Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. CT Rated 1/0 and Larger - Sunlight Resistant - Oil Resistant - Silicone Free.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
8 AWG
8 AWG
|
1
1
|
7
7
|
0.141
0.36
|
45
1.14
|
15
0.38
|
0.278
0.71
|
50
74
|
77
115
|
| More Options |
6 AWG
6 AWG
|
1
1
|
7
7
|
0.177
0.45
|
45
1.14
|
30
0.76
|
0.342
0.87
|
81
121
|
121
180
|
| More Options |
4 AWG
4 AWG
|
1
1
|
7
7
|
0.225
0.57
|
45
1.14
|
30
0.76
|
0.390
0.99
|
128
190
|
176
262
|
| More Options |
2 AWG
2 AWG
|
1
1
|
7
7
|
0.282
0.72
|
45
1.14
|
30
0.76
|
0.455
1.16
|
204
304
|
262
390
|
| More Options |
1 AWG
1 AWG
|
1
1
|
19
19
|
0.322
0.82
|
55
1.40
|
45
1.14
|
0.536
1.36
|
258
384
|
346
515
|
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
19
19
|
0.361
0.92
|
55
1.40
|
45
1.14
|
0.576
1.46
|
326
485
|
421
627
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
19
19
|
0.405
1.03
|
55
1.40
|
45
1.14
|
0.622
1.58
|
410
610
|
516
768
|
| More Options |
3/0 AWG
3/0 AWG
|
1
1
|
19
19
|
0.456
1.16
|
55
1.40
|
45
1.14
|
0.663
1.68
|
518
771
|
631
939
|
| More Options |
4/0 AWG
4/0 AWG
|
1
1
|
19
19
|
0.512
1.30
|
55
1.40
|
45
1.14
|
0.728
1.85
|
653
972
|
780
1161
|
| More Options |
250 KCMIL
250 KCMIL
|
1
1
|
37
37
|
0.558
1.42
|
65
1.65
|
65
1.65
|
0.836
2.12
|
771
1147
|
955
1421
|
| More Options |
350 KCMIL
350 KCMIL
|
1
1
|
37
37
|
0.661
1.68
|
65
1.65
|
65
1.65
|
0.939
2.39
|
1080
1607
|
1291
1921
|
| More Options |
500 KCMIL
500 KCMIL
|
1
1
|
37
37
|
0.789
2.00
|
65
1.65
|
65
1.65
|
1.062
2.70
|
1543
2296
|
1786
2658
|
| More Options |
600 KCMIL
600 KCMIL
|
1
1
|
61
61
|
0.865
2.20
|
80
2.03
|
65
1.65
|
1.203
3.06
|
1852
2756
|
2159
3213
|
| More Options |
750 KCMIL
750 KCMIL
|
1
1
|
61
61
|
0.968
2.46
|
80
2.03
|
65
1.65
|
1.278
3.25
|
2315
3445
|
2644
3935
|
| More Options |
1000 KCMIL
1000 KCMIL
|
1
1
|
91
91
|
1.117
2.84
|
80
2.03
|
65
1.65
|
1.443
3.67
|
3087
4594
|
3464
5155
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
8 AWG
8 AWG
|
1
1
|
1.1
2.79
|
132
59.87
|
0.653
0.97
|
0.786
1.17
|
0.052
0.08
|
50
50
|
55
55
|
| More Options |
6 AWG
6 AWG
|
1
1
|
1.3
3.30
|
209
94.80
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
65
65
|
75
75
|
| More Options |
4 AWG
4 AWG
|
1
1
|
1.5
3.81
|
333
151.05
|
0.258
0.38
|
0.310
0.46
|
0.048
0.07
|
85
85
|
95
95
|
| More Options |
2 AWG
2 AWG
|
1
1
|
1.8
4.57
|
530
240.40
|
0.162
0.24
|
0.195
0.29
|
0.045
0.07
|
115
115
|
130
130
|
| More Options |
1 AWG
1 AWG
|
1
1
|
2.1
5.33
|
669
303.45
|
0.128
0.19
|
0.154
0.23
|
0.046
0.07
|
130
130
|
145
145
|
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
2.3
5.84
|
844
382.83
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
150
150
|
170
170
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
2.4
6.10
|
1064
482.62
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
175
175
|
195
195
|
| More Options |
3/0 AWG
3/0 AWG
|
1
1
|
2.6
6.60
|
1342
608.72
|
0.064
0.10
|
0.078
0.12
|
0.042
0.06
|
200
200
|
225
225
|
| More Options |
4/0 AWG
4/0 AWG
|
1
1
|
2.9
7.37
|
1692
767.48
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
230
230
|
260
260
|
| More Options |
250 KCMIL
250 KCMIL
|
1
1
|
3.3
8.38
|
2000
907.18
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
255
255
|
290
290
|
| More Options |
350 KCMIL
350 KCMIL
|
1
1
|
3.7
9.40
|
2800
1270.06
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
310
310
|
350
350
|
| More Options |
500 KCMIL
500 KCMIL
|
1
1
|
5.3
13.46
|
4000
1814.37
|
0.022
0.03
|
0.029
0.04
|
0.039
0.06
|
380
380
|
430
430
|
| More Options |
600 KCMIL
600 KCMIL
|
1
1
|
6.0
15.24
|
4800
2177.24
|
0.018
0.03
|
0.025
0.04
|
0.039
0.06
|
420
420
|
475
475
|
| More Options |
750 KCMIL
750 KCMIL
|
1
1
|
6.3
16.00
|
6000
2721.55
|
0.014
0.02
|
0.022
0.03
|
0.038
0.06
|
475
475
|
535
535
|
| More Options |
1000 KCMIL
1000 KCMIL
|
1
1
|
7.2
18.29
|
8000
3628.74
|
0.011
0.02
|
0.018
0.03
|
0.037
0.06
|
545
545
|
615
615
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.