CAMV™ C7® Tree Wire is self-supporting covered conductor with a carbon fiber composite core that is used in place of bare conductor in overhead primary distribution. Installed as an uninsulated conductor; however, covering is effective in preventing direct shorts and instantaneous flashovers should tree limbs or other objects contact conductors. Tree wire can have a significant effect in the prevention of wildfires caused by sparks from primary conductors slapping together or contacting tree limbs. Tree wire cables can be an effective solution to solve problems with existing bare conductor circuits without the need for alternatives such as aerial bundled or underground cables.
| Codeword | Size (AWG or kcmil) | Stranding | Insulation Thickness (inch) (cm) | Overall Diameter (inch) (cm) | Total Weight (lb/1000ft) (kg/km) | Rated Breaking Strength (lb) | Amp Rating @130°C (amp) |
|
15kV
15kV
|
2 AWG
2 AWG
|
6/1
6/1
|
0.165
0.42
|
0.646
1.64
|
178
265
|
3,890
3,890
|
257
257
|
|
15kV
15kV
|
2 AWG
2 AWG
|
7/1
7/1
|
0.165
0.42
|
0.652
1.66
|
182
271
|
5,140
5,140
|
258
258
|
|
15kV
15kV
|
1 AWG
1 AWG
|
6/1
6/1
|
0.165
0.42
|
0.687
1.74
|
208
310
|
5,070
5,070
|
296
296
|
|
15kV
15kV
|
1/0
1/0
|
6/1
6/1
|
0.165
0.42
|
0.728
1.85
|
240
357
|
6,160
6,160
|
341
341
|
|
15kV
15kV
|
2/0
2/0
|
6/1
6/1
|
0.165
0.42
|
0.777
1.97
|
282
420
|
7,750
7,750
|
393
393
|
|
15kV
15kV
|
3/0
3/0
|
6/1
6/1
|
0.165
0.42
|
0.832
2.11
|
333
496
|
9,720
9,720
|
454
454
|
|
15kV
15kV
|
4/0
4/0
|
6/1
6/1
|
0.165
0.42
|
0.893
2.27
|
396
589
|
12,200
12,200
|
524
524
|
|
15kV
15kV
|
266.8
266.8
|
18/1
18/1
|
0.165
0.42
|
0.938
2.38
|
440
655
|
8,230
8,230
|
598
598
|
|
15kV
15kV
|
266.8
266.8
|
24/7
24/7
|
0.165
0.42
|
0.96
2.44
|
455
677
|
12,800
12,800
|
602
602
|
|
15kV
15kV
|
266.8
266.8
|
26/7
26/7
|
0.165
0.42
|
0.975
2.48
|
465
692
|
15,400
15,400
|
605
605
|
|
15kV
15kV
|
266.8
266.8
|
30/7
30/7
|
0.165
0.42
|
0.995
2.53
|
480
714
|
20,000
20,000
|
609
609
|
|
15kV
15kV
|
336.4
336.4
|
18/1
18/1
|
0.165
0.42
|
1.013
2.57
|
527
784
|
10,300
10,300
|
691
691
|
|
15kV
15kV
|
336.4
336.4
|
24/7
24/7
|
0.165
0.42
|
1.044
2.65
|
549
817
|
16,600
16,600
|
697
697
|
|
15kV
15kV
|
336.4
336.4
|
26/7
26/7
|
0.165
0.42
|
1.053
2.67
|
556
827
|
19,200
19,200
|
699
699
|
|
15kV
15kV
|
336.4
336.4
|
30/7
30/7
|
0.165
0.42
|
1.061
2.69
|
