Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
0.830
2.11
|
140
3.56
|
0.890
2.26
|
80
2.03
|
1.414
3.59
|
50
1.27
|
1.514
3.85
|
1470
2188
|
1692
767.48
|
18.2
46.23
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.115
2.83
|
140
3.56
|
1.175
2.98
|
80
2.03
|
1.699
4.32
|
60
1.52
|
1.819
4.62
|
2626
3908
|
4000
1814.37
|
21.8
55.37
|
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^ Black overall jacket
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity Directly Buried 90C | Allowable Ampacity In Air 90C | |
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.065
0.10
|
0.030
0.04
|
0.047
0.07
|
0.426 + j0.378
0.426 + j0.378
|
0.066 + j0.047
0.066 + j0.047
|
2788
2788
|
369
369
|
404
404
|
| More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.030
0.04
|
0.021
0.03
|
0.041
0.06
|
0.373 + j0.285
0.373 + j0.285
|
0.031 + j0.041
0.031 + j0.041
|
3671
3671
|
497
497
|
616
616
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A