Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. Green DuragroundTM also available.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
649139 |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
80
2.03
|
|
|
528
13.41
|
396
589
|
|
649088 |
1
1
|
2/0 AWG
2/0 AWG
|
19
19
|
80
2.03
|
|
|
572
14.53
|
488
726
|
|
649148 |
1
1
|
3/0 AWG
3/0 AWG
|
19
19
|
80
2.03
|
|
|
622
15.80
|
603
897
|
|
649097 |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
80
2.03
|
|
|
666
16.92
|
745
1109
|
|
649045 |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
95
2.41
|
|
|
966
24.54
|
1706
2539
|
|
649048 |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
110
2.79
|
|
|
1200
30.48
|
2550
3794
|
|
649130 |
1
1
|
1000 KCMIL
1000 KCMIL
|
61
61
|
110
2.79
|
|
|
1349
34.26
|
3354
4992
|
|