HDFPC-DLO is a 2kV flexible power cable with a variety of possible applications such as but not limited to: Drilling rigs, railroad and transit car wiring, mining and other industrial equipment, and as flexible motor leads and wind turbine applications. The cable is suited for use in wet and dry areas, conduits, ducts, troughs, trays, and where superior electrical properties are desired. HDFPC-DLO is oil, heat, flame, abrasion, and sunlight resistant. Approved for use per the NEC® as Type RHH/RHW-2 and per the CE Code as 2kV Type RW90. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. Sizes 1/0 and Larger Rated For CT Use.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
12 AWG
12 AWG
|
1
1
|
19
19
|
0.091
0.23
|
45
1.14
|
15
0.38
|
0.210
0.53
|
36
54
|
| More Options |
10 AWG
10 AWG
|
1
1
|
19
19
|
0.125
0.32
|
55
1.40
|
25
0.64
|
0.265
0.67
|
58
86
|
| More Options |
8 AWG
8 AWG
|
1
1
|
41
41
|
0.145
0.37
|
55
1.40
|
30
0.76
|
0.330
0.84
|
92
137
|
| More Options |
6 AWG
6 AWG
|
1
1
|
65
65
|
0.186
0.47
|
50
1.27
|
30
0.76
|
0.370
0.94
|
127
189
|
| More Options |
4 AWG
4 AWG
|
1
1
|
105
105
|
0.235
0.60
|
60
1.52
|
35
0.89
|
0.440
1.12
|
196
292
|
| More Options |
2 AWG
2 AWG
|
1
1
|
161
161
|
0.290
0.74
|
60
1.52
|
35
0.89
|
0.500
1.27
|
282
420
|
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
266
266
|
0.379
0.96
|
75
1.91
|
55
1.40
|
0.645
1.64
|
450
670
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
342
342
|
0.400
1.02
|
80
2.03
|
50
1.27
|
0.690
1.75
|
566
842
|
| More Options |
3/0 AWG
3/0 AWG
|
1
1
|
418
418
|
0.480
1.22
|
80
2.03
|
55
1.40
|
0.760
1.93
|
676
1006
|
| More Options |
4/0 AWG
4/0 AWG
|
1
1
|
532
532
|
0.530
1.35
|
80
2.03
|
60
1.52
|
0.815
2.07
|
815
1213
|
| More Options |
262.2 KCMIL
262.2 KCMIL
|
1
1
|
646
646
|
0.565
1.44
|
80
2.03
|
60
1.52
|
0.845
2.15
|
974
1449
|
| More Options |
313.3 KCMIL
313.3 KCMIL
|
1
1
|
779
779
|
0.650
1.65
|
90
2.29
|
70
1.78
|
0.980
2.49
|
1139
1695
|
| More Options |
373.7 KCMIL
373.7 KCMIL
|
1
1
|
931
931
|
0.701
1.78
|
95
2.41
|
70
1.78
|
1.040
2.64
|
1343
1999
|
| More Options |
444.4 KCMIL
444.4 KCMIL
|
1
1
|
1121
1121
|
0.782
1.99
|
90
2.29
|
65
1.65
|
1.105
2.81
|
1654
2461
|
| More Options |
535.3 KCMIL
535.3 KCMIL
|
1
1
|
1330
1330
|
0.843
2.14
|
105
2.67
|
75
1.91
|
1.212
3.08
|
1889
2811
|
| More Options |
646.4 KCMIL
646.4 KCMIL
|
1
1
|
1628
1628
|
0.890
2.26
|
115
2.92
|
80
2.03
|
1.290
3.28
|
2292
3411
|
| More Options |
777.7 KCMIL
777.7 KCMIL
|
1
1
|
1924
1924
|
0.966
2.45
|
120
3.05
|
90
2.29
|
1.405
3.57
|
2727
4058
|
| More Options |
1111 KCMIL
1111 KCMIL
|
1
1
|
2745
2745
|
1.168
2.97
|
115
2.92
|
95
2.41
|
1.640
4.17
|
4161
6192
|
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Allowable Ampacity In Air 75C | Allowable Ampacity In Air 90C | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
12 AWG
12 AWG
|
1.774
2.64
|
2.301
3.42
|
0.054
0.08
|
52
23.59
|
0.8
2.03
|
35
35
|
40
40
|
25
25
|
30
30
|
| More Options |
10 AWG
10 AWG
|
1.081
1.61
|
1.302
1.94
|
0.050
0.07
|
83
37.65
|
1.1
2.79
|
50
50
|
55
55
|
35
35
|
40
40
|
| More Options |
8 AWG
8 AWG
|
0.679
1.01
|
0.818
1.22
|
0.052
0.08
|
132
59.87
|
1.3
3.30
|
70
70
|
80
80
|
50
50
|
55
55
|
| More Options |
6 AWG
6 AWG
|
0.435
0.65
|
0.524
0.78
|
0.051
0.08
|
209
94.80
|
1.5
3.81
|
95
95
|
105
105
|
65
65
|
75
75
|
| More Options |
4 AWG
4 AWG
|
0.274
0.41
|
0.330
0.49
|
0.048
0.07
|
333
151.05
|
1.8
4.57
|
125
125
|
140
140
|
85
85
|
95
95
|
| More Options |
2 AWG
2 AWG
|
0.172
0.26
|
0.207
0.31
|
0.045
0.07
|
530
240.40
|
2.0
5.08
|
170
170
|
190
190
|
115
115
|
130
130
|
| More Options |
1/0 AWG
1/0 AWG
|
0.109
0.16
|
0.131
0.19
|
0.044
0.07
|
844
382.83
|
2.6
6.60
|
230
