SPEC: 83018

Quadruplex 600 Volt USE-2 Underground Service Entrance SPEC83018

Download Category Specifications
PDF Excel Table

Application & Features

Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum, insulated with cross-linked polyethylene. Neutrals are identified by three yellow extruded stripes. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Three-phase conductors and one neutral conductor are cabled together to produce the quadruplex cable configuration. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL listed as USE-2 per UL 854 Service-Entrance Cables

Specifications

Select more options below for part numbers, packaging, and color options:
Code Word Cond. Size Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Num x Neutral Size Neutral Stranding (mils) (mm) Neutral Insulation Thickness Ground Size Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km)
More Options
TULSA TULSA
4 AWG 4 AWG
7 7
0.225 0.57
60 1.52
0.345 0.88
4 4
6 0.15
60 60
AWG AWG
0.832 2.11
251 374
More Options
DYKE DYKE
2 AWG 2 AWG
7 7
0.283 0.72
60 1.52
0.403 1.02
4 4
6 0.15
60 60
AWG AWG
0.973 2.47
337 502
More Options
NOTRE DAME NOTRE DAME
1/0 AWG 1/0 AWG
9 9
0.362 0.92
80 2.03
0.522 1.33
2 2
6 0.15
60 60
AWG AWG
1.236 3.14
535 796
More Options
SYRACUSE SYRACUSE
2/0 AWG 2/0 AWG
11 11
0.405 1.03
80 2.03
0.565 1.44
1 1
7 0.18
80 80
AWG AWG
1.34 3.40
659 981
More Options
SWARTHMORE SWARTHMORE
3/0 AWG 3/0 AWG
17 17
0.456 1.16
80 2.03
0.616 1.56
1/0 1/0
7 0.18
80 80
AWG AWG
1.456 3.70
795 1183
More Options
WAKE FOREST WAKE FOREST
4/0 AWG 4/0 AWG
18 18
0.512 1.30
80 2.03
0.672 1.71
2/0 2/0
11 0.28
80 80
AWG AWG
1.588 4.03
971 1445
More Options
RUST RUST
250 KCMIL 250 KCMIL
22 22
0.558 1.42
95 2.41
0.748 1.90
3/0 3/0
15 0.38
80 80
KCMIL KCMIL
1.753 4.45
1170 1741
More Options
SLIPPERY ROCK SLIPPERY ROCK
350 KCMIL 350 KCMIL
30 30
0.661 1.68
95 2.41
0.851 2.16
4/0 4/0
17 0.43
80 80
KCMIL KCMIL
2.006 5.10
1543 2296
More Options
WOFFORD WOFFORD
500 KCMIL 500 KCMIL
37 37
0.789 2.00
95 2.41
0.979 2.49
350 350
24 0.61
95 95
KCMIL KCMIL
2.293 5.82
2174 3235
More Options
WESTMINSTER WESTMINSTER
750 KCMIL 750 KCMIL
55 55
0.968 2.46
110 2.79
1.188 3.02
350 350
24 0.61
95 95
KCMIL KCMIL
2.798 7.11
3014 4485

Notes:
1. The actual number of strands may differ for single input wire per ASTM B901
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Code Word Cond. Size Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity In Duct 90C
More Options
TULSA TULSA
4 AWG 4 AWG
3.3 8.38
1001 454.05
0.424 0.63
0.528 0.79
0.048 0.07
65/75 65/75
More Options
DYKE DYKE
2 AWG 2 AWG
3.9 9.91
1592 722.12
0.266 0.40
0.331 0.49
0.045 0.07
90/100 90/100
More Options
NOTRE DAME NOTRE DAME
1/0 AWG 1/0 AWG
6.2 15.75
2534 1149.40
0.167 0.25
0.208 0.31
0.044 0.07
120/135 120/135
More Options
SYRACUSE SYRACUSE
2/0 AWG 2/0 AWG
6.7 17.02
3194 1448.77
0.133 0.20
0.166 0.25
0.043 0.06
135/150 135/150
More Options
SWARTHMORE SWARTHMORE
3/0 AWG 3/0 AWG
7.3 18.54
4027 1826.61
0.105 0.16
0.131 0.19
0.042 0.06
155/175 155/175
More Options
WAKE FOREST WAKE FOREST
4/0 AWG 4/0 AWG
7.9 20.07
5078 2303.34
0.084 0.13
0.105 0.16
0.041 0.06
180/205 180/205
More Options
RUST RUST
250 KCMIL 250 KCMIL
8.8 22.35
6000 2721.55
0.070 0.10
0.087 0.13
0.041 0.06
205/230 205/230
More Options
SLIPPERY ROCK SLIPPERY ROCK
350 KCMIL 350 KCMIL
12 30.48
8400 3810.17
0.051 0.08
0.064 0.10
0.040 0.06
250/280 250/280
More Options
WOFFORD WOFFORD
500 KCMIL 500 KCMIL
13.8 35.05
12000 5443.10
0.036 0.05
0.045 0.07
0.039 0.06
310/350 310/350
More Options
WESTMINSTER WESTMINSTER
750 KCMIL 750 KCMIL
16.8 42.67
18000 8164.66
0.023 0.03
0.030 0.04
0.038 0.06
385/435 385/435

Notes:
1. Inductive reactance assumes cables are cradled in conduit, and the neutral is carrying no current.
2. Triple parallel inductive reactance calculation assumes the phase conductors are adjacent to one another.
3. Conductors assumed to be reverse lay stranded, compressed construction.
4. Phase spacing assumes cables are touching.
5. Resistances shown are for the Phase conductors only.
6. Ampacity based on 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor.

Standards & References

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • UL 854 Service Entrance Cable
  • ICEA S-105-692 Standard For 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables

Construction

  1. Conductor:Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Neutral:Cross Linked Polyethylene (XLPE) with three Yellow Extruded Stripes (YES)

For information about our Cable-Rejuvenation Services please visit us at:   Cable-Rejuvenation Services
You can email us at: Cable-Rejuvenation Services