SPEC: 45042

Southwire® Machine Flex® CU 600/1000V PVC-Nylon Insulation Shielded TPE Gray Jacket. THHN SPEC45042

Type TC-ER Shielded Machine Tray Control Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s shielded Machine Flex® tray control cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. Southwire’s shielded flexible machine tray cable is ideal for use in for use in CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and bever- age, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
18 AWG 18 AWG
2 2
16 16
0.044 0.11
15 0.38
45 1.14
0.293 0.74
24 36
52 77
7.148 10.64
8.613 12.82
3.5 8.89
- -
14 14
More Options
18 AWG 18 AWG
3 3
16 16
0.044 0.11
15 0.38
45 1.14
0.320 0.81
30 45
63 94
7.148 10.64
8.613 12.82
3.8 9.65
- -
14 14
More Options
18 AWG 18 AWG
4 4
16 16
0.044 0.11
15 0.38
45 1.14
0.326 0.83
36 54
70 104
7.148 10.64
8.613 12.82
3.9 9.91
- -
11 11
More Options
18 AWG 18 AWG
5 5
16 16
0.044 0.11
15 0.38
45 1.14
0.353 0.90
43 64
82 122
7.148 10.64
8.613 12.82
4.2 10.67
- -
11 11
More Options
18 AWG 18 AWG
7 7
16 16
0.044 0.11
15 0.38
45 1.14
0.378 0.96
55 82
100 149
7.148 10.64
8.613 12.82
4.5 11.43
- -
9 9
More Options
18 AWG 18 AWG
9 9
16 16
0.044 0.11
15 0.38
45 1.14
0.442 1.12
68 101
129 192
7.148 10.64
8.613 12.82
5.3 13.46
- -
9 9
More Options
18 AWG 18 AWG
12 12
16 16
0.044 0.11
15 0.38
45 1.14
0.478 1.21
86 128
155 231
7.148 10.64
8.613 12.82
5.7 14.48
- -
7 7
More Options
18 AWG 18 AWG
18 18
16 16
0.044 0.11
15 0.38
60 1.52
0.576 1.46
119 177
222 330
7.148 10.64
8.613 12.82
6.9 17.53
- -
7 7
More Options
18 AWG 18 AWG
25 25
16 16
0.044 0.11
15 0.38
60 1.52
0.658 1.67
161 240
289 430
7.148 10.64
8.613 12.82
7.8 19.81
- -
6 6
More Options
16 AWG 16 AWG
2 2
26 26
0.059 0.15
15 0.38
45 1.14
0.321 0.82
34 51
66 98
4.487 6.68
5.406 8.05
3.8 9.65
- -
18 18
More Options
16 AWG 16 AWG
3 3
26 26
0.059 0.15
15 0.38
45 1.14
0.331 0.84
43 64
78 116
4.487 6.68
5.406 8.05
3.9 9.91
- -
18 18
More Options
16 AWG 16 AWG
4 4
26 26
0.059 0.15
15 0.38
45 1.14
0.360 0.91
53 79
93 138
4.487 6.68
5.406 8.05
4.3 10.92
- -
14 14
More Options
16 AWG 16 AWG
5 5
26 26
0.059 0.15
15 0.38
45 1.14
0.391 0.99
63 94
110 164
4.487 6.68
5.406 8.05
4.6 11.68
- -
14 14
More Options
16 AWG 16 AWG
7 7
26 26
0.059 0.15
15 0.38
45 1.14
0.427 1.08
80 119
135 201
4.487 6.68
5.406 8.05
5.1 12.95
- -
12 12
More Options
16 AWG 16 AWG
9 9
26 26
0.059 0.15
15 0.38
45 1.14
0.491 1.25
100 149
171 254
4.487 6.68
5.406 8.05
5.8 14.73
- -
12 12
More Options
16 AWG 16 AWG
12 12
26 26
0.059 0.15
15 0.38
60 1.52
0.562 1.43
128 190
220 327
4.487 6.68
5.406 8.05
6.7 17.02
- -
9 9
More Options
16 AWG 16 AWG
18 18
26 26
0.059 0.15
15 0.38
60 1.52
0.646 1.64
185 275
303 451
4.487 6.68
5.406 8.05
7.7 19.56
- -
9 9
More Options
16 AWG 16 AWG
25 25
26 26
0.059 0.15
15 0.38
60 1.52
0.746 1.89
248 369
398 592
4.487 6.68
5.406 8.05
8.9 22.61
- -
8 8
More Options
14 AWG 14 AWG
2 2
41 41
0.073 0.19
15 0.38
45 1.14
0.349 0.89
48 71
84 125
2.814 4.19
3.391 5.05
4.1 10.41
20 20
25 25
More Options
14 AWG 14 AWG
3 3
41 41
0.073 0.19
15 0.38
45 1.14
0.363 0.92
62 92
102 152
2.814 4.19
3.391 5.05
4.3 10.92
20 20
25 25
More Options
14 AWG 14 AWG
4 4
41 41
0.073 0.19
15 0.38
45 1.14
0.402 1.02
76 113
125 186
2.814 4.19
3.391 5.05
4.8 12.19
16 16
20 20
More Options
14 AWG 14 AWG
5 5
41 41
0.073 0.19
15 0.38
45 1.14
0.431 1.09
91 135
144 214
2.814 4.19
3.391 5.05
5.1 12.95
16 16
20 20
More Options
14 AWG 14 AWG
7 7
41 41
0.073 0.19
15 0.38
