500-1221 CU 15KV JUMPER CABLE RED

Southwire #: 56942899

Single Conductor Flexible Conductor with an EPR Insulation Non-Shielded Jumper Cable

Download Category Specifications
PDF Excel Table
Select Product Specifications
Construction
Outer Jacket / Armor Color
Packaging

Application

Southwire’s medium voltage non-shielded jumper and switchgear cable is a flexible power cable that is intended for use in substations installed on insulators and inside switchgear isolated from ground and where a non-shielded flexible cable is desired. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C. See Table 2 for installation guidelines. This cable is rated up to 40KV and is not UL listed.

Specifications

Stock # 56942899 56942899
Size (AWG or kcmil) (mm2) 500 KCMIL 500 KCMIL
No. of Strands 1221 1221
Nom. OD (mils) (mm) 1350 34.29 mils mm
Nominal Total Weight (lbs/1000') (kgs/km) 1970 2932 lbs/1000' kgs/km

Standards & References

  • ASTM B33: Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172: Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors

Construction

  • Conductor: Flexible rope lay stranded annealed bare or tinned copper
  • Conductor Shield: Nylon semi-conducting tape, helically applied
  • Insulation: Heat, moisture, and ozone resistant Ethylene Propylene Rubber(EPR)

Resources

There are no downloadable resources for this product.