230
|
260
260
|
150
150
|
170
170
|
| More Options |
2/0 AWG
2/0 AWG
|
0.087
0.13
|
0.104
0.15
|
0.043
0.06
|
1064
482.62
|
2.8
7.11
|
265
265
|
300
300
|
175
175
|
195
195
|
| More Options |
3/0 AWG
3/0 AWG
|
0.069
0.10
|
0.083
0.12
|
0.042
0.06
|
1342
608.72
|
3.0
7.62
|
310
310
|
350
350
|
200
200
|
225
225
|
| More Options |
4/0 AWG
4/0 AWG
|
0.055
0.08
|
0.067
0.10
|
0.041
0.06
|
1692
767.48
|
3.3
8.38
|
360
360
|
405
405
|
230
230
|
260
260
|
| More Options |
262.2 KCMIL
262.2 KCMIL
|
0.026
0.04
|
0.033
0.05
|
0.031
0.05
|
2097
951.18
|
3.4
8.64
|
415
415
|
466
466
|
264
264
|
301
301
|
| More Options |
313.3 KCMIL
313.3 KCMIL
|
0.039
0.06
|
0.048
0.07
|
0.031
0.05
|
2506
1136.70
|
3.9
9.91
|
460
460
|
518
518
|
298
298
|
332
332
|
| More Options |
373.7 KCMIL
373.7 KCMIL
|
0.033
0.05
|
0.042
0.06
|
0.031
0.05
|
2989
1355.79
|
5.2
13.21
|
524
524
|
592
592
|
323
323
|
365
365
|
| More Options |
444.4 KCMIL
444.4 KCMIL
|
0.026
0.04
|
0.040
0.06
|
0.029
0.04
|
3555
1612.52
|
5.5
13.97
|
578
578
|
652
652
|
358
358
|
405
405
|
| More Options |
535.3 KCMIL
535.3 KCMIL
|
0.021
0.03
|
0.028
0.04
|
0.030
0.04
|
4282
1942.28
|
6.1
15.49
|
644
644
|
730
730
|
394
394
|
446
446
|
| More Options |
646.4 KCMIL
646.4 KCMIL
|
0.018
0.03
|
0.025
0.04
|
0.030
0.04
|
5171
2345.52
|
6.5
16.51
|
720
720
|
812
812
|
439
439
|
496
496
|
| More Options |
777.7 KCMIL
777.7 KCMIL
|
0.016
0.02
|
0.024
0.04
|
0.030
0.04
|
6221
2821.80
|
7.0
17.78
|
801
801
|
905
905
|
483
483
|
543
543
|
| More Options |
1111 KCMIL
1111 KCMIL
|
0.011
0.02
|
0.016
0.02
|
0.029
0.04
|
8888
4031.53
|
8.2
20.83
|
993
993
|
1119
1119
|
570
570
|
648
648
|
* Ampacities in raceway are based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities for non-standard sizes were extrapolated
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
* #12 and #10 AWG are not approved for CSA RW90
| Cond. Size | Black | Red | Brown | Orange | Yellow | Green | Gray |
|
12
12
|
665446
665446
|
665465
665465
|
665466
665466
|
665467
665467
|
665468
665468
|
|
|
|
10
10
|
665469
665469
|
665470
665470
|
665471
665471
|
665472
665472
|
665473
665473
|
|
|
|
8
8
|
TBA
TBA
|
665474
665474
|
665475
665475
|
665476
665476
|
665477
665477
|
|
|
|
6
6
|
665478
665478
|
665479
665479
|
665480
665480
|
665481
665481
|
665482
665482
|
|
|
|
4
4
|
665483
665483
|
665484
665484
|
665485
665485
|
653627
653627
|
|
||
|
2
2
|
138238
138238
|
138239
138239
|
138240
138240
|
138241
138241
|
|
||
|
1
1
|
167020
167020
|
138282
138282
|
138283
138283
|
138287
138287
|
138288
138288
|
138289
138289
|
|
|
1/0
1/0
|
138242
138242
|
138243
138243
|
138244
138244
|
138245
138245
|
138246
138246
|
|
|
|
2/0
2/0
|
138247
138247
|
138248
138248
|
138249
138249
|
138251
138251
|
|
||
|
3/0
3/0
|
138252
138252
|
138253
138253
|
138254
138254
|
138255
138255
|
138256
138256
|
|
|
|
4/0
4/0
|
138257
138257
|
138258
138258
|
138259
138259
|
138260
138260
|
|
||
|
262.6
262.6
|
641176
641176
|
665452
665452
|
665453
665453
|
665454
665454
|
665455
665455
|
|
|
|
313.3
313.3
|
665456
665456
|
665457
665457
|
665458
665458
|
665459
665459
|
665460
665460
|
|
|
|
373.7
373.7
|
655203
655203
|
678900
678900
|
576729
576729
|
678901
678901
|
678902
678902
|
|
|
|
444.4
444.4
|
678975
678975
|
665461
665461
|
665462
665462
|
665463
665463
|
665464
665464
|
|
|
|
535.3
535.3
|
138211
138211
|
138212
138212
|
138213
138213
|
677552
677552
|
|
||
|
646.4
646.4
|
138229
138229
|
138215
138215
|
138216
138216
|
138217
138217
|
138218
138218
|
|
|
|
777.7
777.7
|
640980
640980
|
640981
640981
|
640982
640982
|
138219
138219
|
640983
640983
|
||
|
1111
1111
|
138220
138220
|
138221
138221
|
138222
138222
|
138223
138223
|
138224
138224
|
|