AMW 1015 LW65

Download Category Specifications
PDF Excel Table

Application & Features

  • For use in internal wiring of electrical equipment in dry or damp locations
  • Applications include electric ranges, heating equipment and lighting fixtures

Specifications

Select more options below for part numbers, packaging, and color options:
Conductor
Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km)
More Options
24 AWG 24 AWG
7 7
30 0.76
87 2.21
5 7
More Options
22 AWG 22 AWG
7 7
30 0.76
91 2.31
6 9
More Options
20 AWG 20 AWG
7 7
30 0.76
99 2.51
7 11
More Options
18 AWG 18 AWG
1 1
30 0.76
103 2.62
9 13
More Options
18 AWG 18 AWG
7 7
30 0.76
106 2.69
10 15
More Options
18 AWG 18 AWG
16 16
30 0.76
106 2.69
10 15
More Options
16 AWG 16 AWG
26 26
30 0.76
117 2.97
13 20
More Options
14 AWG 14 AWG
1 1
30 0.76
130 3.30
18 27
More Options
12 AWG 12 AWG
7 7
30 0.76
151 3.84
27 40

Standards & References

  • CSA Spec. C22.2, No. 127
  • UL Spec. AWM Style 1015, 1019, 1020, 1230, 1284, 1032, 1283, 1232, 1028
  • CSA LL90458
  • UL E30398
  • Meets material content restrictions of the RoHS-2 Directive

Construction

  1. Available in all colors except clear and transparent
  2. Solid or stranded conductor of soft bare, or tinned, or prefused copper
  3. Thermoplastic insulation