Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Cond. Size (AWG/Kcmil) | 500 500 | |
Cond. Strands | 37 37 | |
Diameter Over Conductor (in) (cm) | 0.789 2.00 | inch cm |
Diameter Over Insulation (in) (cm) | 1.092 2.77 | inch cm |
Insulation Thickness (mils) (mm) | 140 3.56 | mils mm |
Diameter Over Shield (in) (cm) | 1.152 2.93 | inch cm |
Ground (No. x AWG) | 1x3 1x3 | |
Inner Jacket Thickness (mils) (mm) | 125 3.18 | mils mm |
Diameter Over Armor (in) (cm) | 3.129 7.95 | inch cm |
Jacket Thickness (mils) (mm) | 85 2.16 | mils mm |
Approx. OD (in) (cm) | 3.299 8.38 | inch cm |
Approx. Weight (lbs/1000') (kgs/km) | 8123 12088 | lbs/1000' kgs/km |
Max Pull Tension (lbs) (kg) | 12000 5443.10 | lbs kg |
Min. Bend Radius (in) (cm) | 23.1 58.67 | inch cm |
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^Black outer jacket