For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. Meets Flame Spread and Smoke Release requirements of NFPA 130. Rated for 1000 lbs./FT maximum sidewall pressure.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Ground Size | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
12 AWG
12 AWG
|
7
7
|
0.088
0.22
|
45
1.14
|
1x14
1x14
|
50
1.27
|
0.675
1.71
|
45
1.14
|
0.765
1.94
|
259
385
|
104
47.17
|
5.3
13.46
|
| More Options |
12 AWG
12 AWG
|
7
7
|
0.088
0.22
|
45
1.14
|
1x14
1x14
|
65
1.65
|
0.698
1.77
|
45
1.14
|
0.788
2.00
|
293
436
|
156
70.76
|
5.5
13.97
|
| More Options |
10 AWG
10 AWG
|
7
7
|
0.113
0.29
|
45
1.14
|
1x12
1x12
|
65
1.65
|
0.723
1.84
|
45
1.14
|
0.813
2.07
|
312
464
|
166
75.30
|
5.6
14.22
|
† Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
† Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | |
| More Options |
12 AWG
12 AWG
|
1.662
2.47
|
2.002
2.98
|
0.054
0.08
|
| More Options |
12 AWG
12 AWG
|
1.662
2.47
|
2.002
2.98
|
0.054
0.08
|
| More Options |
10 AWG
10 AWG
|
1.040
1.55
|
1.253
1.86
|
0.050
0.07
|
† Ampacities have been adjusted for more than Three Current-Carrying Conductors
† Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.