Southwire’s 5KV TECK 90, 5000V, non-shielded, EPR insulated power cable is a CSA approved armoured cable for industrial and commercial medium voltage applications. FT4, -40°C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and is concrete encaseable. <br> <ul> <li>-40°C - CSA Cold Bend and Impact Temperature</li> <li> -25°C - Min. Installation Temperature</li> <li> 90°C - Max. Continuous Operating Temperature</li> <li> 140°C for Emergency Overload Temperature</li> <li>250°C for Short Circuit Temperature</li> </ul>
Cond. Size (AWG/Kcmil) | 1 1 | |
Cond. Strands | 19 19 | |
Diameter Over Conductor (in) (cm) | 0.322 0.82 | inch cm |
Insulation Thickness (mils) (mm) | 90 2.29 | mils mm |
Inner Jacket Thickness (mils) (mm) | 85 2.16 | mils mm |
Diameter Over Armor (in) (cm) | 1.682 4.27 | inch cm |
Jacket Thickness (mils) (mm) | 55 1.40 | mils mm |
Approx. OD (in) (cm) | 1.792 4.55 | inch cm |
Approx. Weight (lbs/1000') (kgs/km) | 1788 2661 | lbs/1000' kgs/km |
Max Pull Tension (lbs) (kg) | 2008 910.81 | lbs kg |
Min. Bend Radius (in) (cm) | 12.5 31.75 | inch cm |
* Other conductor sizes and outer jacket colours are available upon request. (#s in brackets represent # of strands / conductor. Number of strands may vary as per CSA standard.)