Southwire’s 2.4KV XLPE cables are suited for use in dry areas, conduits, ducts, troughs, trays and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. Rated for 1000 lbs./FT maximum sidewall pressure. Silicone Free.
| Cond. Size | 4 AWG 4 AWG | |
| Cond. Strands | 7 7 | |
| Diameter Over Conductor (in) (cm) | 0.225 0.57 | inch cm |
| Insulation Thickness (mils) (mm) | 110 2.79 | mils mm |
| Approx. OD (in) (cm) | 0.481 1.22 | inch cm |
| Approx. Weight (lbs/1000') (kgs/km) | 215 320 | lbs/1000' kgs/km |
| Max Pull Tension (lbs) (kg) | 334 151.50 | lbs kg |
| Min. Bend Radius (in) (cm) | 3.8 9.65 | inch cm |
| Conduit Size (in) (cm) | 1.5 3.81 | inch cm |