Southwire's 600 Volt Type MC-HL ARMOR-X® control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -40°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.
| Cond. Size | Conductor Number | Cond. Strands | Insulation Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Min. Bend Radius (in) (cm) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
14 AWG
14 AWG
|
2
2
|
7
7
|
30
0.76
|
0.480
1.22
|
50
1.27
|
0.586
1.49
|
38
57
|
165
246
|
2.631
3.92
|
3.170
4.72
|
4.1
10.41
|
20
20
|
25
25
|
| More Options |
14 AWG
14 AWG
|
6
6
|
7
7
|
30
0.76
|
0.650
1.65
|
50
1.27
|
0.756
1.92
|
89
132
|
267
397
|
2.631
3.92
|
3.170
4.72
|
5.3
13.46
|
16
16
|
20
20
|
| More Options |
14 AWG
14 AWG
|
8
8
|
7
7
|
30
0.76
|
0.700
1.78
|
50
1.27
|
0.806
2.05
|
114
170
|
318
473
|
2.631
3.92
|
3.170
4.72
|
5.6
14.22
|
14
14
|
17
17
|
| More Options |
14 AWG
14 AWG
|
9
9
|
7
7
|
30
0.76
|
0.790
2.01
|
50
1.27
|
0.896
2.28
|
127
189
|
352
524
|
2.631
3.92
|
3.170
4.72
|
6.3
16.00
|
14
14
|
17
17
|
| More Options |
14 AWG
14 AWG
|
11
11
|
7
7
|
30
0.76
|
0.480
1.22
|
50
1.27
|
0.586
1.49
|
153
228
|
322
479
|
2.631
3.92
|
3.170
4.72
|
4.1
10.41
|
10
10
|
12
12
|
| More Options |
14 AWG
14 AWG
|
12
12
|
7
7
|
30
0.76
|
0.790
2.01
|
50
1.27
|
0.896
2.28
|
153
228
|
387
576
|
2.631
3.92
|
3.170
4.72
|
6.3
16.00
|
10
10
|
12
12
|
| More Options |
14 AWG
14 AWG
|
18
18
|
7
7
|
30
0.76
|
0.920
2.34
|
50
1.27
|
1.026
2.61
|
242
360
|
540
804
|
2.631
3.92
|
3.170
4.72
|
7.2
18.29
|
10
10
|
12
12
|
| More Options |
14 AWG
14 AWG
|
36
36
|
7
7
|
30
0.76
|
0.943
2.40
|
50
1.27
|
1.043
2.65
|
472
702
|
793
1180
|
2.631
3.92
|
3.170
4.72
|
4.1
10.41
|
8
8
|
10
10
|
| More Options |
12 AWG
12 AWG
|
2
2
|
7
7
|
30
0.76
|
0.530
1.35
|
50
1.27
|
0.636
1.62
|
61
91
|
193
287
|
1.662
2.47
|
2.002
2.98
|
4.5
11.43
|
25
25
|
30
30
|
| More Options |
12 AWG
12 AWG
|
3
3
|
7
7
|
30
0.76
|
0.610
1.55
|
50
1.27
|
0.716
1.82
|
81
121
|
236
351
|
1.662
2.47
|
2.002
2.98
|
5.0
12.70
|
25
25
|
30
30
|
| More Options |
12 AWG
12 AWG
|
5
5
|
7
7
|
30
0.76
|
0.700
1.78
|
50
1.27
|
0.806
2.05
|
121
180
|
313
466
|
1.662
2.47
|
2.002
2.98
|
5.6
14.22
|
20
20
|
24
24
|
| More Options |
12 AWG
12 AWG
|
6
6
|
7
7
|
30
0.76
|
0.700
1.78
|
50
1.27
|
0.806
2.05
|
141
210
|
336
500
|
1.662
2.47
|
2.002
2.98
|
5.6
14.22
|
20
20
|
24
24
|
| More Options |
12 AWG
12 AWG
|
8
8
|
7
7
|
30
0.76
|
0.790
2.01
|
50
1.27
|
0.896
2.28
|
182
271
|
409
609
|
1.662
2.47
|
2.002
2.98
|
6.3
16.00
|
17
17
|
21
21
|
| More Options |
12 AWG
12 AWG
|
11
11
|
7
7
|
30
0.76
|
0.920
2.34
|
50
1.27
|
1.026
2.61
|
243
362
|
516
768
|
1.662
2.47
|
2.002
2.98
|
7.2
18.29
|
12
12
|
15
15
|
| More Options |
12 AWG
12 AWG
|
12
12
|
7
7
|
30
0.76
|
0.920
2.34
|
50
1.27
|
1.026
2.61
|
263
391
|
543
808
|
1.662
2.47
|
2.002
2.98
|
7.2
18.29
|
12
12
|
15
15
|
| More Options |
12 AWG
12 AWG
|
18
18
|
7
7
|
30
0.76
|
1.020
2.59
|
50
1.27
|
1.126
2.86
|
385
573
|
722
1074
|
1.662
2.47
|
2.002
2.98
|
7.9
20.07
|
12
12
|
15
15
|
| More Options |
10 AWG
10 AWG
|
2
2
|
7
7
|
30
0.76
|
0.650
1.65
|
50
1.27
|
0.756
1.92
|
97
144
|
268
399
|
1.040
1.55
|
1.253
1.86
|
5.3
13.46
|
35
35
|
40
40
|
| More Options |
10 AWG
10 AWG
|
5
5
|
7
7
|
30
0.76
|
0.790
2.01
|
50
1.27
|
0.896
2.28
|
193
287
|
411
612
|
1.040
1.55
|
1.253
1.86
|
6.3
16.00
|
28
28
|
32
32
|
| More Options |
10 AWG
10 AWG
|
6
6
|
7
7
|
30
0.76
|
0.790
2.01
|
50
1.27
|
0.896
2.28
|
225
335
|
450
670
|
1.040
1.55
|
1.253
1.86
|
6.3
16.00
|
28
28
|
32
32
|
| More Options |
10 AWG
10 AWG
|
8
8
|
7
7
|
30
0.76
|
0.480
1.22
|
50
1.27
|
0.586
1.49
|
289
430
|
472
702
|
1.040
1.55
|
1.253
1.86
|
4.1
10.41
|
24
24
|
28
28
|
| More Options |
10 AWG
10 AWG
|
11
11
|
7
7
|
30
0.76
|
1.020
2.59
|
50
1.27
|
1.126
2.86
|
386
574
|
699
1040
|
1.040
1.55
|
1.253
1.86
|
7.9
20.07
|
17
17
|
20
20
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
! No CSA product Type RA90-HL
^ Tested as per IEC 60332-3-22 & 60092-350