566
842
|
23,400
23,400
|
701
701
|
|
15kV
15kV
|
397.5
397.5
|
18/1
18/1
|
0.165
0.42
|
1.073
2.73
|
603
897
|
12,200
12,200
|
767
767
|
|
15kV
15kV
|
397.5
397.5
|
24/7
24/7
|
0.165
0.42
|
1.113
2.83
|
632
941
|
20,200
20,200
|
776
776
|
|
15kV
15kV
|
397.5
397.5
|
26/7
26/7
|
0.165
0.42
|
1.112
2.82
|
633
942
|
22,300
22,300
|
776
776
|
|
15kV
15kV
|
397.5
397.5
|
30/7
30/7
|
0.165
0.42
|
1.145
2.91
|
661
984
|
30,300
30,300
|
784
784
|
|
15kV
15kV
|
477.0
477.0
|
18/1
18/1
|
0.165
0.42
|
1.145
2.91
|
701
1043
|
14,600
14,600
|
860
860
|
|
15kV
15kV
|
477.0
477.0
|
24/7
24/7
|
0.165
0.42
|
1.181
3.00
|
730
1086
|
23,600
23,600
|
869
869
|
|
15kV
15kV
|
477.0
477.0
|
26/7
26/7
|
0.165
0.42
|
1.179
2.99
|
730
1086
|
25,700
25,700
|
868
868
|
|
15kV
15kV
|
477.0
477.0
|
30/7
30/7
|
0.165
0.42
|
1.208
3.07
|
758
1128
|
34,400
34,400
|
875
875
|
|
15kV
15kV
|
556.5
556.5
|
18/1
18/1
|
0.170
0.43
|
1.219
3.10
|
805
1198
|
16,900
16,900
|
946
946
|
|
15kV
15kV
|
556.5
556.5
|
24/7
24/7
|
0.170
0.43
|
1.256
3.19
|
837
1246
|
27,100
27,100
|
955
955
|
|
15kV
15kV
|
556.5
556.5
|
26/7
26/7
|
0.170
0.43
|
1.26
3.20
|
842
1253
|
30,400
30,400
|
956
956
|
|
15kV
15kV
|
556.5
556.5
|
30/7
30/7
|
0.170
0.43
|
1.294
3.29
|
875
1302
|
40,800
40,800
|
965
965
|
|
15kV
15kV
|
636.0
636.0
|
18/1
18/1
|
0.170
0.43
|
1.28
3.25
|
900
1339
|
19,000
19,000
|
1029
1029
|
|
15kV
15kV
|
636.0
636.0
|
24/7
24/7
|
0.170
0.43
|
1.326
3.37
|
940
1399
|
31,500
31,500
|
1041
1041
|
|
15kV
15kV
|
636.0
636.0
|
26/7
26/7
|
0.170
0.43
|
1.34
3.40
|
954
1420
|
36,700
36,700
|
1045
1045
|
|
15kV
15kV
|
636.0
636.0
|
30/7
30/7
|
0.170
0.43
|
1.363
3.46
|
982
1461
|
43,600
43,600
|
1051
1051
|
|
15kV
15kV
|
795.0
795.0
|
24/7
24/7
|
0.180
0.46
|
1.442
3.66
|
1139
1695
|
36,700
36,700
|
1189
1189
|
|
15kV
15kV
|
795.0
795.0
|
26/7
26/7
|
0.180
0.46
|
1.469
3.73
|
1166
1735
|
44,600
44,600
|
1197
1197
|
|
15kV
15kV
|
795.0
795.0
|
30/7
30/7
|
0.180
0.46
|
1.503
3.82
|
1206
1795
|
54,100
54,100
|
1207
1207
|
|
15kV
15kV
|
795.0
795.0
|
45/7
45/7
|
0.180
0.46
|
1.425
3.62
|
1102
1640
|
26,700
26,700
|
1182
1182
|
|
25kV
25kV
|
2 AWG
2 AWG
|
6/1
6/1
|
0.265
0.67
|
0.846
2.15
|
275
409
|
3,890
3,890
|
252
252
|
|
25kV
25kV
|
2 AWG
2 AWG
|
7/1
7/1
|
0.265
0.67
|
0.852
2.16
|
279
415
|
5,140
5,140
|
253
253
|
|
25kV
25kV
|
1 AWG
1 AWG
|
6/1
6/1
|
