SPEC: 44140

3/C CU 2000V EPDM/CPE Type G-GC Industrial Grade Cable 90°C. MSHA Approved SPEC44140

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

Download Category Specifications
PDF Excel Table

Application & Features

Southwire Type G-GC cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications where equipment grounding is required per NEC Article 400. Suitable for continuous submersion in water – ideal for submersible pumps, marine application. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as permanent building wiring. Meets FT-5 Flame Test. cUL Listed.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Ground Check Size Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
3 3
71 71
0.145 0.37
60 1.52
1x10 1x10
145 3.68
0.980 2.49
655 975
More Options
6 AWG 6 AWG
3 3
65 65
0.186 0.47
60 1.52
1x10 1x10
145 3.68
1.055 2.68
815 1213
More Options
4 AWG 4 AWG
3 3
112 112
0.235 0.60
60 1.52
1x8 1x8
130 3.30
1.172 2.98
1116 1661
More Options
2 AWG 2 AWG
3 3
168 168
0.290 0.74
60 1.52
1x8 1x8
165 4.19
1.289 3.27
1405 2091
More Options
1 AWG 1 AWG
3 3
224 224
0.300 0.76
80 2.03
1x8 1x8
145 3.68
1.455 3.70
1733 2579
More Options
1/0 AWG 1/0 AWG
3 3
259 259
0.379 0.96
80 2.03
1x8 1x8
185 4.70
1.660 4.22
2096 3119
More Options
2/0 AWG 2/0 AWG
3 3
324 324
0.400 1.02
80 2.03
1x8 1x8
215 5.46
1.704 4.33
2519 3749
More Options
3/0 AWG 3/0 AWG
3 3
418 418
0.480 1.22
80 2.03
1x8 1x8
205 5.21
1.830 4.65
3015 4487
More Options
4/0 AWG 4/0 AWG
3 3
532 532
0.530 1.35
80 2.03
1x8 1x8
175 4.45
1.970 5.00
3710 5521
More Options
250 KCMIL 250 KCMIL
3 3
608 608
0.605 1.54
95 2.41
1x8 1x8
260 6.60
2.284 5.80
4691 6981
More Options
350 KCMIL 350 KCMIL
3 3
855 855
0.670 1.70
95 2.41
1x8 1x8
330 8.38
2.681 6.81
6135 9130
More Options
500 KCMIL 500 KCMIL
3 3
1221 1221
0.858 2.18
95 2.41
1x8 1x8
290 7.37
2.891 7.34
8028 11947

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Allowable Ampacity In Air 60C Allowable Ampacity In Air 75C Allowable Ampacity In Air 90C
More Options
8 AWG 8 AWG
0.679 1.01
0.818 1.22
0.052 0.08
3.9 9.91
48 48
57 57
65 65
More Options
6 AWG 6 AWG
0.435 0.65
0.524 0.78
0.051 0.08
5.2 13.21
63 63
77 77
87 87
More Options
4 AWG 4 AWG
0.274 0.41
0.330 0.49
0.048 0.07
5.8 14.73
84 84
101 101
114 114
More Options
2 AWG 2 AWG
0.172 0.26
0.207 0.31
0.045 0.07
6.4 16.26
112 112
133 133
152 152
More Options
1 AWG 1 AWG
0.137 0.20
0.164 0.24
0.046 0.07
7.2 18.29
131 131
156 156
177 177
More Options
1/0 AWG 1/0 AWG
0.109 0.16
0.131 0.19
0.044 0.07
8.3 21.08
151 151
181 181
205 205
More Options
2/0 AWG 2/0 AWG
0.087 0.13
0.104 0.15
0.043 0.06
8.5 21.59
174 174
208 208
237 237
More Options
3/0 AWG 3/0 AWG
0.069 0.10
0.083 0.12
0.042 0.06
9.1 23.11
201 201
241 241
274 274
More Options
4/0 AWG 4/0 AWG
0.055 0.08
0.067 0.10
0.041 0.06
9.8 24.89
232 232
277 277
316 316
More Options
250 KCMIL 250 KCMIL
0.047 0.07
0.057 0.08
0.041 0.06
13.7 34.80
259 259
310 310
352 352
More Options
350 KCMIL 350 KCMIL
0.033 0.05
0.042 0.06
0.040 0.06
16.0 40.64
318 318
381 381
433 433
More Options
500 KCMIL 500 KCMIL
0.023 0.03
0.031 0.05
0.039 0.06
17.3 43.94
392 392
470 470
536 536

* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650 Standard for Portable Power Cable
  • CSA C22.2 No. 96 Portable Power Cables
  • RoHS-2 (European Directive 2011/65/EU)

Construction

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, red
  4. Ground Check:One insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
  5. Ground Conductors:Two insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
  6. Fillers:Paper fillers applied as needed to round the cable core
  7. Reinforcement Binder:Reinforcing binder with twine applied over the core
  8. Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)