Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
1/0 AWG
1/0 AWG
|
10
10
|
0.336
0.85
|
0.814
2.07
|
220
5.59
|
0.874
2.22
|
110
2.79
|
2.501
6.35
|
75
1.91
|
2.651
6.73
|
2807
4177
|
1900
861.82
|
18.6
47.24
|
| More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.615
1.56
|
1.102
2.80
|
220
5.59
|
1.162
2.95
|
125
3.18
|
3.173
8.06
|
85
2.16
|
3.343
8.49
|
4529
6740
|
6300
2857.63
|
23.4
59.44
|
| More Options |
500 KCMIL
500 KCMIL
|
34
34
|
0.735
1.87
|
1.244
3.16
|
220
5.59
|
1.304
3.31
|
135
3.43
|
3.480
8.84
|
85
2.16
|
3.650
9.27
|
5373
7996
|
9000
4082.33
|
25.6
65.02
|
| More Options |
750 KCMIL
750 KCMIL
|
53
53
|
0.908
2.31
|
1.416
3.60
|
220
5.59
|
1.476
3.75
|
125
3.18
|
3.860
9.80
|
85
2.16
|
4.030
10.24
|
6826
10158
|
13500
6123.49
|
28.2
71.63
|
* Strand count meets minimum number per ASTM
^Yellow jacket
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity Directly Buried 90C | Allowable Ampacity In Air 90C | |
| More Options |
1/0 AWG
1/0 AWG
|
0.168
0.25
|
0.211
0.31
|
0.056
0.08
|
0.044
0.07
|
0.584 + j0.394
0.584 + j0.394
|
0.211 + j0.043
0.211 + j0.043
|
2738
2738
|
202
202
|
176
176
|
| More Options |
350 KCMIL
350 KCMIL
|
0.050
0.07
|
0.065
0.10
|
0.037
0.06
|
0.037
0.06
|
0.417 + j0.291
0.417 + j0.291
|
0.065 + j0.035
0.065 + j0.035
|
3628
3628
|
386
386
|
363
363
|
| More Options |
500 KCMIL
500 KCMIL
|
0.035
0.05
|
0.046
0.07
|
0.032
0.05
|
0.035
0.05
|
0.387 + j0.297
0.387 + j0.297
|
0.047 + j0.036
0.047 + j0.036
|
4071
4071
|
465
465
|
447
447
|
| More Options |
750 KCMIL
750 KCMIL
|
0.020
0.03
|
0.030
0.04
|
0.030
0.04
|
0.030
0.04
|
0.355 + j0.220
0.355 + j0.220
|
0.034 + j0.031
0.034 + j0.031
|
4566
4566
|
563
563
|
566
566
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E