45 1.14
0.466 1.18
119 177
178 265
2.814 4.19
3.391 5.05
5.5 13.97
14 14
17 17
More Options
14 AWG 14 AWG
12 12
41 41
0.073 0.19
15 0.38
60 1.52
0.623 1.58
192 286
297 442
2.814 4.19
3.391 5.05
7.4 18.80
10 10
12 12
More Options
14 AWG 14 AWG
18 18
41 41
0.073 0.19
15 0.38
60 1.52
0.720 1.83
277 412
412 613
2.814 4.19
3.391 5.05
8.6 21.84
10 10
12 12
More Options
14 AWG 14 AWG
25 25
41 41
0.073 0.19
15 0.38
80 2.03
0.875 2.22
384 571
582 866
2.814 4.19
3.391 5.05
10.5 26.67
9 9
11 11
More Options
12 AWG 12 AWG
2 2
65 65
0.094 0.24
15 0.38
45 1.14
0.387 0.98
70 104
112 167
1.774 2.64
2.137 3.18
4.6 11.68
25 25
30 30
More Options
12 AWG 12 AWG
3 3
65 65
0.094 0.24
15 0.38
45 1.14
0.416 1.06
91 135
142 211
1.774 2.64
2.137 3.18
4.9 12.45
25 25
30 30
More Options
12 AWG 12 AWG
4 4
65 65
0.094 0.24
15 0.38
45 1.14
0.450 1.14
114 170
172 256
1.774 2.64
2.137 3.18
5.4 13.72
20 20
24 24
More Options
12 AWG 12 AWG
5 5
65 65
0.094 0.24
15 0.38
45 1.14
0.489 1.24
138 205
207 308
1.774 2.64
2.137 3.18
5.8 14.73
20 20
24 24
More Options
12 AWG 12 AWG
7 7
65 65
0.094 0.24
15 0.38
60 1.52
0.555 1.41
181 269
268 399
1.774 2.64
2.137 3.18
6.6 16.76
17 17
21 21
More Options
10 AWG 10 AWG
2 2
105 105
0.117 0.30
20 0.51
60 1.52
0.455 1.16
102 152
159 237
1.111 1.65
1.339 1.99
5.4 13.72
35 35
40 40
More Options
10 AWG 10 AWG
3 3
105 105
0.117 0.30
20 0.51
60 1.52
0.544 1.38
136 202
218 324
1.111 1.65
1.339 1.99
6.5 16.51
35 35
40 40
More Options
10 AWG 10 AWG
4 4
105 105
0.117 0.30
20 0.51
60 1.52
0.574 1.46
177 263
268 399
1.111 1.65
1.339 1.99
6.8 17.27
28 28
32 32
More Options
10 AWG 10 AWG
5 5
105 105
0.117 0.30
20 0.51
60 1.52
0.608 1.54
212 315
316 470
1.111 1.65
1.339 1.99
7.2 18.29
28 28
32 32
More Options
10 AWG 10 AWG
7 7
105 105
0.117 0.30
20 0.51
60 1.52
0.658 1.67
280 417
394 586
1.111 1.65
1.339 1.99
7.8 19.81
24 24
28 28
More Options
8 AWG 8 AWG
4 4
168 168
0.153 0.39
30 0.76
60 1.52
0.742 1.88
292 435
438 652
0.715 1.06
0.861 1.28
8.9 22.61
40 40
44 44
More Options
6 AWG 6 AWG
4 4
259 259
0.198 0.50
30 0.76
60 1.52
0.885 2.25
463 689
668 994
0.450 0.67
0.541 0.81
10.6 26.92
52 52
60 60
More Options
4 AWG 4 AWG
4 4
420 420
0.235 0.60
40 1.02
80 2.03
1.057 2.68
674 1003
997 1484
0.282 0.42
0.340 0.51
12.6 32.00
68 68
76 76
More Options
2 AWG 2 AWG
4 4
651 651
0.302 0.77
40 1.02
80 2.03
1.237 3.14
1060 1577
1433 2133
0.179 0.27
0.216 0.32
14.8 37.59
92 92
104 104

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • CAN/ULC-S139 UL Electrical Circuit Integrity System #44 (FHIT/7 44)
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 13 Power-Limited Circuit Cables
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material Style 2463 (80C, 600V)
  • UL 758 AWM Style 2587
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2250 Instrumentation Tray Cable
  • UL 2277 Type WTTC
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables

Construction

  1. Conductor: Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation: Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground: One Green Ground with Yellow Stripe THHN
  4. Drain Wire: Tinned copper sized one awg size smaller than phase conductor. Drain wire size is two gauge smaller than phase size
  5. Shielding: 100% coverage Alum/Mylar/Alum Foil, overall 85% coverage tinned copper braid
  6. Jacket: Gray Thermoplastic Elastomer TPE: Other jacket colors available upon request

Resources

There are no downloadable resources for this product.