0.265
0.67
|
0.887
2.25
|
309
460
|
5,070
5,070
|
290
290
|
|
25kV
25kV
|
1/0
1/0
|
6/1
6/1
|
0.265
0.67
|
0.928
2.36
|
347
516
|
6,160
6,160
|
333
333
|
|
25kV
25kV
|
2/0
2/0
|
6/1
6/1
|
0.265
0.67
|
0.977
2.48
|
395
588
|
7,750
7,750
|
384
384
|
|
25kV
25kV
|
3/0
3/0
|
6/1
6/1
|
0.265
0.67
|
1.032
2.62
|
453
674
|
9,720
9,720
|
442
442
|
|
25kV
25kV
|
4/0
4/0
|
6/1
6/1
|
0.265
0.67
|
1.093
2.78
|
524
780
|
12,200
12,200
|
510
510
|
|
25kV
25kV
|
266.8
266.8
|
18/1
18/1
|
0.265
0.67
|
1.138
2.89
|
573
853
|
8,230
8,230
|
581
581
|
|
25kV
25kV
|
266.8
266.8
|
24/7
24/7
|
0.265
0.67
|
1.16
2.95
|
591
880
|
12,800
12,800
|
585
585
|
|
25kV
25kV
|
266.8
266.8
|
26/7
26/7
|
0.265
0.67
|
1.175
2.98
|
603
897
|
15,400
15,400
|
588
588
|
|
25kV
25kV
|
266.8
266.8
|
30/7
30/7
|
0.265
0.67
|
1.195
3.04
|
621
924
|
20,000
20,000
|
592
592
|
|
25kV
25kV
|
336.4
336.4
|
18/1
18/1
|
0.265
0.67
|
1.213
3.08
|
671
999
|
10,300
10,300
|
671
671
|
|
25kV
25kV
|
336.4
336.4
|
24/7
24/7
|
0.265
0.67
|
1.244
3.16
|
696
1036
|
16,600
16,600
|
677
677
|
|
25kV
25kV
|
336.4
336.4
|
26/7
26/7
|
0.265
0.67
|
1.253
3.18
|
704
1048
|
19,200
19,200
|
679
679
|
|
25kV
25kV
|
336.4
336.4
|
30/7
30/7
|
0.265
0.67
|
1.261
3.20
|
715
1064
|
23,400
23,400
|
680
680
|
|
25kV
25kV
|
397.5
397.5
|
18/1
18/1
|
0.265
0.67
|
1.273
3.23
|
755
1124
|
12,200
12,200
|
745
745
|
|
25kV
25kV
|
397.5
397.5
|
24/7
24/7
|
0.265
0.67
|
1.313
3.34
|
788
1173
|
20,200
20,200
|
753
753
|
|
25kV
25kV
|
397.5
397.5
|
26/7
26/7
|
0.265
0.67
|
1.312
3.33
|
790
1176
|
22,300
22,300
|
753
753
|
|
25kV
25kV
|
397.5
397.5
|
30/7
30/7
|
0.265
0.67
|
1.345
3.42
|
821
1222
|
30,300
30,300
|
760
760
|
|
25kV
25kV
|
477.0
477.0
|
18/1
18/1
|
0.265
0.67
|
1.345
3.42
|
862
1283
|
14,600
14,600
|
835
835
|
|
25kV
25kV
|
477.0
477.0
|
24/7
24/7
|
0.265
0.67
|
1.381
3.51
|
895
1332
|
23,600
23,600
|
842
842
|
|
25kV
25kV
|
477.0
477.0
|
26/7
26/7
|
0.265
0.67
|
1.379
3.50
|
895
1332
|
25,700
25,700
|
842
842
|
|
25kV
25kV
|
477.0
477.0
|
30/7
30/7
|
0.265
0.67
|
1.408
3.58
|
926
1378
|
34,400
34,400
|
848
848
|
|
25kV
25kV
|
556.5
556.5
|
18/1
18/1
|
0.270
0.69
|
1.419
3.60
|
975
1451
|
16,900
16,900
|
917
917
|
|
25kV
25kV
|
556.5
556.5
|
24/7
24/7
|
0.270
0.69
|
1.456
3.70
|
1011
1505
|
27,100
27,100
|
926
926
|
|
25kV
25kV
|
556.5
556.5
|
26/7
26/7
|
0.270
0.69
|
1.46
