SPEC: 43618

600V CU EPR PAIRS CPE POS Instrumentation

Type TC-ER Instrumentation Cable 600 Volt Tinned Copper Conductors EPR Insulated Single Pairs with Overall Shield POS. CPE Jacket Heat, Moisture, Oil and Sunlight Resistant. Rated for -30°C to 90°C

Download Category Specifications
PDF Excel Table

Application

Southwire’s Instrumentation Cables Type TC-ER per UL 1277 are suitable for installations as outlined in NEC Article 336 for process control and instrumentation, control circuits for operation and interconnection of protective and signaling devices and for general use in manufacturing, industrial and commercial distribution systems. Cables are constructed with 7-strand tinned copper conductors insulated with Ethylene Propylene Rubber EPR. The paired conductors are colored black, white, and alpha-numeric printed. The overall assembly is covered with an aluminum polyester foil with 100% coverage and a tinned drain wire. The cable is suited for use in cable trays, raceways, conduit, aerial (when supported with a messenger) and direct burial. The cable is rated for -30°C to 90°C wet or dry and rated for Class I Div II hazardous locations, sun and oil resistant. The jacket is black Chlorinated Polyethylene CPE with a rip cord for easy removal. 1 Pair is not TC-ER Rated.

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Min. Bend Radius (in) (cm) DC Resistance @ 25C (ohms/1000') (ohms/km)
More Options
18 18
1 1
0.045 0.11
30 0.76
45 1.14
0.309 0.78
46 68
1.8 4.57
6.669 9.92
More Options
18 18
5 5
0.045 0.11
30 0.76
60 1.52
0.714 1.81
178 265
4.2 10.67
6.669 9.92
More Options
18 18
12 12
0.045 0.11
30 0.76
80 2.03
0.941 2.39
377 561
5.6 14.22
6.669 9.92
More Options
16 16
1 1
0.056 0.14
30 0.76
45 1.14
0.333 0.85
57 85
1.9 4.83
4.181 6.22
More Options
16 16
4 4
0.056 0.14
30 0.76
60 1.52
0.589 1.50
177 263
3.5 8.89
4.181 6.22

† 1 Pair is not TC-ER Rated.

Size
AWG
Capacitance
pF/ft
Inductance
µH/ft
18 18
40.66 40.66
0.0957 0.0957
16 16
48.51 48.51
0.0895 0.0895

Standards & References

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • EPA 40 CFR, Part 26, Subpart C heavy metals per Table 1, TCLP method

Construction

  1. Conductor: Class B stranded tinned copper per ASTM B3 and B33
  2. Insulation: Twisted pair with Premium Grade Flame-retardant Ethylene Propylene Rubber FR-EPR Black/White alpha-numeric print alternate and inverted. 1-ONE, 2-TWO
  3. Overall Drain Wire: Tinned Copper sized two AWG sizes smaller than pair size. For #18 awg pair: Drain is 20 awg. For #16 awg pair: Drain is 18 awg.
  4. Overall Shielded: 100% coverage aluminum/polyester foil shield with a drain wire as shown in step 5
  5. Rip Cord: Rip cord under jacket for ease of removal
  6. Jacket: Black sunlight, oil and moisture resistant thermoplastic Chlorinated Polyethylene CPE jacket