SPEC 25075 DURATRAY™ CU 1000V XLPE Insulation. RHH/RHW-2/RW90 UL & CSA

Single Copper Conductors, XLPE Insulation, Sunlight Resistant, 1000V, 90ºC MAX, -40ºC MIN, Gasoline & Oil Resistant

Download Category Specifications
Excel Table

Application

Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. Green DuragroundTM also available.

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
694140
1 1
1/0 AWG 1/0 AWG
19 19
80 2.03
528 13.41
394 587
649089
1 1
2/0 AWG 2/0 AWG
19 19
80 2.03
572 14.53
486 723
649149
1 1
3/0 AWG 3/0 AWG
19 19
80 2.03
622 15.80
601 895
649098
1 1
4/0 AWG 4/0 AWG
19 19
80 2.03
666 16.92
744 1107
649108
1 1
350 KCMIL 350 KCMIL
37 37
95 2.41
841 21.36
1216 1810
649047
1 1
500 KCMIL 500 KCMIL
37 37
95 2.41
966 24.54
1703 2534
649049
1 1
750 KCMIL 750 KCMIL
61 61
110 2.79
1200 30.48
2545 3787
649131
1 1
1000 KCMIL 1000 KCMIL
61 61
110 2.79
1349 34.26
3349 4984
649108
1 1
350 KCMIL 350 KCMIL
37 37
95 2.41
841 21.36
1216 1810

Standards & References

  • ASTM B3: Soft or Annealed Copper Wire
  • ASTM B8: Concentric-Lay-Stranded Copper Conductors
  • ASTM B230: Aluminum, 1350-H19 Wire for Electrical Purposes
  • CSA C22.2 No. 38: Thermoset-insulated wires and cables
  • CSA C22.2 No.230: Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 & No. 0.3: Wire and Cable Test Methods
  • CSA: LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA: SUN RES - for Sunlight Resistant rating
  • CSA: ST1 Smoke Test - marked FT4-ST1 (1/0 and Larger)
  • Oil Res: I & Sun Res - AWG 8 & Larger

Construction

  • Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  • Insulation: Cross Linked Polyethylene (XLPE)