3.71
|
1017
1513
|
30,400
30,400
|
927
927
|
|
25kV
25kV
|
556.5
556.5
|
30/7
30/7
|
0.270
0.69
|
1.494
3.79
|
1055
1570
|
40,800
40,800
|
935
935
|
|
25kV
25kV
|
636.0
636.0
|
18/1
18/1
|
0.270
0.69
|
1.48
3.76
|
1078
1604
|
19,000
19,000
|
997
997
|
|
25kV
25kV
|
636.0
636.0
|
24/7
24/7
|
0.270
0.69
|
1.526
3.88
|
1124
1673
|
31,500
31,500
|
1008
1008
|
|
25kV
25kV
|
636.0
636.0
|
26/7
26/7
|
0.270
0.69
|
1.54
3.91
|
1140
1697
|
36,700
36,700
|
1012
1012
|
|
25kV
25kV
|
636.0
636.0
|
30/7
30/7
|
0.270
0.69
|
1.563
3.97
|
1170
1741
|
43,600
43,600
|
1018
1018
|
|
25kV
25kV
|
795.0
795.0
|
24/7
24/7
|
0.270
0.69
|
1.622
4.12
|
1317
1960
|
36,700
36,700
|
1154
1154
|
|
25kV
25kV
|
795.0
795.0
|
26/7
26/7
|
0.270
0.69
|
1.649
4.19
|
1346
2003
|
44,600
44,600
|
1163
1163
|
|
25kV
25kV
|
795.0
795.0
|
30/7
30/7
|
0.270
0.69
|
1.683
4.27
|
1391
2070
|
54,100
54,100
|
1171
1171
|
|
25kV
25kV
|
795.0
795.0
|
45/7
45/7
|
0.270
0.69
|
1.605
4.08
|
1277
1900
|
26,700
26,700
|
1149
1149
|
|
35kV
35kV
|
1/0
1/0
|
6/1
6/1
|
0.315
0.80
|
1.028
2.61
|
409
609
|
6,160
6,160
|
330
330
|
|
35kV
35kV
|
2/0
2/0
|
6/1
6/1
|
0.315
0.80
|
1.077
2.74
|
460
685
|
7,750
7,750
|
380
380
|
|
35kV
35kV
|
3/0
3/0
|
6/1
6/1
|
0.315
0.80
|
1.132
2.88
|
522
777
|
9,720
9,720
|
437
437
|
|
35kV
35kV
|
4/0
4/0
|
6/1
6/1
|
0.315
0.80
|
1.193
3.03
|
596
887
|
12,200
12,200
|
504
504
|
|
35kV
35kV
|
266.8
266.8
|
18/1
18/1
|
0.315
0.80
|
1.238
3.14
|
649
966
|
8,230
8,230
|
574
574
|
|
35kV
35kV
|
266.8
266.8
|
24/7
24/7
|
0.315
0.80
|
1.26
3.20
|
668
994
|
12,800
12,800
|
578
578
|
|
35kV
35kV
|
266.8
266.8
|
26/7
26/7
|
0.315
0.80
|
1.275
3.24
|
681
1013
|
15,400
15,400
|
581
581
|
|
35kV
35kV
|
266.8
266.8
|
30/7
30/7
|
0.315
0.80
|
1.295
3.29
|
699
1040
|
20,000
20,000
|
584
584
|
|
35kV
35kV
|
336.4
336.4
|
18/1
18/1
|
0.315
0.80
|
1.313
3.34
|
751
1118
|
10,300
10,300
|
662
662
|
|
35kV
35kV
|
336.4
336.4
|
24/7
24/7
|
0.315
0.80
|
1.344
3.41
|
778
1158
|
16,600
16,600
|
668
668
|
|
35kV
35kV
|
336.4
336.4
|
26/7
26/7
|
0.315
0.80
|
1.353
3.44
|
787
1171
|
19,200
19,200
|
670
670
|
|
35kV
35kV
|
336.4
336.4
|
30/7
30/7
|
0.315
0.80
|
1.361
3.46
|
798
1188
|
23,400
23,400
|
671
671
|
|
35kV
35kV
|
397.5
397.5
|
18/1
18/1
|
0.315
0.80
|
1.373
3.49
|
838
1247
|
12,200
12,200
|
735
735
|
|
35kV
35kV
|
397.5
397.5
|
24/7
24/7
|
0.315
