Southwire's Romex® SIMpull ® NMD90 cables may be used for both exposed work in dry locations or concealed work in dry or damp locations. The maximum allowable conductor temperature is 90°C. The minimum recommended installation temperature is -25°C for two-conductor cables and -10°C for three-conductor cables (with suitable handling procedures). Material should be properly stored above 0°C for 24 hours prior to installation. The maximum voltage rating for all intended applications is 300 volts. Consult the Canadian Electrical Code1 for further information related to applications.
Conductor | Ground Wire | |||||||||||
Size (AWG or kcmil) | No. of Conductors | No. of Strands | Size (AWG) | No. of Strands | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Nom. OD (mils) (mm) | Nom. Height (mils) (mm) | Nom. Width (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity at 30°C Ambient | |
471748 | 14 AWG 14 AWG | 2 2 | 1 1 | 14 14 | 30 0.76 | 196 4.98 | 396 10.07 | 69 103 | 25* 25* | |||
471797 | 14 AWG 14 AWG | 3 3 | 1 1 | 14 14 | 30 0.76 | 388 9.87 | 91 135 | 25* 25* | ||||
471755 | 12 AWG 12 AWG | 2 2 | 1 1 | 14 14 | 30 0.76 | 212 5.41 | 429 10.91 | 88 131 | 30* 30* | |||
471805 | 12 AWG 12 AWG | 3 3 | 1 1 | 14 14 | 30 0.76 | 428 10.89 | 118 176 | 30* 30* | ||||
471763 | 10 AWG 10 AWG | 2 2 | 1 1 | 12 12 | 30 0.76 | 233 5.94 | 488 12.41 | 124 185 | 40* 40* | |||
471813 | 10 AWG 10 AWG | 3 3 | 1 1 | 12 12 | 30 0.76 | 479 12.19 | 168 250 | 40* 40* | ||||
551038 | 8 AWG 8 AWG | 2 2 | 7 7 | 10 10 | 45 1.14 | 316 8.03 | 694 17.63 | 211 314 | 55 55 | |||
471821 | 8 AWG 8 AWG | 3 3 | 7 7 | 10 10 | 45 1.14 | 635 16.14 | 284 422 | 55 55 | ||||
557881 | 6 AWG 6 AWG | 2 2 | 7 7 | 8 8 | 45 1.14 | 374 9.50 | 800 20.32 | 340 506 | 75 75 | |||
471839 | 6 AWG 6 AWG | 3 3 | 7 7 | 8 8 | 45 1.14 | 775 19.70 | 433 645 | 75 75 | ||||
557727 | 4 AWG 4 AWG | 2 2 | 7 7 | 8 8 | 60 1.52 | 839 21.32 | 463 689 | |||||
557882 | 3 AWG 3 AWG | 2 2 | 7 7 | 6 6 | 80 2.03 | 937 23.82 | 611 909 | |||||
676254 | 3 AWG 3 AWG | 3 3 | 7 7 | 6 6 | 80 2.03 | 1029 26.14 | 823 1225 | 115 115 | ||||
557880 | 2 AWG 2 AWG | 3 3 | 7 7 | 6 6 | 80 2.03 | 991 25.19 | 867 1290 |
* In accordance with the 2015 Canadian Electrical Code Part I Rule 14-104(2)
Romex® SIMpull ® NMD90 cables meet or exceed the following requirements: • ASTM • CSA C22.2 No. 48 (non-metallic sheathed cable) • Canadian Electrical Code
Southwire's Romex® SIMpull ® NMD90 cables are available as two- or three-conductor cables with a bare grounding conductor. It is manufactured using annealed (soft) copper conductors—compressed standing for stranded conductors; a heat-resistant thermoplastic polyvinyl chloride (PVC) insulation and nylon jacket for the individual conductors with a PVC jacket for the overall construction. Conductors are white" black and red (for 3 conductor cables). Cable jackets are colour coded by size for quick identification: