Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
574460 |
4
4
|
6 AWG
6 AWG
|
7
7
|
45
1.14
|
|
|
965
24.51
|
651
969
|
|
890229 |
4
4
|
1/0 AWG
1/0 AWG
|
19
19
|
55
1.40
|
|
|
1452
36.90
|
1908
2839
|
|
551452 |
4
4
|
350 KCMIL
350 KCMIL
|
37
37
|
65
1.65
|
|
|
2299
58.40
|
5710
8497
|
|
605410 |
4
4
|
500 KCMIL
500 KCMIL
|
37
37
|
65
1.65
|
|
|
2634
66.93
|
7854
11688
|
|
563407 |
4
4
|
600 KCMIL
600 KCMIL
|
61
61
|
80
2.03
|
|
|
2915
74.04
|
9303
13845
|
|