Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
672150 |
1
1
|
2 AWG
2 AWG
|
7
7
|
175
4.45
|
|
|
911
23.14
|
570
848
|
|
552080 |
1
1
|
350 KCMIL
350 KCMIL
|
37
37
|
175
4.45
|
|
|
1277
32.44
|
1662
2473
|
|
552082 |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
175
4.45
|
|
|
1644
41.76
|
3129
4657
|
|
605279 |
1
1
|
1000 KCMIL
1000 KCMIL
|
61
61
|
175
4.45
|
|
|
1823
46.30
|
4063
6047
|
|