Southwire’s 600 Volt or 1000 Volt SOLONONplus® Type XHHW-2 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
673577 |
1
1
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
129
3.29
|
20
29
|
|
673578 |
1
1
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
147
3.74
|
28
42
|
|
673614 |
1
1
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
173
4.39
|
42
62
|
|
673560 |
1
1
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
|
|
236
5.99
|
71
106
|
|
673629 |
1
1
|
6 AWG
6 AWG
|
7
7
|
45
1.14
|
|
|
272
6.91
|
105
157
|
|
673645 |
1
1
|
4 AWG
4 AWG
|
7
7
|
45
1.14
|
|
|
319
8.10
|
159
236
|
|
673881 |
1
1
|
3 AWG
3 AWG
|
7
7
|
45
1.14
|
|
|
346
8.79
|
195
291
|
|
673652 |
1
1
|
2 AWG
2 AWG
|
7
7
|
45
1.14
|
|
|
371
9.42
|
241
358
|
|
673677 |
1
1
|
1 AWG
1 AWG
|
19
19
|
55
1.40
|
|
|
438
11.13
|
309
461
|
|
673664 |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
55
1.40
|
|
|
478
12.14
|
383
570
|
|
673904 |
1
1
|
2/0 AWG
2/0 AWG
|
19
19
|
55
1.40
|
|
|
522
13.26
|
474
705
|
|
673917 |
1
1
|
3/0 AWG
3/0 AWG
|
19
19
|
55
1.40
|
|
|
572
14.53
|
588
875
|
|
673929 |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
55
1.40
|
|
|
614
15.60
|
729
1085
|
|
673941 |
1
1
|
250 KCMIL
250 KCMIL
|
37
37
|
65
1.65
|
|
|
678
17.22
|
868
1291
|
|
673955 |
1
1
|
350 KCMIL
350 KCMIL
|
37
37
|
65
1.65
|
|
|
777
19.74
|
1193
1775
|
|
673978 |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
65
1.65
|
|
|
902
22.91
|
1676
2495
|
|
673990 |
1
1
|
600 KCMIL
600 KCMIL
|
61
61
|
80
2.03
|
|
|
1008
25.60
|
2031
3023
|
|