Southwire’s 1000 Volt Type TC-ER PantoFLEX™ DC Power Cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Type (TC-ER) per NEC 336.10. Silicone free.
| Cond. Size | Cond. Strands | Strand Class | Conductor Number | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Ground Size | Jacket Thickness (mils) (mm) | Jacket Color | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | DC Resistance at 25C (ohms/1000') (ohms/km) | Max Pull Tension (lbs) (kg) | |
| More Options |
4/0 AWG
4/0 AWG
|
532
532
|
I
I
|
2
2
|
0.53
1.35
|
55
1.40
|
1x4
1x4
|
80
2.03
|
BK
BK
|
1.49
3.78
|
1833
2728
|
0.053
0.08
|
1693
767.93
|
| More Options |
250 KCMIL
250 KCMIL
|
627
627
|
I
I
|
2
2
|
0.605
1.54
|
65
1.65
|
1x3
1x3
|
80
2.03
|
BK
BK
|
1.666
4.23
|
2210
3289
|
0.045
0.07
|
2000
907.18
|
| More Options |
350 KCMIL
350 KCMIL
|
893
893
|
I
I
|
2
2
|
0.67
1.70
|
65
1.65
|
1x3
1x3
|
110
2.79
|
BK
BK
|
1.86
4.72
|
2971
4421
|
0.032
0.05
|
2800
1270.06
|
* Ampacity based on 2023 NEC Table 310(16): Ampacities of Insulated Conductors with Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried)
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.