Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground Size | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.362
0.92
|
1.24
3.15
|
420
10.67
|
1.3
3.30
|
1x6
1x6
|
125
3.18
|
3.472
8.82
|
85
2.16
|
3.642
9.25
|
5339
7945
|
2534
1149.40
|
25.5
64.77
|
5
12.70
|
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
1.284
3.26
|
420
10.67
|
1.344
3.41
|
1x6
1x6
|
125
3.18
|
3.567
9.06
|
85
2.16
|
3.737
9.49
|
5810
8646
|
3194
1448.77
|
26.2
66.55
|
5
12.70
|
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
1.39
3.53
|
420
10.67
|
1.45
3.68
|
1x4
1x4
|
125
3.18
|
3.796
9.64
|
85
2.16
|
3.966
10.07
|
6961
10359
|
5078
2303.34
|
27.8
70.61
|
5
12.70
|
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity Directly Buried 90C | Allowable Ampacity In Air 90C | |
| More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.139
0.21
|
0.077
0.11
|
0.035
0.05
|
0.489+j0.314
0.489+j0.314
|
0.139+j0.052
0.139+j0.052
|
4059
4059
|
256
256
|
231
231
|
| More Options |
2/0 AWG
2/0 AWG
|
0.082
0.12
|
0.112
0.17
|
0.072
0.11
|
0.034
0.05
|
0.459+j0.302
0.459+j0.302
|
0.112+j0.050
0.112+j0.050
|
4195
4195
|
290
290
|
265
265
|
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.070
0.10
|
0.063
0.09
|
0.030
0.04
|
0.408+j0.275
0.408+j0.275
|
0.070+j0.046
0.070+j0.046
|
4524
4524
|
369
369
|
348
348
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E