0.80
|
1.413
3.59
|
874
1301
|
20,200
20,200
|
743
743
|
|
35kV
35kV
|
397.5
397.5
|
26/7
26/7
|
0.315
0.80
|
1.412
3.59
|
876
1304
|
22,300
22,300
|
743
743
|
|
35kV
35kV
|
397.5
397.5
|
30/7
30/7
|
0.315
0.80
|
1.445
3.67
|
910
1354
|
30,300
30,300
|
750
750
|
|
35kV
35kV
|
477.0
477.0
|
18/1
18/1
|
0.315
0.80
|
1.445
3.67
|
950
1414
|
14,600
14,600
|
823
823
|
|
35kV
35kV
|
477.0
477.0
|
24/7
24/7
|
0.315
0.80
|
1.481
3.76
|
985
1466
|
23,600
23,600
|
831
831
|
|
35kV
35kV
|
477.0
477.0
|
26/7
26/7
|
0.315
0.80
|
1.479
3.76
|
985
1466
|
25,700
25,700
|
830
830
|
|
35kV
35kV
|
477.0
477.0
|
30/7
30/7
|
0.315
0.80
|
1.508
3.83
|
1018
1515
|
34,400
34,400
|
837
837
|
|
35kV
35kV
|
556.5
556.5
|
18/1
18/1
|
0.320
0.81
|
1.519
3.86
|
1067
1588
|
16,900
16,900
|
905
905
|
|
35kV
35kV
|
556.5
556.5
|
24/7
24/7
|
0.320
0.81
|
1.556
3.95
|
1106
1646
|
27,100
27,100
|
913
913
|
|
35kV
35kV
|
556.5
556.5
|
26/7
26/7
|
0.320
0.81
|
1.56
3.96
|
1112
1655
|
30,400
30,400
|
914
914
|
|
35kV
35kV
|
556.5
556.5
|
30/7
30/7
|
0.320
0.81
|
1.594
4.05
|
1152
1714
|
40,800
40,800
|
922
922
|
|
35kV
35kV
|
636.0
636.0
|
18/1
18/1
|
0.320
0.81
|
1.58
4.01
|
1174
1747
|
19,000
19,000
|
983
983
|
|
35kV
35kV
|
636.0
636.0
|
24/7
24/7
|
0.320
0.81
|
1.626
4.13
|
1223
1820
|
31,500
31,500
|
994
994
|
|
35kV
35kV
|
636.0
636.0
|
26/7
26/7
|
0.320
0.81
|
1.64
4.17
|
1240
1845
|
36,700
36,700
|
998
998
|
|
35kV
35kV
|
636.0
636.0
|
30/7
30/7
|
0.320
0.81
|
1.663
4.22
|
1272
1893
|
43,600
43,600
|
1003
1003
|
|
35kV
35kV
|
795.0
795.0
|
24/7
24/7
|
0.320
0.81
|
1.722
4.37
|
1422
2116
|
36,700
36,700
|
1137
1137
|
|
35kV
35kV
|
795.0
795.0
|
26/7
26/7
|
0.320
0.81
|
1.749
4.44
|
1454
2164
|
44,600
44,600
|
1145
1145
|
|
35kV
35kV
|
795.0
795.0
|
30/7
30/7
|
0.320
0.81
|
1.783
4.53
|
1500
2232
|
54,100
54,100
|
1154
1154
|
|
35kV
35kV
|
795.0
795.0
|
45/7
45/7
|
0.320
0.81
|
1.705
4.33
|
1382
2057
|
26,700
26,700
|
1132
1132
|
Southwire’s CAMV™ C7® Tree Wire meets or exceeds all applicable ICEA specifications and ASTM B941
3-Layer concentrically stranded Thermal-Resistant Aluminum Conductor, Composite Reinforced (ZTACCR/C7-TS®), cross-linked polyethylene (XLPE) conductor shield, cross-linked low density polyethylene (LDXLPE) inner layer and gray or black track-resistant high density cross-linked polyethylene (TRHDXLPE) outer layer.