SPEC: 10015

SIMpull XHHW-2®/RW90 Aluminum with AlumaFlex® Brand Conductors SPEC10015

Power Cable 600 or 1000 Volts. Alumaflex® Brand Aluminum Alloy (AA-8176) Conductor. Cross-linked Polyethylene (XLPE) Insulation. Moisture Resistant High Heat.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire SIMpull XHHW-2®/RW90 with AlumaFlex® Brand Conductors Wire & Cable with Alumaflex® Brand conductors are primarily used in conduit and cable trays for services, feeders and branch circuits in commercial or industrial applications as specified in the National Electrical Code. XHHW-2/RW90 conductors is suitable for use in wet or dry locations at temperatures not to exceed 90°C. Voltage for all applications is up to 1000 volts. Suitable for use in Health Care Facilities per section 517.160 of the NEC where a dielectric constant of 3.5 or less may be specified. This cable can be installed without application of pulling lubricant. RW90 is for open wiring and use in raceways (except cable troughs and ventilated flexible cableways) in dry or wet locations as per Canadian Electrical Code. For open wiring exposed to the weather.

Southwire Aluminum SIMpull® XHHW-2/RW90 conductors comply with the following:
- Federal Specification AA-59544
- NOM-ANCE, XHHW-2, 90ºC
- CT Rated- Sizes 1/0 AWG and larger
- FT4 350 Kcmil and larger
- National Electrical Code
- Gas and Oil Resistant II- All sizes
- Sunlight Resistant- Sizes 6 AWG and larger
- RoHS/Reach Compliant

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Approx. OD (inches) (cm) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
6 AWG 6 AWG
1 1
7 7
0.169 0.43
45 1.14
0.259 0.66
0.265 0.67
24 36
40 60
More Options
4 AWG 4 AWG
1 1
7 7
0.213 0.54
45 1.14
0.303 0.77
0.309 0.78
39 58
58 86
More Options
2 AWG 2 AWG
1 1
6 6
0.268 0.68
45 1.14
0.358 0.91
0.364 0.92
62 92
86 128
More Options
1 AWG 1 AWG
1 1
8 8
0.299 0.76
55 1.40
0.409 1.04
0.415 1.05
78 116
110 164
More Options
1/0 AWG 1/0 AWG
1 1
10 10
0.336 0.85
55 1.40
0.446 1.13
0.452 1.15
99 147
134 199
More Options
2/0 AWG 2/0 AWG
1 1
12 12
0.376 0.96
55 1.40
0.486 1.23
0.492 1.25
125 186
163 243
More Options
3/0 AWG 3/0 AWG
1 1
15 15
0.423 1.07
55 1.40
0.533 1.35
0.539 1.37
158 235
200 298
More Options
4/0 AWG 4/0 AWG
1 1
19 19
0.475 1.21
55 1.40
0.585 1.49
0.591 1.50
199 296
246 366
More Options
250 KCMIL 250 KCMIL
1 1
22 22
0.52 1.32
65 1.65
0.65 1.65
0.658 1.67
235 350
296 440
More Options
300 KCMIL 300 KCMIL
1 1
21 21
0.57 1.45
65 1.65
0.7 1.78
0.708 1.80
282 420
350 521
More Options
350 KCMIL 350 KCMIL
1 1
35 35
0.616 1.56
65 1.65
0.746 1.89
0.754 1.92
329 490
401 597
More Options
400 KCMIL 400 KCMIL
1 1
35 35
0.659 1.67
65 1.65
0.789 2.00
0.797 2.02
376 560
453 674
More Options
500 KCMIL 500 KCMIL
1 1
34 34
0.736 1.87
65 1.65
0.866 2.20
0.874 2.22
471 701
556 827
More Options
600 KCMIL 600 KCMIL
1 1
37 37
0.813 2.07
80 2.03
0.973 2.47
0.981 2.49
565 841
679 1010
More Options
700 KCMIL 700 KCMIL
1 1
58 58
0.877 2.23
80 2.03
1.037 2.63
1.045 2.65
659 981
781 1162
More Options
750 KCMIL 750 KCMIL
1 1
61 61
0.908 2.31
80 2.03
1.068 2.71
1.076 2.73
706 1051
832 1238
More Options
750 KCMIL 750 KCMIL
1 1
61 61
0.908 2.31
80 2.03
1.068 2.71
1.076 2.73
706 1051
832 1238
More Options
900 KCMIL 900 KCMIL
1 1
58 58
0.999 2.54
80 2.03
1.159 2.94
1.167 2.96
861 1281
986 1467
More Options
1000 KCMIL 1000 KCMIL
1 1
61 61
1.117 2.84
80 2.03
1.277 3.24
1.228 3.12
942 1402
1088 1619

* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
6 AWG 6 AWG
1 1
1.1 2.79
157 71.21
0.674 1.00
0.840 1.25
0.051 0.08
50 50
55 55
More Options
4 AWG 4 AWG
1 1
1.2 3.05
250 113.40
0.424 0.63
0.528 0.79
0.048 0.07
65 65
75 75
More Options
2 AWG 2 AWG
1 1
1.5 3.81
398 180.53
0.266 0.40
0.331 0.49
0.045 0.07
90 90
100 100
More Options
1 AWG 1 AWG
1 1
1.7 4.32
502 227.70
0.211 0.31
0.263 0.39
0.046 0.07
100 100
115 115
More Options
1/0 AWG 1/0 AWG
1 1
1.8 4.57
633 287.12
0.167 0.25
0.208 0.31
0.044 0.07
120 120
135 135
More Options
2/0 AWG 2/0 AWG
1 1
2 5.08
798 361.97
0.133 0.20
0.166 0.25
0.043 0.06
135 135
150 150
More Options
3/0 AWG 3/0 AWG
1 1
2.2 5.59
1006 456.31
0.105 0.16
0.131 0.19
0.042 0.06
155 155
175 175
More Options
4/0 AWG 4/0 AWG
1 1
2.4 6.10
1269 575.61
0.084 0.13
0.105 0.16
0.041 0.06
180 180
205 205
More Options
250 KCMIL 250 KCMIL
1 1
2.6 6.60
1500 680.39
0.070 0.10
0.087 0.13
0.041 0.06
205 205
230 230
More Options
300 KCMIL 300 KCMIL
1 1
2.8 7.11
1800 816.47
0.059 0.09
0.074 0.11
0.041 0.06
230 230
260 260
More Options
350 KCMIL 350 KCMIL
1 1
3 7.62
2100 952.54
0.051 0.08
0.064 0.10
0.040 0.06
250 250
280 280
More Options
400 KCMIL 400 KCMIL
1 1
3.2 8.13
2400 1088.62
0.044 0.07
0.055 0.08
0.040 0.06
270 270
305 305
More Options
500 KCMIL 500 KCMIL
1 1
3.5 8.89
3000 1360.78
0.036 0.05
0.045 0.07
0.039 0.06
310 310
350 350
More Options
600 KCMIL 600 KCMIL
1 1
3.9 9.91
3600 1632.93
0.030 0.04
0.038 0.06
0.039 0.06
340 340
385 385
More Options
700 KCMIL 700 KCMIL
1 1
5.2 13.21
4200 1905.09
0.026 0.04
0.034 0.05
0.038 0.06
375 375
425 425
More Options
750 KCMIL 750 KCMIL
1 1
5.4 13.72
4500 2041.16
0.023 0.03
0.030 0.04
0.038 0.06
385 385
435 435
More Options
750 KCMIL 750 KCMIL
1 1
5.4 13.72
4500 2041.16
0.023 0.03
0.030 0.04
0.038 0.06
385 385
435 435
More Options
900 KCMIL 900 KCMIL
1 1
5.8 14.73
5400 2449.40
0.019 0.03
0.025 0.04
0.037 0.06
425 425
480 480
More Options
1000 KCMIL 1000 KCMIL
1 1
6.1 15.49
6000 2721.55
0.017 0.03
0.023 0.03
0.037 0.06
445 445
500 500

* Ampacities based upon 2023 NEC Table 310.16 Raceway or Cable, Not more than 3 copper conductors on an ambient temperature of 30°C.
* Ampacities derived from the 2021 Canadian Electrical Code. - Table 4 - for Raceway or Cable. Not more than 3 aluminum conductors on an ambient temperature of 30°C.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

Size (strand) Black Red Blue White Brown Orange Yellow Gray Green Purple Pink Tan
8 (7) 8 (7)
455950 455950
138627 138627
6 (7) 6 (7)
112706
643836
643837
591212
591209
591210
591211
585321
4 (7) 4 (7)
112714
591114
591115
591116
591201
591202
591203
598051
585320
2 (6) 2 (6)
112722
643620
643621
592621
591213
591214
591215
598052
585319
1 (8) 1 (8)
112730
591204
591205
591206
591207
591208
591216
596497
585318
1/0 (10) 1/0 (10)
112748
591284
591285
591286
585291
585292
585293
585294
585290
596423
2/0 (12) 2/0 (12)
112755
591288
591289
591290
585296
585297
585298
585300
585295
596422
3/0 (16) 3/0 (16)
112763
585302
585303
585304
585305
585306
585308
585309
585301
4/0 (19) 4/0 (19)
585317
585316
585314
585313
585312
585311
585310
567439
250 (22) 250 (22)
278341
576390
576391
576392
576385
576386
576387
576388
567440
592468
300 (21) 300 (21)
278358
576382
576383
576384
576133
576134
576135
576136
576361
593380
350 (35) 350 (35)
278366
576378
576379
576380
576374
576375
576376
576377
567437
592562
669682
669683
400 (35) 400 (35)
278374
576370
576372
576373
576127
576129
576130
576131
567384
593379
455994
455995
500 (34) 500 (34)
278382
576367
576368
576369
576362
576364
576365
576366
576394
589196
669675
669681
600 (37) 600 (37)
278390
576350
576351
576352
576345
576346
576347
576349
567375
589197
700 (58) 700 (58)
278408
576341
576342
576343
576344
750 (61) 750 (61)
278416
592233
592234
592235
567432
567433
567434
567435
567436
592469
900 (56) 900 (56)
554059
671912
671915
671918
560445
560446
560447
560448
1000 (61) 1000 (61)
278424
138626 138626
138625 138625
672168 672168
662187
662321
662186
662541
653124

Standards & References

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • NMX-J-451-ANCE Thermoset insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements

Construction

  1. Conductor:Class B compact stranded bare aluminum per ASTM B800 and ASTM B801 or Single Input Wire (SIW) compact aluminum per ASTM B836
  2. Insulation:Flame-Retardant and Moisture-Resistant Thermoset Cross-Linked Polyethylene (XLPE) with Patented SIMpull® Technology in various colors