SPEC 45411 CU 2000V XLPE Insulation. RHH/RHW-2 PV

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Copper Conductor XLPE Insulation. Sizes 14 AWG through 1000 Kcmil. Heat, Moisture, Sunlight Resistant RoHS. 90°C

Download Category Specifications
Excel Table

Application

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
597958
1 1
12 AWG 12 AWG
19 19
75 1.91
243 6.17
40 59
579962
1 1
10 AWG 10 AWG
19 19
75 1.91
263 6.68
53 80
569037
1 1
8 AWG 8 AWG
19 19
85 2.16
313 7.95
80 118
569039
1 1
6 AWG 6 AWG
19 19
85 2.16
349 8.86
114 170
569040
1 1
4 AWG 4 AWG
19 19
85 2.16
396 10.06
168 250
569043
1 1
1/0 AWG 1/0 AWG
19 19
105 2.67
570 14.48
397 590
569044
1 1
2/0 AWG 2/0 AWG
19 19
105 2.67
614 15.60
489 728
578324
1 1
500 KCMIL 500 KCMIL
37 37
120 3.05
1006 25.55
1685 2508

Standards & References

  • ASTM B3: Soft or Annealed Copper Wire
  • ASTM B8: Concentric-Lay-Stranded Copper Conductors
  • ASTM B787: 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 44: Thermoset-Insulated Wires and Cables
  • UL 4703: Standard for Photovoltaic Wire
  • Made in America:: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • VW-1: Vertical-Wire Flame Test (Optional)

Construction

  • Conductor: Stranded bare copper per ASTM B3 and ASTM B8 or ASTM B787
  • Insulation: Cross Linked Polyethylene (XLPE). Colors available upon request.

Resources

There are no downloadable resources for this product.