Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Cond. Size (AWG/Kcmil) | 2/0 2/0 | |
Cond. Strands | 19 19 | |
Diameter Over Conductor (in) (cm) | 0.405 1.03 | inch cm |
Diameter Over Insulation (in) (cm) | 0.624 1.58 | inch cm |
Insulation Thickness (mils) (mm) | 90 2.29 | mils mm |
Diameter Over Shield (in) (cm) | 0.684 1.74 | inch cm |
Ground (No. x AWG) | 1x6 1x6 | |
Inner Jacket Thickness (mils) (mm) | 110 2.79 | mils mm |
Diameter Over Armor (in) (cm) | 2.091 5.31 | inch cm |
Jacket Thickness (mils) (mm) | 60 1.52 | mils mm |
Approx. OD (in) (cm) | 2.211 5.62 | inch cm |
Approx. Weight (lbs/1000') (kgs/km) | 3050 4539 | lbs/1000' kgs/km |
Max Pull Tension (lbs) (kg) | 3194 1448.77 | lbs kg |
Min. Bend Radius (in) (cm) | 15.5 39.37 | inch cm |
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^ Yellow outer jacket