| NM-B
(SPEC 10028) |
- Consists of two, three, or four insulated phase conductors plus a bare grounding conductor, all under an overall jacket
- Primarily used as branch circuit wiring for outlets, switches, and other general purpose and dedicated circuits in indoor residential locations
- For indoor dry locations only
|
NO |
NO |
NO |
Yes |
NO |
| UF-B
(SPEC 10036) |
- Consists of two or three insulated phase conductors with or without a bare grounding conductor, all encased in an overall jacket
- Generally used for feeder and branch circuits for outside post lamps, pumps, swimming pools/hot tubs, workshops, and other loads and apparatuses
- Can be used in place of NM-B2
|
YES |
YES |
NO3 |
YES |
YES4 |
| SER (SPEC 10041,SPEC 10052) |
- Consists of two, three, or four insulated conductors plus a bare neutral/grounding conductor5, all under a binder tape and an overall jacket
- Insulated conductors identified with colored stripes
- Cable is round
- Primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard
- Can be used anywhere SE cables are permitted
|
NO |
NO |
NO3 |
YES6 |
YES7 |
| SEU (SPEC 10040,SPEC 10043,SPEC 10050) |
- Consists of two insulated conductors plus a concentric neutral/grounding conductor5, all under a binder tape and an overall jacket
- Cable is flat/oval
- Primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard
- Can be used anywhere SE cables are permitted
|
NO |
NO |
NO3 |
YES6 |
YES7 |
| MHF (SPEC 10054) |
- Consists of four RHH/RHW-2/USE-2 conductors twisted together
- Neutral conductor has white striping
- Grounding conductor is colored green
- Intended for the connection of mobile homes to a supply of electricity
where permanent wiring is required, as specified in the NEC1
- Can also be used anywhere RHH/RHW-2/ USE-2 conductors are permitted
(see below)
|
YES |
YES |
NO |
YES8 |
YES8 |
| THHN/THWN(-2) (SPEC 10000, SPEC 10003, SPEC 10012) |
- Primarily used in conduit and cable trays for service, feeder, and branch circuits in
commercial and industrial applications
- Can also be used in residential applications
|
NO |
YES |
NO |
YES8 |
YES8 |
| XHHW-2 (SPEC 10005, SPEC 10006, SPEC 10015) |
- Primarily used in conduit and cable trays for service, feeder, and branch circuits
in commercial and industrial applications
- Can also be used in residential applications
|
NO |
YES |
NO |
YES8 |
YES8 |
| RHH/RHW-2/USE-2 (SPEC 10010, SPEC 10020) |
- Primarily used as underground service entrance conductors
- Can also be used for feeder and branch circuits
|
YES |
YES |
NO |
YES8 |
YES8 |
| URD (URD Specs) |
- Consists of two, three, or four insulated conductors twisted together
- Neutral conductor has three yellow stripes
- Typically used by the utility company, not homeowners
- Meant to connect a pad-mounted transformer to a meter box
- May lack the ratings necessary for applications subject to NEC1jurisdiction
|
YES |
YES |
NO |
NO9 |
YES10 |
| Service Drop (Service Drop Specs) |
- Consists of one, two, or three insulated conductors twisted together with a
bare neutral
- Meant to connect a pole-mounted transformer to a meter box
- NOT UL-rated and cannot be used in applications subject to NEC1 jurisdiction
|
NO |
NO |
YES11 |
NO |
NO |