Southwire's Romex® SIMpull® NMD90 cables may be used for both exposed work in dry locations or concealed work in dry or damp locations.
The maximum allowable conductor temperature is 90°C. The minimum recommended installation temperature is -25°C for two-conductor cables
and -10°C for three-conductor cables (with suitable handling procedures). Material should be properly stored above 0°C for 24 hours prior to installation. The maximum voltage rating for all intended applications is 300 volts. Consult the Canadian Electrical Code for further information related to applications.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Ground Size | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
6 AWG
6 AWG
|
3
3
|
7
7
|
0.169
0.43
|
50
1.27
|
1 x 8
1 x 8
|
45
1.14
|
0.753
1.91
|
90
134
|
219
326
|
| More Options |
4 AWG
4 AWG
|
3
3
|
7
7
|
0.212
0.54
|
50
1.27
|
1 x 6
1 x 6
|
80
2.03
|
0.934
2.37
|
144
214
|
358
533
|
| More Options |
2 AWG
2 AWG
|
3
3
|
6
6
|
0.268
0.68
|
50
1.27
|
1 x 6
1 x 6
|
80
2.03
|
1.067
2.71
|
214
318
|
468
696
|
* Strand count meets minimum number per ASTM
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
6 AWG
6 AWG
|
3
3
|
3.000
7.62
|
0.674
1.00
|
0.812
1.21
|
0.051
0.08
|
50
50
|
55
55
|
| More Options |
4 AWG
4 AWG
|
3
3
|
3.700
9.40
|
0.424
0.63
|
0.510
0.76
|
0.048
0.07
|
65
65
|
75
75
|
| More Options |
2 AWG
2 AWG
|
3
3
|
5.300
13.46
|
0.267
0.40
|
0.321
0.48
|
0.045
0.07
|
90
90
|
100
100
|
* Ampacity values based on Canadian Electrical Code, Part 1 2024 Table 4. See also CEC Rules 4-004 and 4-006 for additional requirements.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.