Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
0.990
2.51
|
220
5.59
|
1.050
2.67
|
80
2.03
|
1.424
3.62
|
60
1.52
|
1.534
3.90
|
1582
2354
|
1692
767.48
|
18.4
46.74
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
1.044
2.65
|
220
5.59
|
1.124
2.85
|
80
2.03
|
1.620
4.11
|
60
1.52
|
1.740
4.42
|
1880
2798
|
2000
907.18
|
20.9
53.09
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.252
3.18
|
220
5.59
|
1.312
3.33
|
80
2.03
|
1.836
4.66
|
60
1.52
|
1.956
4.97
|
2890
4301
|
4000
1814.37
|
23.5
59.69
|
| More Options |
1000 KCMIL
1000 KCMIL
|
61
61
|
1.117
2.84
|
1.613
4.10
|
220
5.59
|
1.673
4.25
|
110
2.79
|
2.237
5.68
|
75
1.91
|
2.369
6.02
|
4832
7191
|
8000
3628.74
|
28.4
72.14
|
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^^ Tinned Conductors
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity Directly Buried 90C | Allowable Ampacity In Air 90C | |
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.065
0.10
|
0.032
0.05
|
0.047
0.07
|
0.419 + j0.328
0.419 + j0.328
|
0.066 + j0.047
0.066 + j0.047
|
3284
3284
|
369
369
|
404
404
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.056
0.08
|
0.030
0.04
|
0.048
0.07
|
0.405 + j0.311
0.405 + j0.311
|
0.057 + j0.048
0.057 + j0.048
|
3451
3451
|
412
412
|
456
456
|
| More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.030
0.04
|
0.022
0.03
|
0.043
0.06
|
0.359 + j0.249
0.359 + j0.249
|
0.031 + j0.043
0.031 + j0.043
|
4167
4167
|
497
497
|
616
616
|
| More Options |
1000 KCMIL
1000 KCMIL
|
0.011
0.02
|
0.019
0.03
|
0.017
0.03
|
0.039
0.06
|
0.316 + j0.187
0.316 + j0.187
|
0.020 + j0.039
0.020 + j0.039
|
5214
5214
|
596
596
|
813
813
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M