.05
470 470
- -
695 695
- -
More Options
750 KCMIL 750 KCMIL
0.014 0.02
0.023 0.03
0.033 0.05
585 585
- -
900 900
- -
More Options
1000 KCMIL 1000 KCMIL
0.011 0.02
0.019 0.03
0.032 0.05
670 670
- -
1075 1075
- -

* NEC ampacities are based on:
* For Duct: Table 315.60(C)(11) Detail 1.
* For Free Air: Table 315.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Size
AWG
Stock Code
#2 #2
607457
500 500
601484 601484

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • CT USE Sizes 1/0 AWG and Larger
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (Tinned Copper per ASTM B33 optional)
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:No Lead Ethylene Propylene Rubber (NL-EPR)
  4. Overall Jacket:Polyvinyl Chloride (PVC)

Resources

There are no downloadable resources for this product.