SPEC 45441 CU 600V XLPE Insulation Shielded Signal Pair TPE jacket. RHH/RHW-2 Variable Frequency Drive (VFD)

Type TC-ER Variable Frequency Drive Cable, 600 Volts or 1000 Volts , Tinned Copper Conductors, Cross Linked Insulation Type RHH/RHW-2 With Shielded Pair, Thermoplastic Elastomer Jacket, Rated 90°C Dry or Wet, -40°C Cold Impact, Identification Method 4. 1000 Volts Flexible Motor Supply. CSA CIC/TC FT4 Flame.

Download Category Specifications
Excel Table

Application

Applications and Features: Power supply cable for VFDs and motors, suitable for cable tray, conduit, raceways, (TC-ER) and machine tool wiring conforming to NFPA 79 2018. Suitable for free air and direct burial. Its flexible design is ideal for use on operation processes in accordance with NEC® Articles 336, 501 and 502 including, but not limited to: fans, pumps, conveyors, compressors, elevators and lifts, extruders, crushers and presses, assembly lines, food and beverage, wind energy and data centers. Cable is rated for -40C Cold Bend and Impact. Multiple approvals for multiple applications. The additional shielded pair can be used for signal, temperature sensors or brake.

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
646241
6 6
16 AWG 16 AWG
26 26
45 1.14
16 16
663 16.85
226 337
646242
6 6
14 AWG 14 AWG
41 41
45 1.14
14 14
703 17.88
272 405
646243
6 6
12 AWG 12 AWG
65 65
45 1.14
12 12
705 17.92
319 474
646244
6 6
10 AWG 10 AWG
105 105
45 1.14
10 10
777 19.75
424 631
677156
8 8
8 AWG 8 AWG
168 168
60 1.52
1028 26.11
654 973
677158
8 8
6 AWG 6 AWG
266 266
60 1.52
1054 26.77
846 1258

Standards & References

  • ASTM B33: Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172: Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174: Standard Specification for Bunch-Stranded Copper
  • UL 44: Thermoset-Insulated Wires and Cables
  • UL 758: Standard for Appliance Wiring Material Style 20886
  • UL 1277: Type TC-ER Standard Power and Control Cables (1000V 14AWG and Larger)
  • UL 2277: Flexible Motor Supply Cable and Wind Turbine Tray Cable
  • CSA C22.2 No. 210: Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230: Tray Cables - Rated TC
  • CSA C22.2 No. 239: Control and instrumentation cables
  • CE/RoHS-2: – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79: Electrical Standard for Industrial Machinery
  • Made in America:: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  • Conductor: Class K, flexible stranded tinned annealed copper per ASTM B3, B172, and B174
  • Insulation: Cross linked insulation on all conductors (Type RHH/RHW-2 on 14 AWG and larger)
  • Ground: One green ground with yellow stripe cross linked insulation (size equal to phase conductor)
  • Drain Wire: Tinned copper drain wire
  • Twisted Shielded Pair: 100% coverage aluminum/Mylar foil shield (color code: black, white)
  • Overall Shielding: 100% coverage aluminum/Mylar/aluminum foil, overall 85% coverage tinned copper braid
  • Jacket: Black Thermoplastic Elastomer (TPE)