Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
3/0 AWG
3/0 AWG
|
15
15
|
0.422
1.07
|
0.641
1.63
|
90
2.29
|
0.701
1.78
|
110
2.79
|
2.127
5.40
|
60
1.52
|
2.247
5.71
|
2323
3457
|
3020
1369.85
|
15.7
39.88
|
| More Options |
500 KCMIL
500 KCMIL
|
34
34
|
0.735
1.87
|
0.986
2.50
|
90
2.29
|
1.046
2.66
|
110
2.79
|
2.873
7.30
|
75
1.91
|
2.977
7.56
|
4457
6633
|
9000
4082.33
|
20.8
52.83
|
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity Directly Buried 90C | Allowable Ampacity In Air 90C | |
| More Options |
3/0 AWG
3/0 AWG
|
0.105
0.16
|
0.133
0.20
|
0.019
0.03
|
0.034
0.05
|
0.508 + j0.461
0.508 + j0.461
|
0.133 + j0.032
0.133 + j0.032
|
2199
2199
|
260
260
|
234
234
|
| More Options |
500 KCMIL
500 KCMIL
|
0.036
0.05
|
0.052
0.08
|
0.018
0.03
|
0.014
0.02
|
0.414 + j0.372
0.414 + j0.372
|
0.046 + j0.030
0.046 + j0.030
|
3197
3197
|
465
465
|
385
385
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E