Southwire's 5kV / 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. For installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Cond. Size | 1 AWG 1 AWG | |
Cond. Strands | 19 19 | |
Diameter Over Conductor (in) (cm) | 0.322 0.82 | inch cm |
Diameter Over Insulation (in) (cm) | 0.590 1.50 | inch cm |
Insulation Thickness (mils) (mm) | 115 2.92 | mils mm |
Diameter Over Shield (in) (cm) | 0.650 1.65 | inch cm |
Inner Jacket Thickness (mils) (mm) | 80 2.03 | mils mm |
Diameter Over Armor (in) (cm) | 1.957 4.97 | inch cm |
Jacket Thickness (mils) (mm) | 60 1.52 | mils mm |
Approx. OD (in) (cm) | 2.077 5.28 | inch cm |
Approx. Weight (lbs/1000') (kgs/km) | 2356 3506 | lbs/1000' kgs/km |
Max Pull Tension (lbs) (kg) | 2008 910.81 | lbs kg |
Min. Bend Radius (in) (cm) | 14.5 36.83 | inch cm |
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^ Stock Code: 674110. Yellow Jacket