Predominantly used for primary underground distribution in conduit systems suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 28,000 volts or less and at conductor temperatures not to exceed 90°C for normal operation.
| Conductor | ||||||
| No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | |
| More Options |
1
1
|
1/0 AWG
1/0 AWG
|
18
18
|
280
7.11
|
1244
31.60
|
760
1131
|
| More Options |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
280
7.11
|
1260
32.01
|
774
1152
|
| More Options |
1
1
|
2/0 AWG
2/0 AWG
|
18
18
|
280
7.11
|
1284
32.62
|
798
1187
|
| More Options |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
280
7.11
|
1781
45.24
|
1638
2438
|
| More Options |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
280
7.11
|
2033
51.65
|
2269
3376
|
| More Options |
1
1
|
1000 KCMIL
1000 KCMIL
|
61
61
|
280
7.11
|
2167
55.06
|
2755
4100
|
Southwire 28kV HI-DRI Primary UD TRXLP Cable meets or exceeds the following ASTM specifications:
The cable is composed of a moisture blocked unilay compact stranded 1350-H16/26 aluminum phase conductor, covered by a semi-conducting cross-linked polyethylene strand shield, a tree-retardant cross-linked polyethylene primary insulation, and a semi-conducting cross-linked polyethylene insulation shield. Conductors are available with 100% insulation level. A concentric neutral of bare copper wires and a sunlight resistant, -40°C rated, insulating linear low density polyethylene jacket are applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. Has red extruded stripes.